Plan Review Notes For Permit 03040114
Permit Number 03040114
Review Stop B
Sequence Number 1
Notes
Date Text
2003-04-28 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS WITH UPDATED SBCCI REPORT
 THAT MATCHES ENGINEERED DRAWINGS.
 CHECK DESIGN PRESSURES AND MAX/MIN
 PANEL SPAN SHOWN ON THE INSTALLATION
 SCHEDULE AND THOSE SHOWN ON ENGINEERED
 DRAWINGS AND REVISE AS REQUIRED.SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 2-REVISE DETAIL S21 FOR COLUMN BETWEEN
 GARAGE AND STAIRWAY TO MATCH CONDITION
 SHOWN ON 2ND FLOOR FRAMING PLAN. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 3-REVISE CONNECTOR TC-1 SHOWN ON ROOF
 FRAMING PLAN FOR FRONT FRAMED WALL.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 4-WINDOW 34SH DOESN'T PROVIDE THE 24"
 CLEAR HEIGHT REQUIRED BY SEC. 1005.4
 FBC 2001. REVISE AS REQUIRED.
 ALSO, MAKE CHECK THAT WINDOW SH24+5
 PROVIDES 24" CLEAR HEIGHT AND 5.7 S.F.
 CLEAR OPENING. SEC. 1005.4 FBC 2001.
 5-RESUBMIT ENERGY CALCULATIONS WITH THE
 ENGINEER'S ORIGINAL SIGNATURE & SEAL.
 CHAPTER 471 FLORIDA STATUTES AND SEC.
 103.0 CHAPTER 13 FBC 2001.