2006-10-19 10:05:24 | ****CORRECTIONS**** |
| REVISION 22 |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2001 |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2001 |
| |
| 1.)A2.06, A36AB, AND OTHER SHEETS STATES THAT |
| OPENINGS WILL BE PROTECTED BY A HURRICANE SHUTTER. |
| REMOVABLE SHUTTERS ON COMMERCIAL BUILDINGS MUST BE |
| APPROVED BY THE BUILDING OFFICIAL, SEE ATTACHED POLICY, |
| ITEM 13.IF YOU HAVE NOT SUBMITTED A HURRICANE SHUTTER |
| INSTALLATION PLAN, PLEASE DO SO AT THIS TIME.IF YOU |
| HAVE AN APPROVED PLAN, PLEASE REVISE TO INCLUDE THE NEW |
| OPENINGS AND SUBMIT.A PRELIMINARY REVIEW OF THE PLAN |
| CAN BE DONE VIA EMAIL, [email protected] SHOULD BE |
| DONE PRIOR TO RESUBMITTAL TO AVOID DELAYS IN REVISION |
| APPROVAL. |
| |
| 2.)WERE PRODUCT APPROVALS SUBMITTED FOR THE SHUTTERS? |
| DID THE DOOR CHANGE FROM ORIGINAL APPROVAL?HAS A NEW |
| PRODUCT APPROVAL BEEN SUBMITTED?NO DOOR TYPE |
| INDICATED.NOTE THAT ONE DOOR IS AT AN ELEVATOR LOBBY, |
| SEE FBC412.6.1. |
| |
| 3.)A2.11 AND OTHER SHEETS SHOW A CHANGE TO JOHN |
| MANVILLE MODIFIED OVER LWC.HAS THE PRODUCT APPROVAL |
| BEEN REVIEWED BY THE CITY?IF NOT, SUBMIT AT THIS TIME |
| AND INDICATE WHICH APPROVED ASSEMBLY YOU ARE USING. |
| |
| 4.)A2.11 SHOWS "ACCESS DOOR PROVIDED UNDER THE STAIR |
| REQUESTED BY CITY INSPECTOR."NO STAIRS SHOWN.WHAT |
| WILL THIS AREA BE USED FOR?DOES NOT APPEAR TO BE AN |
| EXIT STAIR, PLEASE CLARIFY ON THIS SHEET PURPOSE OF THE |
| SPACE AND STAIRS.SEE FBC1006 IN REGARDS TO OPENINGS |
| IN STAIRWAYS AND FBC1006.1.4 IN REGARDS TO SPACE UNDER |
| THE STAIR. |
| |
| 5.)IT IS NOT CLEAR WHAT CHANGED ON A-3-10AB.PLEASE |
| CLARIFY. |
| |
| 6.)REVISION 20 HAD ACCESSIBILITY CORRECTIONS, BUT THE |
| SHEET WAS NOT SUBMITTED.SINCE THIS WAS AN AS-BUILT, |
| PLEASE ADVISE AS TO HOW THIS WAS RESOLVED.SEE REVIEW |
| B 49, "SEE SHEET A2.05 AND A-3-5DA FOR NEW DOOR COMMON |
| TO MENS / WOMENS RESTROOM BY GYM."FBC11-4.13.6. |
| |
| 6.)WHEN RESUBMITTING, PLEASE INCLUDE A RESPONSE |
| LETTER TO EXPEDITE PLAN REVIEW. |
| |
| |
| ALSO REVIEWED - A2.02, A2.04, A31AB, A31B0, A32B0, |
| A34B0, A34AB, A36DA, A39AB, A6.07, A10.02, A36B0, |
| A10.05, A10.06, A10.07, ID5.0, ID6.0, ID11.0 |