Plan Review Notes For Permit 03032421 |
Permit Number |
03032421 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-06-17 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE SOIL TEST REPORT PRIOR TO | | CONSTRUCTION. SOIL TEST REPORT IN FILE | | IS PRELIMINARY ONLY AND IT REQUIRES | | ADDITIONAL BORINGS TO BE PERFORMED. | | SEE LIMITATIONS ON PRELIMINARY REPORT. | | 2-UPDATE TRUSS ANCHOR SCHEDULE AND ALL | | DETAILS THAT ARE AFFECTED BY SECTION | | 1609.4.3 FBC 2001, WHICH DOESN'T ALLOW | | THE STRESS INCREASE TO BE USED. | | **NOTE: ANCHORS HIGHLIGHTED ON THE USP | | 2003 CATALOGUE ARE THE ONLY ONES THAT | | DON'T INCLUDE THE INCREASE. OTHERS DO. | | SEE FOOTNOTE ON USP 2003 CATALOGUE. | | 3-REVISE DETAIL 2/A3. THIS CAN NOT BE A | | BEARING WALL ACCORDING TO THE SPECS | | SHOWN. SEC. 104.2.1.2 CITY AMENDMENTS | | TO FBC 2001. | | 4-MISSING PRODUCT APPROVAL FOR SINGLE | | HUNG WINDOWS. |
|