Plan Review Notes
Plan Review Notes For Permit 03032368
Permit Number 03032368
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-04-04 00:00:001) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS.
  
 2) NO INTERIOR FINISH CLASSIFICATION
 FOR THE WALLS AND CEILINGS.
  
 3) RISERS FOR STAIRS NEAR SECRETARY
 POOL AREA DOES NOT MEET CODE.
  
 4) STAIRS NEAR KITCHEN DOES NOT MEET
 CODE.
  
 5) ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHTS SHALL BE PLACED ON THE SAME
 DRAWING.
  
 6) NO FIRE EXTINGUISHERS SHOWN ON THE
 PLANS.
  
 7) IF NO FIRE SPRINKLERS ARE PLANNED,
 THEN STORAGE ROOMS SHALL BE FIRE
 RATED AT LEAST ONE HOUR WITH PROPER
 OPENING PROTECTIVES.
  
 8) WRONG BUILDING CODE REFERENCED ON
 THE PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910