Plan Review Notes For Permit 03031844 |
Permit Number |
03031844 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-04-03 00:00:00 | *************** UNSAT **************** | | | | 1)NOTE: SD NOT PERMITTED IN KITCHEN, | | NFPA-72 8-1.4.2 | | | | 2)NOTE: PLEASE SIZE GROUNDING ELECTRODE | | PER 310-15/250-66. 400A SERVICE. | | | | 3)NOTE: PLEASE SEE MIN LOAD FOR WASHER | | CIRCUIT PER 220-16 1.5 | | | | 4)NOTE: PLEASE LIST THE REQ`D DEDICATED | | BATH CIRCUIT(S) PER 210-52D/210-11C-3 | | | | 5)NOTE: PLEASE MOVE SD TO OUTSIDE | | MASTER BEDROOM. | | | | 6)NOTE: PLEASE SEE MISSING EQUIPMENT | | GROUNDING CONDUCTOR BETWEEN MAIN AND | | PANEL "B". | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|