Plan Review Notes For Permit 03032368
Permit Number 03032368
Review Stop P
Sequence Number 2
Notes
Date Text
2003-07-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMIN. CODE
  
 1) FROM PREVIOUS REVIEW: SHOW DETAIL FOR
 TOILET ROOMS. FOR WATER CLOSETS SHOW
 CLEAR FLOOR SPACE 11-4.16.2, HEIGHT
 11-4.16.3, GRAB BARS 11-4.16.4, AND
 FLUSH CONTROLS 11-4.16.5. FOR LAVS SHOW
 HEIGHT & CLEARANCES 11-4.19.2, CLEAR
 FLOOR SPACE 11-4.19.3, EXPOSED PIPES
 11-4.19.4, AND FAUCETS 11-4.19.5. FOR
 BREAK ROOM SINK SHOW HEIGHT 11-4.24.2,
 KNEE CLEARANCES 11-4.24.3, DEPTH 11-4.
 24.4, CLEAR FLOOR SPACE 11-4.24.5, EX-
 POSED PIPES & SURFACES 11-4.24.6, AND
 FAUCETS 11-4.24.7. SECTION 104.2.1 -
 INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A
 WHOLE OR IN PART, NOR SHALL THE TERM
 "LEGAL" OR ITS EQUIVALENT BE USED AS A
 SUBSTITUTE FOR SPECIFIC INFORMATION.
 2) TOILET ROOM FOR OFFICES #'S 4 & 5 IS
 NOT A PRIVATE TOILET ROOM BUT A COMMON
 USE TOILET ROOM AND SHALL BE ACCESSIBLE.
 SEE COMMENT #1 FOR DETAILS REQUIRED FOR
 TYPICAL ACCESSIBLE TOILET ROOM. ALSO
 SHOW COMPLIANCE WITH 11-4.21 AND ALL
 SUBSECTIONS. SIZE & CLEARANCE 11-4.21.2,
 SEAT 11-4.21.3, GRAB BARS 11-4.21.4,
 CONTROLS 11-4.21.5, & CURBS 11-4.21.7
 3) NEW COMMENT, PER TABLE 403.1 A DRINK-
 ING FOUNTAIN IS REQUIRED. ALSO SEE SECT-
 ION 410.1
 4) NEW COMMENT SUBMIT A WATER RISER DIA-
 GRAM. WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9 (AT DISHWASHER & ICE MAKER
 IN REFRIG. IF INSTALLED), SHALL BE LOCA-
 TED NEAR THE FIXTURE IN AN "EFFECTIVE
 RANGE" AND NOT IN THE CEILING AT THE TOP
 OF THE DROPS.
 5) PLEASE SEE ATTACHED SHEET CONCERNING
 ARCHITECTS SEAL AND TITLE BLOCK REQUIRED
 FOR EACH SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692