2003-05-31 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | CODE REQUIREMENTS. THE SIZE OF THE | | DRAINAGE PIPING SHALL NOT BE REDUCED IN | | SIZE IN THE DIRECTION OF THE FLOW. SEC | | 704.2 (BATH #2 THRU KIT) - TUB & SHOWER | | IN MASTER BATH NOT VENTED. - FIXTURES | | FROM LAUNDRY ROOM SHALL NOT DRAIN INTO | | THE WET VENT FOR MASTER BATH. - DOES | | NOT REFLECT FLOOR PLAN. - SECOND FLOOR | | BATHROOMS/LAUNDRY ROOM SHALL NOT DRAIN | | THROUGH FIRST FLOOR POWDER ROOM PIPING. | | -- SEE ATTACHED SHEET FOR EXAMPLE OF | | SANITARY RISER DIAGRAM THAT REFLECTS THE | | FLOOR PLAN, AND MEETS ALL CODE REQUIRE- | | MENTS. --- | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 | | (561) 805-6721 | | FAX (561) 653-2692 |
|