2003-08-04 00:00:00 | **************** UNSAT ************ |
| |
| 1)NOTE: PLEASE CORRELATE RISER DIAGRAM, |
| PANEL ETC. PANEL SHOWN AS 225A,ON RISER, |
| 400A ON SCHEDULE AND400A OCP FEEDING |
| A 225A PANEL. LOAD SHOWN AT 257A'S ON |
| A 225A PANEL? |
| |
| 215/310-16/240/230/ ETC |
| |
| 2)NOTE: PLEASE SHOW LOAD CALCULATIONS |
| AS REQUESTED ON FIRST REVIEW. 220 |
| SEE ALL ART'S REFERENCED ON FIRST REVIEW |
| |
| 3)NOTE: PLEASE CLARIFY SOME CIRCUITING |
| SHOWN FOR EM/EXT LTS MISSING. PLEASE SEE |
| 700-12E FOR CIRCUITING. |
| |
| 4)NOTE: PLEASE CLARFIY LIGHTING SHOWN |
| AS REQ'D SIGN CIRCUIT? SHOWN AS WHAT |
| APPEARS TO BE FLOOD LTS? SYMBOL NOT |
| SHOWN ON ELECTRICAL LEGEND? |
| PLEASE SHOW REQ'D SIGN CIRCUIT AT |
| ENTRANCE PER 600-5 |
| |
| 5)NOTE: PLEASE CLARIFY TWO A/C SYSTEMS |
| NOW SHOWN ON PLANS AND ONLY ONE ON PANEL |
| SCHEDULE? PLEASE ALSO INCLUDE ON LOAD |
| CALCUALTIONS PER 220/215-5 |
| CIRCUIT #'S SHOWN ON PLANS BUT DO NOT |
| CORRELATE W/ PANEL SCHEDULE? |
| |
| 6)NOTE: PLEASE CLARIFY SEC`S, NOT SHOW- |
| -ING ANY CONDUCTOR SIZE FROM METER TO |
| MAIN? PLEASE ALSO SEE SIZE SHOWN FROM |
| MAIN TO PANEL AS 3-# 4/0 MCM,,,? |
| PLEASE SEE 310-16 FOR SIZING |
| |
| 7)NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| SYSTEM, PER 250-50 GRND RD, COLD WATER |
| ETC, IF AVAILABLE. |
| |
| 8)NOTE: PLEASE SEE COPY OF FS 553.80(2)- |
| (B) W/ RESPECT TO DESIGN PROFESSIONAL. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |