Plan Review Notes For Permit 03031844 |
Permit Number |
03031844 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-05-05 00:00:00 | ************** UNSAT ************** | | | | 1)NOTE: PLEASE SEE PLANS FOR SD PLACE- | | -MENT. PLANS STILL SHOW BOTH SD`S INSIDE | | BEDROOM. ONE NEEDS TO BE OUTSIDE. ONE | | SD WAS MOVED INTO HALLWAY OUTSIDE MASTER | | BED AREA AND SHOULD HAVE REMAINED WHERE | | IT WAS. | | NFPA-72 8-1.4.2 | | | | 2)NOTE: PLEASE CORRELATE RISER DIAGRAM | | AND PANEL SCHEDULES. PANELS SHOWN AS | | 150A AND RISER SHOWS 200A? METER SHOWN | | AS 300A WITH TWO 200A MAINS.? | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|