Plan Review Notes For Permit 03031958 |
Permit Number |
03031958 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-03-31 00:00:00 | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS AS | | PER 2001 FBC(M) TABLE 403.3 & ASHRAE | | 62-89. | | | | 2.INDICATE EXHAUST (NEW OR EXISTING) | | | | 3.PLEASE CLARIFY THE LOCATION OF THE | | CONDENSER UNIT, IT APPEARS TO BE AGAINST | | THE BUILDING.INDICATE WHERE THE | | PROPERTY LINE - 3 FT SETBACK REQUIRED. | | | | 4.IS THIS A HAIR SALON OR WILL NAILS | | & PEDICURES BE DONE AT THIS LOCATION? | | IF SO, COMPLY WITH ASHRAE 62-89 SECTION | | 5.7. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|