Plan Review Notes
Plan Review Notes For Permit 03032368
Permit Number 03032368
Review Stop B
Sequence Number 1
Notes
Date Text
2003-04-11 00:00:00THE GENERAL NOTES ON SHEET 1 DECLARES
 THE 1997 STANDARD BUILDING CODE.THE
 CITYOF WEST PALM BEACH AND THE STATE OF
 FLORIDA ARE CURRENTLY USING THE 2001
 FLORIDA BUILDING CODE.
  
 SEE FBC 104.3.1.1 FOR THE MINIMUM
 CRITERIA REQUIRED FOR PLAN REVIEW.
  
 THE ADDITION OF THE SECOND FLOOR AS
 WELLAS THE CHANGE OF USE FROM
 WAREHOUSE/STORAGE TO OFFICE IS SUBJECT
 TO IMPACT FEES COLLECTED BY THE COUNTY.
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED THE FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL (561) 233-5025 FOR
 MORE INFORMATION.
  
 THE OPENINGS ON THE SOUTH AND EAST
 EXTERIOR WALLS ARE REQUIRED TO BE FIRE
 PROTECTED AS PROVIDED FOR IN FBC TABLE
 600.
  
 OPENINGS IN THE WEST WALL ARE
 PROHIBITTED BY FBC TABLE 600.
  
 THE DESIGNATED FIVE FEET WIDE AISLE FOR
 THE HC PARKING SPACE IS NOT SHOWN ON THE
 SITE PLAN. SEE FBC 11- 4.6.3.
  
 VERTICAL ACCESSIBILITY IS REQUIRED FOR
 THE OFFICES SHOWN AS #4 & #5 AND THE
 SECOND FLOOR.SEE FBC 11- 4.1.6.
  
 PLEASE PROVIDE A BETTER STRUCTURAL
 FRAMING PLAN INCLUDING ALL OF THE
 DESIGN LOADS AND STANDARDS USED.SHOW
 THE MODIFICATIONS TO THE EXISTING WALLS
 IF ANY.THE PLACEMENT OF THE COLUMN AND
 FOOTING THAT ARE SHOWN IN SECTION ONLY.
  
 PROVIDE COMPLETE STRUCTURAL
 CALCULATIONSFOR THE SECOND FLOOR DESIGN.
  
 THE STAIRS MUST HAVE
 HANDRAILS COMPLYING WITH FBC 1007.5.
  
 THE SECOND FLOOR STAIRS ARE REQUIRED TO
 BE ENCLOSED IN FIRE RATED CONSTRUCTION.
 SEE FBC 1006.1.1.
  
 TWO MEANS OF EGRESS ARE REQUIRED FROM
 THE SECOND FLOOR.SEE FBC 1004.2.1 AND
 FBC 1027.1.1.
  
 THE 8" STAIR RISER SHOWN DOES NOT COMPLY
 WITH FBC 1007.3.
  
 THIS BUILDING IS LOCATED IN THE
 DESIGNATED FIRE DISTRICT AND EXTERIOR
 ARCHITECTURAL TRIM IS REQUIRED TO BE
 FIRE RETARDANT TREATED LUMBER OF
 NON-COMBUSTIBLE MATERIAL.SEE FBC
 F102.2.7 AS AMENDED BY THE CITY OF WEST
 PALM BEACH.
  
 PLEASE PROVIDE THREE COPIES OF SIGNED
 AND SEALED ENERGY CODE CALCLULATIONS.
 SEE FBC 13- 101.3.