Plan Review Notes
Plan Review Notes For Permit 03031844
Permit Number 03031844
Review Stop E
Sequence Number 2
Notes
Date Text
2003-05-05 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE SEE PLANS FOR SD PLACE-
 -MENT. PLANS STILL SHOW BOTH SD`S INSIDE
 BEDROOM. ONE NEEDS TO BE OUTSIDE. ONE
 SD WAS MOVED INTO HALLWAY OUTSIDE MASTER
 BED AREA AND SHOULD HAVE REMAINED WHERE
 IT WAS.
 NFPA-72 8-1.4.2
  
 2)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANEL SCHEDULES. PANELS SHOWN AS
 150A AND RISER SHOWS 200A? METER SHOWN
 AS 300A WITH TWO 200A MAINS.?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy