2003-06-17 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE SOIL TEST REPORT PRIOR TO
 CONSTRUCTION. SOIL TEST REPORT IN FILE
 IS PRELIMINARY ONLY AND IT REQUIRES
 ADDITIONAL BORINGS TO BE PERFORMED.
 SEE LIMITATIONS ON PRELIMINARY REPORT.
 2-UPDATE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC 2001, WHICH DOESN'T ALLOW
 THE STRESS INCREASE TO BE USED.
 **NOTE: ANCHORS HIGHLIGHTED ON THE USP
 2003 CATALOGUE ARE THE ONLY ONES THAT
 DON'T INCLUDE THE INCREASE. OTHERS DO.
 SEE FOOTNOTE ON USP 2003 CATALOGUE.
 3-REVISE DETAIL 2/A3. THIS CAN NOT BE A
 BEARING WALL ACCORDING TO THE SPECS
 SHOWN. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
 4-MISSING PRODUCT APPROVAL FOR SINGLE
 HUNG WINDOWS.