2003-04-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03040061
 ADD: 2316 S DIXIE HWY
 CONT: MIKE MOORE CONST
 TEL: (561)745-1054
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) WHAT TYPE OF OCCUPANCY IS THIS STRUC-
 TURE TO BE USED FOR? EXITING MERCANTILE
 VS BUSSINESS SEE EXCEPTIONS 1018.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 IDENTIFY ROOM USAGE?
  
 3) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 4)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGTH IN ACCORDANCE WITH TABLE 1511.7.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026