2003-04-15 00:00:00DENIED:2001 FLORIDA BUILDING CODE,
 (MECHANICAL)
 1.AS PER 2001 FBC(M) 501.3, EXHAUST
 SYSTEM SHALL BE DISCHARGED OUTDOORS AT
 A POINT FROM WHICH IT CANNOT AGAIN BE
 DRAWN IN BY THE VENTILATION SYSTEM.
 (EXHAUST OUTLET IN RELATION TO OUTSIDE
 AIR INTAKE).
  
 2.CLARIFY THE 6" OUTSIDE AIR DUCT
 TERMINATING IN THE AHU CLOSET.THE
 RETURN AIR APPEARS TO BE DUCTED INTO
 THE AHU.IS THE O.A. TIED INTO THE
 RETURN OR OPEN TO THE AHU CLOSET?
  
 3.TOILET ROOM BETWEEN OFFICE #4 & 5
 DOES NOT INDICATE AN EXHAUST FAN.AS
 PER 2001 FBC(M) 501.2 SINGLE OR COMBINED
 MECHANICAL EXHAUST SYSTEMS FROM TOILET,
 URINAL & SIMILAR ROOMS SHALL BE
 INDEPENDENT IF OTHER EXHAUST SYSTEMS.
 ALSO 403.2.1, ROOMS CONTAINING SHOWERS,
 BATHTUBS OR SIMILAR BATHING FIXTURES
 SHALL BE MECHANICALLY EXHAUSTED.
  
 4.FRESH AIR CALCS ARE INCOMPLETE, THE
 DO NOT INDICATE SQ FOOTAGE OR NUMBER
 OF PEOPLE.
  