Notes
Date Text
2003-04-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT 2 SECTION 11-4.1.6, IF EXISTING
 ELEMENTS, SPACES, OR COMMON AREAS ARE
 ALTERED, THEN EACH SUCH ALTERED ELEMENT,
 SPACE, FEATURE, OR AREA SHALL COMPLY
 WITH THE APPLICABLE PROVISIONS OF
 11-4.1.1 TO 11-4.1.3 - IF TOILET ROOMS
 ARE PROVIDED THEN EACH PUBLIC AND COMMON
 USE TOILET SHALL COMPLU WITH 11-4.22
 IF BATHING ROOMS ARE PROVIDED, THEN EACH
 PUBLIC AND COMMON USE BATHROOM SHALL
 COMPLY WITH 11-4.23. - PLEASE SHOW CLEAR
 FLOOR SPACE, TURNING CIRCLE ECT. TO
 COMPLY WITH 11-4.16 AND ALL SUB SECTIONS
 ALSO SHOW DETAIL FOR SHOWER SHOWING
 COMPLIANCE WITH 11-4.21 AND ALL SUBSEC-
 TIONS.
 2) SHT 2 NEW BREAK SINK, SUBMIT DETAIL
 SHOWING COMPLIANCE WITH 11-4.24 AND ALL
 SUBSECTIONS.
 3) SEPARATE PERMIT REQUIRED FOR IRRIGAT-
 ION. SUBMIT PLANS AT TIME OF APPLICATION
  