2003-07-24 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 11 |
| FBC-2001 AMENDMENTS, CHAPTER |
| ONE, ADMIN. CODE |
| |
| 1) FROM PREVIOUS REVIEW: SHOW DETAIL FOR |
| TOILET ROOMS. FOR WATER CLOSETS SHOW |
| CLEAR FLOOR SPACE 11-4.16.2, HEIGHT |
| 11-4.16.3, GRAB BARS 11-4.16.4, AND |
| FLUSH CONTROLS 11-4.16.5. FOR LAVS SHOW |
| HEIGHT & CLEARANCES 11-4.19.2, CLEAR |
| FLOOR SPACE 11-4.19.3, EXPOSED PIPES |
| 11-4.19.4, AND FAUCETS 11-4.19.5. FOR |
| BREAK ROOM SINK SHOW HEIGHT 11-4.24.2, |
| KNEE CLEARANCES 11-4.24.3, DEPTH 11-4. |
| 24.4, CLEAR FLOOR SPACE 11-4.24.5, EX- |
| POSED PIPES & SURFACES 11-4.24.6, AND |
| FAUCETS 11-4.24.7. SECTION 104.2.1 - |
| INFORMATION SHALL BE SPECIFIC, AND THE |
| TECHNICAL CODES SHALL NOT BE CITED AS A |
| WHOLE OR IN PART, NOR SHALL THE TERM |
| "LEGAL" OR ITS EQUIVALENT BE USED AS A |
| SUBSTITUTE FOR SPECIFIC INFORMATION. |
| 2) TOILET ROOM FOR OFFICES #'S 4 & 5 IS |
| NOT A PRIVATE TOILET ROOM BUT A COMMON |
| USE TOILET ROOM AND SHALL BE ACCESSIBLE. |
| SEE COMMENT #1 FOR DETAILS REQUIRED FOR |
| TYPICAL ACCESSIBLE TOILET ROOM. ALSO |
| SHOW COMPLIANCE WITH 11-4.21 AND ALL |
| SUBSECTIONS. SIZE & CLEARANCE 11-4.21.2, |
| SEAT 11-4.21.3, GRAB BARS 11-4.21.4, |
| CONTROLS 11-4.21.5, & CURBS 11-4.21.7 |
| 3) NEW COMMENT, PER TABLE 403.1 A DRINK- |
| ING FOUNTAIN IS REQUIRED. ALSO SEE SECT- |
| ION 410.1 |
| 4) NEW COMMENT SUBMIT A WATER RISER DIA- |
| GRAM. WATER HAMMER ARRESTORS REQUIRED BY |
| SECTION 604.9 (AT DISHWASHER & ICE MAKER |
| IN REFRIG. IF INSTALLED), SHALL BE LOCA- |
| TED NEAR THE FIXTURE IN AN "EFFECTIVE |
| RANGE" AND NOT IN THE CEILING AT THE TOP |
| OF THE DROPS. |
| 5) PLEASE SEE ATTACHED SHEET CONCERNING |
| ARCHITECTS SEAL AND TITLE BLOCK REQUIRED |
| FOR EACH SHEET. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |