Plan Review Notes
Plan Review Notes For Permit 03032368
Permit Number 03032368
Review Stop B
Sequence Number 2
Notes
Date Text
2003-08-11 00:00:002ND REVIEW
 1)AS NOTED ON THE FIRST CHECKLIST THE
 OPENINGS IN THE EXTERIOR WALL ON THE
 SOUTH PROPERTY LINE ARE
 REQUIRED TO BE FIRE RATED, AND THE WEST
 WALL ARE PROHIBITTED BY FBC TABLE 600.
 THE ARCHITECT'S QUOTING OF FBC
 3401.7.2.4 IS WITHOUT STANDING FOR THIS
 PROJECT.SEE FBC 3401.7.2.6 AND REVISE
 AS NECESSARY.ALSO, SEE FBC 104.2.1
 WITH REGARDS TO QUOTING CODE SECTIONS
 NOT BEING AN ACCEPTABLE ALTERNATIVE TO
 SPECIFIC DESIGN INFORMATION.
  
 2) VERTICAL ACCESIBILITY IS REQUIRED
 FOR OFFICES SHOWN AS #4 AND #5 AS
 PREVIOUSLY NOTED.SEE FBC 11-4.1.5.6
 (1) (K) (III).
  
 3) THE STRUCTURAL CALCULATIONS
 PREVIOUSLY REQUESTED FOR THE SECOND
 FLOOR CONSTRUCTION HAVE NOT BEEN
 PROVIDED.
 THE DECLARED 1/2" X 5" BOLTS @ 4' ON
 CENTER SHOWN IN SECTION 2/A ON SHEET 3
 APPEARS TO BE VERY INADEQUATE FOR THE
 LOADS TO BE IMPOSED ON THE WOOD
 PERPENDICULAR TO THE GRAIN. HOW WAS THE
 MINIMAL 75# LIVE LOAD DETERMINED?
 PLEASE PROVIDE COMPLETE STRUCTURAL
 CALCULATIONS.
  
 4) THE STAIRS TO OFFICES 4 AND 5
 REQUIRE HANDRAILS ON EACH SIDE AN WITHIN
 30" OF THE WIDTH REQUIRED FOR EGRESS.
 SEE FBC 1007.5.2, FBC 1007.5.5 AND FBC
 1007.5.7.DO NOT QUOTE THOSE CODE
 SECTIONS BUT
 SHOW A GRAPHIC DEPICTION AND/OR NOTES
 TO CLEARLY SHOW THE DESIGN INTENT.
 INCLUDE FASTENING AND CONNECTION
 DETAILS.
  
 5) PLEASE PROVIDE THE FIRE DESIGN
 NUMBER FOR THE SEVERAL PLACES CALLING
 OUT "1 FIRE RATED" SEE FBC 701.5.
  
  
 6) SECTION 1/A, SHEET 3. THE STEEL
 COLUMN IS 3"X3"X WHAT?
  
 7) SECTION 3/A, WHAT ARE THE
 DIMENSIONS,MATERIAL AND CONNECTION
 METHODS?
  
 8) THE SIX INCH SPACE AT THE TOE RAIL
 OF THE GUARD RAIL SHOWN IN SECTION 3/A
 DOES NOT COMPLY WITH FBC 1015.3.IF THE
 GUARD RAIL IS A DELEGATED DESIGN SHOW
 MINIMUM REQUIRED LOADS AS PROVIDED FOR
 IN FBC 1608.2.2.
  
 9) THE SECOND FLOOR STAIRS ARE REQUIRED
 TO BE ENCLOSED WITH FIRE RATED
 CONSTRUCTION AND TO PROVIDE A PROTECTED
 PATH TO THE OUTSIDE.
 SEE FBC 1006.1.1 AND FBC 1010.1.
  
 10) TWO INDEPENDENT EXITS ARE REQUIRED
 FROM THE SECOND FLOOR.SEE FBC
 1004.2.1 AND 1027.1.FURTHER, THE
 TRAVEL DISTANCE IS >75' SO A SINGLE EXIT
 IS NOT ALLOWED FOR GROUP B OCCUPANCY IN
 THIS CASE.SEE ALSO FBC 303.1 #4 WITH R
 ESPECT TO MIXED OCCUPANCIES.
  
 11) SHOW OR NOTE SPECIFICALLY THE
 EXTERIOR TRIMS TO BE USED AS TO MATERIAL
 AND METHODS SEE FBC 104.2.