Plan Review Notes
Plan Review Notes For Permit 03032368
Permit Number 03032368
Review Stop E
Sequence Number 1
Notes
Date Text
2003-04-07 00:00:00*********** UNSAT *****************
  
 1)NOTE; PLEASE SEE FIRE REVIEW COMMENTS
 THAT WILL HAVE AN AFFECT ON E-SHEETS.
  
 2)NOTE: PLEASE CALRFIY IF THIS IS A NEW
 OR EXISTING SERVICE? SHOWN AS NEW, IS
 THIS REPLACING EXIST?
  
 3)NOTE; PLEASE SEE FEEDER/SEC`S FOR
 NEW 400A SERVICE. PLEASE SIZE PER 310-16
 SHOWN AS 3/0` WHICH ARE ONLY RATED FOR
 200A`S.
  
 4)NOTE ; PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE W/ SUBMITTED PANEL
 SCHEDULE.
  
 5)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PER 220-3,220-10,220-11,220-13 ETC AND
 ALL CONTINUOUS LOADS PER 215-3/230-42
  
 6)NOTE: PLEASE SIZE OCP FOR AHU HEAT
 PER 424-3B MIN @125%.
  
 7)NOTE:PLEASE CALRIFY CIRCUITING FOR
 EM/EXXT LTS PER700-12E
  
 PLEASE SUBMIT THE ABVOVE INFORMATION
 FOR REVIEW/.
 561-659-8096 EXT 8372
 [email protected]