Plan Review Notes For Permit 03032368 |
Permit Number |
03032368 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-04-15 00:00:00 | DENIED:2001 FLORIDA BUILDING CODE, | | (MECHANICAL) | | 1.AS PER 2001 FBC(M) 501.3, EXHAUST | | SYSTEM SHALL BE DISCHARGED OUTDOORS AT | | A POINT FROM WHICH IT CANNOT AGAIN BE | | DRAWN IN BY THE VENTILATION SYSTEM. | | (EXHAUST OUTLET IN RELATION TO OUTSIDE | | AIR INTAKE). | | | | 2.CLARIFY THE 6" OUTSIDE AIR DUCT | | TERMINATING IN THE AHU CLOSET.THE | | RETURN AIR APPEARS TO BE DUCTED INTO | | THE AHU.IS THE O.A. TIED INTO THE | | RETURN OR OPEN TO THE AHU CLOSET? | | | | 3.TOILET ROOM BETWEEN OFFICE #4 & 5 | | DOES NOT INDICATE AN EXHAUST FAN.AS | | PER 2001 FBC(M) 501.2 SINGLE OR COMBINED | | MECHANICAL EXHAUST SYSTEMS FROM TOILET, | | URINAL & SIMILAR ROOMS SHALL BE | | INDEPENDENT IF OTHER EXHAUST SYSTEMS. | | ALSO 403.2.1, ROOMS CONTAINING SHOWERS, | | BATHTUBS OR SIMILAR BATHING FIXTURES | | SHALL BE MECHANICALLY EXHAUSTED. | | | | 4.FRESH AIR CALCS ARE INCOMPLETE, THE | | DO NOT INDICATE SQ FOOTAGE OR NUMBER | | OF PEOPLE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|