2003-04-03 00:00:00*************** UNSAT ****************
  
 1)NOTE: SD NOT PERMITTED IN KITCHEN,
 NFPA-72 8-1.4.2
  
 2)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 PER 310-15/250-66. 400A SERVICE.
  
 3)NOTE: PLEASE SEE MIN LOAD FOR WASHER
 CIRCUIT PER 220-16 1.5
  
 4)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH CIRCUIT(S) PER 210-52D/210-11C-3
  
 5)NOTE: PLEASE MOVE SD TO OUTSIDE
 MASTER BEDROOM.
  
 6)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN AND
 PANEL "B".
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  