2003-04-18 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 FUEL GAS | | | | 1) SHT P-18 GAS ISOMETRIC, REFERENCE | | NFPA-54 (1996) - NFPA-54 NOT ADOPTED IN | | FBC-2001. PLEASE INDICATE CODE IN FBC- | | 2001 FUEL GAS CODE THAT WILL SHOW 400' | | DEVELOPED LENGTH @ 2PSI. | | 2) SHT P-18 GAS ISOMETRIC, LINE SUPPLY- | | ING REGULATOR #2 SHOWS 1775 MBH, BUT | | ONLY SHOWS 2 @ 400 MBH & 1 @ 200 MBH = | | 1000 MBH. PLEASE CLAIRFY. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 | | (561) 805-6721 | | FAX (561) 653-2692 |
|