2003-04-14 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 03040061 |
| ADD: 2316 S DIXIE HWY |
| CONT: MIKE MOORE CONST |
| TEL: (561)745-1054 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1) WHAT TYPE OF OCCUPANCY IS THIS STRUC- |
| TURE TO BE USED FOR? EXITING MERCANTILE |
| VS BUSSINESS SEE EXCEPTIONS 1018. |
| |
| 2)FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| IDENTIFY ROOM USAGE? |
| |
| 3) TABLE 803.3 MINIMUM INTERIOR FINISH |
| CLASSIFICATION; PROVIDE INFORMATION |
| BASED ON INTERIOR FINISH REQUIREMENTS |
| BASED ON OCCUPANCY. |
| |
| 4)1511.7 ROOF MOUNTED MECHANICAL UNIT |
| S SHALL BE MOUNTED ON CURBS RAISED A |
| MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| FACE, OR WHERE ROOFING MATERIALS EXTEND |
| BENEATH THE UNIT, ON RAISED EQUIPMENT |
| SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| HEIGTH IN ACCORDANCE WITH TABLE 1511.7. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| JIM WITMER |
| BUILDING PLAN REVIEW |