2003-04-16 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS WITH UPDATED SBCCI PRODUCT | | APPROVAL THAT MATCHES ENGINEERING | | DRAWINGS. ALSO, CHECK DESIGN PRESSURES | | AND MAX./MIN. PANEL SPAN. SECTION | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | 2-PROVIDE COMPLETE SPECIFICATIONS FOR | | GARAGE DOOR STRUCTURAL BUCK DETAIL. | | NEED ANCHOR EMBEDMENT AND WASHER. SEC. | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | 3-BUILDING SECTION A/A-5: REVISE THE | | HANDRAIL HEIGHT. SEE SEC. 1007.5.1 | | FBC 2001. | | 4-PROVIDE SOIL TEST REPORT PRIOR TO | | CONSTRUCTION. |
|