2003-04-11 00:00:00 | THE GENERAL NOTES ON SHEET 1 DECLARES |
| THE 1997 STANDARD BUILDING CODE.THE |
| CITYOF WEST PALM BEACH AND THE STATE OF |
| FLORIDA ARE CURRENTLY USING THE 2001 |
| FLORIDA BUILDING CODE. |
| |
| SEE FBC 104.3.1.1 FOR THE MINIMUM |
| CRITERIA REQUIRED FOR PLAN REVIEW. |
| |
| THE ADDITION OF THE SECOND FLOOR AS |
| WELLAS THE CHANGE OF USE FROM |
| WAREHOUSE/STORAGE TO OFFICE IS SUBJECT |
| TO IMPACT FEES COLLECTED BY THE COUNTY. |
| BEFORE A PERMIT TO CONSTRUCT MAY BE |
| ISSUED THE FEES MUST BE PAID TO THE |
| COUNTY, THE PERMIT PLANS STAMPED BY |
| THAT OFFICE AND A COPY OF THE PAID |
| RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION.CALL (561) 233-5025 FOR |
| MORE INFORMATION. |
| |
| THE OPENINGS ON THE SOUTH AND EAST |
| EXTERIOR WALLS ARE REQUIRED TO BE FIRE |
| PROTECTED AS PROVIDED FOR IN FBC TABLE |
| 600. |
| |
| OPENINGS IN THE WEST WALL ARE |
| PROHIBITTED BY FBC TABLE 600. |
| |
| THE DESIGNATED FIVE FEET WIDE AISLE FOR |
| THE HC PARKING SPACE IS NOT SHOWN ON THE |
| SITE PLAN. SEE FBC 11- 4.6.3. |
| |
| VERTICAL ACCESSIBILITY IS REQUIRED FOR |
| THE OFFICES SHOWN AS #4 & #5 AND THE |
| SECOND FLOOR.SEE FBC 11- 4.1.6. |
| |
| PLEASE PROVIDE A BETTER STRUCTURAL |
| FRAMING PLAN INCLUDING ALL OF THE |
| DESIGN LOADS AND STANDARDS USED.SHOW |
| THE MODIFICATIONS TO THE EXISTING WALLS |
| IF ANY.THE PLACEMENT OF THE COLUMN AND |
| FOOTING THAT ARE SHOWN IN SECTION ONLY. |
| |
| PROVIDE COMPLETE STRUCTURAL |
| CALCULATIONSFOR THE SECOND FLOOR DESIGN. |
| |
| THE STAIRS MUST HAVE |
| HANDRAILS COMPLYING WITH FBC 1007.5. |
| |
| THE SECOND FLOOR STAIRS ARE REQUIRED TO |
| BE ENCLOSED IN FIRE RATED CONSTRUCTION. |
| SEE FBC 1006.1.1. |
| |
| TWO MEANS OF EGRESS ARE REQUIRED FROM |
| THE SECOND FLOOR.SEE FBC 1004.2.1 AND |
| FBC 1027.1.1. |
| |
| THE 8" STAIR RISER SHOWN DOES NOT COMPLY |
| WITH FBC 1007.3. |
| |
| THIS BUILDING IS LOCATED IN THE |
| DESIGNATED FIRE DISTRICT AND EXTERIOR |
| ARCHITECTURAL TRIM IS REQUIRED TO BE |
| FIRE RETARDANT TREATED LUMBER OF |
| NON-COMBUSTIBLE MATERIAL.SEE FBC |
| F102.2.7 AS AMENDED BY THE CITY OF WEST |
| PALM BEACH. |
| |
| PLEASE PROVIDE THREE COPIES OF SIGNED |
| AND SEALED ENERGY CODE CALCLULATIONS. |
| SEE FBC 13- 101.3. |