2003-08-11 00:00:00 | 2ND REVIEW |
| 1)AS NOTED ON THE FIRST CHECKLIST THE |
| OPENINGS IN THE EXTERIOR WALL ON THE |
| SOUTH PROPERTY LINE ARE |
| REQUIRED TO BE FIRE RATED, AND THE WEST |
| WALL ARE PROHIBITTED BY FBC TABLE 600. |
| THE ARCHITECT'S QUOTING OF FBC |
| 3401.7.2.4 IS WITHOUT STANDING FOR THIS |
| PROJECT.SEE FBC 3401.7.2.6 AND REVISE |
| AS NECESSARY.ALSO, SEE FBC 104.2.1 |
| WITH REGARDS TO QUOTING CODE SECTIONS |
| NOT BEING AN ACCEPTABLE ALTERNATIVE TO |
| SPECIFIC DESIGN INFORMATION. |
| |
| 2) VERTICAL ACCESIBILITY IS REQUIRED |
| FOR OFFICES SHOWN AS #4 AND #5 AS |
| PREVIOUSLY NOTED.SEE FBC 11-4.1.5.6 |
| (1) (K) (III). |
| |
| 3) THE STRUCTURAL CALCULATIONS |
| PREVIOUSLY REQUESTED FOR THE SECOND |
| FLOOR CONSTRUCTION HAVE NOT BEEN |
| PROVIDED. |
| THE DECLARED 1/2" X 5" BOLTS @ 4' ON |
| CENTER SHOWN IN SECTION 2/A ON SHEET 3 |
| APPEARS TO BE VERY INADEQUATE FOR THE |
| LOADS TO BE IMPOSED ON THE WOOD |
| PERPENDICULAR TO THE GRAIN. HOW WAS THE |
| MINIMAL 75# LIVE LOAD DETERMINED? |
| PLEASE PROVIDE COMPLETE STRUCTURAL |
| CALCULATIONS. |
| |
| 4) THE STAIRS TO OFFICES 4 AND 5 |
| REQUIRE HANDRAILS ON EACH SIDE AN WITHIN |
| 30" OF THE WIDTH REQUIRED FOR EGRESS. |
| SEE FBC 1007.5.2, FBC 1007.5.5 AND FBC |
| 1007.5.7.DO NOT QUOTE THOSE CODE |
| SECTIONS BUT |
| SHOW A GRAPHIC DEPICTION AND/OR NOTES |
| TO CLEARLY SHOW THE DESIGN INTENT. |
| INCLUDE FASTENING AND CONNECTION |
| DETAILS. |
| |
| 5) PLEASE PROVIDE THE FIRE DESIGN |
| NUMBER FOR THE SEVERAL PLACES CALLING |
| OUT "1 FIRE RATED" SEE FBC 701.5. |
| |
| |
| 6) SECTION 1/A, SHEET 3. THE STEEL |
| COLUMN IS 3"X3"X WHAT? |
| |
| 7) SECTION 3/A, WHAT ARE THE |
| DIMENSIONS,MATERIAL AND CONNECTION |
| METHODS? |
| |
| 8) THE SIX INCH SPACE AT THE TOE RAIL |
| OF THE GUARD RAIL SHOWN IN SECTION 3/A |
| DOES NOT COMPLY WITH FBC 1015.3.IF THE |
| GUARD RAIL IS A DELEGATED DESIGN SHOW |
| MINIMUM REQUIRED LOADS AS PROVIDED FOR |
| IN FBC 1608.2.2. |
| |
| 9) THE SECOND FLOOR STAIRS ARE REQUIRED |
| TO BE ENCLOSED WITH FIRE RATED |
| CONSTRUCTION AND TO PROVIDE A PROTECTED |
| PATH TO THE OUTSIDE. |
| SEE FBC 1006.1.1 AND FBC 1010.1. |
| |
| 10) TWO INDEPENDENT EXITS ARE REQUIRED |
| FROM THE SECOND FLOOR.SEE FBC |
| 1004.2.1 AND 1027.1.FURTHER, THE |
| TRAVEL DISTANCE IS >75' SO A SINGLE EXIT |
| IS NOT ALLOWED FOR GROUP B OCCUPANCY IN |
| THIS CASE.SEE ALSO FBC 303.1 #4 WITH R |
| ESPECT TO MIXED OCCUPANCIES. |
| |
| 11) SHOW OR NOTE SPECIFICALLY THE |
| EXTERIOR TRIMS TO BE USED AS TO MATERIAL |
| AND METHODS SEE FBC 104.2. |