2003-05-01 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE SOIL TEST REPORT PRIOR TO
 CONSTRUCTION.
 2-SHEET C-1: SPECIFY THE APPLICABLE
 INTERNAL PRESSURE COEFFICIENT ON THE
 DESIGN INFORMATION AS REQUIRED BY SEC.
 1606.1.7 FBC 2001.
 3-PROVIDE COMPLETE DETAIL/SPECIFICATIONS
 FOR HANGING AIR HANDLER UNIT FROM
 TRUSSES. SPECIFY ALL FASTENERS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 4-PROVIDE SPECIFICATIONS FOR FIREBLOCK'G
 AT ALL CONCEALED SPACES AS REQUIRED BY
 SEC. 2305 FBC 2001. INCLUDING STAIRS.
 5-PROVIDE COMPLETE DETAILS AND SPECS FOR
 HANDRAIL HEIGHT AND OPENINGS ALLOWANCE
 AS REQUIRED BY SEC. 1007.5 FBC 2001.
 6-SPECIFY SAFETY GLASS FOR WINDOW AT
 COVERED ENTRY. SEC. 2405.2 FBC 2001.
 7-CLARIFY WHAT IS THE DETACHABLE SAFETY
 RAIL SPECIFIED ON ELEVATION ON SHEET
 A-4. SEC. 104.2.1.2 CITY AMENDMENTS.
 8-UPDATE TRUSS SCHEDULE. SEE UPDATED
 USP CATALOGUE (2003). ALSO, PROVIDE
 ENGINEERING CALCULATIONS FOR VALUES
 OTHER THAN THOSE SHOWN BY USP. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 **NOTE: ALSO CONSIDER THAT IF USING 10D
 NAILS, THEN IT NEEDS 1 3/4" MINIMUM
 PENETRATION TO USE THIS VALUES. ONE
 TRUSS DOESN'T HAVE THIS THICKNESS.
 9-ROOF FRAMING PLAN: REVISE CONNECTORS
 SPECIFIED FOR FRAMED WALLS. NEED WOOD
 TO WOOD CONNECTORS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 10-PROVIDE COMPLETE DETAILS & STRUCTURAL
 INFORMATION FOR PRECAST GUARDRAIL TO
 BE USED ON 2ND FLOOR BALCONY.SECTION
 1015 FBC 2001 AND SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 11-SHEET A-1: CLARIFY FOOTING AT GARAGE
 INTERIOR BEARING WALL. F8 OR TE-1?.
 DETAIL #2 DOESN'T APPLY AT GARAGE.
 REVISE AS REQUIRED.
 DETAIL 38 NEED 12" MIN. BELOW GRADE.
 12-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS UNDER A SEPARATE
 PERMIT.