2003-04-16 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE UPDATED SBCCI PRODUCT APPROVAL
 REPORT THAT MATCHES ENGINEERING DWGS.
 CHECK THE DESIGN PRESSURES AND MAX/MIN
 PANEL SPAN SHOWN ON THE INSTALLATION
 SCHEDULE AND VERIFY WITH ENGINEERED
 DRAWINGS. SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 2-CLARIFY/REVISE DETAIL S21 TO MATCH 2ND
 FLOOR FRAMING PLAN. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 3-WINDOW 34SH DOESN'T PROVIDE THE 24"
 CLEAR HEIGHT REQUIRED BY SECTION
 1005.4 FBC 2001. REVISE/CLARIFY AS
 REQUIRED. ALSO, VERIFY THAT 24+5SH
 WINDOW PROVIDE THE 24" CLEAR HEIGHT &
 5.7 S.F. MINIMUM CLEAR OPENING.
 4-RESUBMIT ENERGY CALCULATIONS WITH
 ENGINEER'S ORIGINAL SIGNATURE & SEAL.
 CHAPTER 471 FLORIDA STATUTES AND SEC.
 103.0 CHAPTER 13 FBC 2001.