Plan Review Notes
Plan Review Notes For Permit 03032015
Permit Number 03032015
Review Stop P
Sequence Number 1
Notes
Date Text
2003-04-01 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 2) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER. - POOL DATA SHOWS AUTO VAC
 CLEANER, BUT PIPING DIAGRAM AND PIPING
 SCHEMATIC SHOWS NONE. PLEASE CLAIRFY
 3) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 4) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 5) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
 6) PIPING SCHEMATIC DOES NOT REFLECT THE
 PIPING DIAGRAM. ONLY ONE PUMP IS SHOWN,
 NO POOL HEATERS ARE SHOWN. IF THERE IS
 A VACUMM LINE IT SHALL BE SHOWN. THERE
 IS NO PIPING SHOWN FOR THE SPA ON THE
 SCHEMATIC. PLEASE SUBMIT A PIPING SCHEM-
 ATIC THAT REFLECTS THE POOL PIPING WITH
 ALL PUMPS, FILTERS, HEATERS, MAIN DRAINS
 VALVES ECT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377