Plan Review Notes
Plan Review Notes For Permit 03032127
Permit Number 03032127
Review Stop M
Sequence Number 1
Notes
Date Text
2003-03-31 00:00:00DENIED:
  
 AS PER 2001 FBC CHAPTER 13 SECTION
 407.1.ABCD.2.2.2 ZONES, THE SUPPLY OF
 THE HVAC SYSTEM TO EACH ZONE (APARTMENT
 & HOUSE) SHALL BE CONTROLLED BY
 INDIVDUAL THERMOSTAT RESPONDING TO THE
 TEMPERATURE WITHIN THE ZONE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.