2003-04-10 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE PANEL SCHEDULE, SHOW
 FOUR COND UNITS? PLEASE ALSO SEE OCP
 SHOWN AS 2-P 30A,PLEASE SEE 7.5KW LOAD
 SHOWN FOR AHU/HEAT. PLEASE CORRELATE
 AND SIZE OCP PER 424-3
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED
 PANEL SCHEDULE. 215-5
  
 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215-3/230-42 ETC.
  
 4)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SIGN CIRCUIT REQ`D PER 600-5
  
 5)NOTE: PLEASE SEE 700-12E FOR CIRCUIT-
 -ING FO EM/EXT LTS. SAME AS GEN LTS.
  
 6)NOTE: PLEASE CLARIFY/SHOW NEW OR EXIST
 -ING SHOW WINDOW RECEPTS 210-62/220-12
  
 7)NOTE: PLEASE SEE SEE SIZE OPENING FOR
 ACCESS TO ELECTRICAL ROOM, @ 1/8 SCALE
 IT APPEARS DOOR IS LESS THAN 2' WIDE?
 110-26
  
 8)NOTE: PLEASE NOTE, MAX OCP FOR WATER
 HEATER CAN NOT EXCEED 150% OF LOAD.
 WATER HEATER IS SHOWN AS HAVING 40A
 OCP.422-11
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]
  
 9)NOTE: PLEASE CLARIFY REQ`D ROOFTOP
 RECEPT. 210-63