2003-09-26 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 03031778 |
| ADD: 610 CLEMATIS STREET |
| CONT: WHITING- TURNER CONTRACTING |
| TEL: (954)776-0800 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| ARCH B & A BERMELLO AJAMIL & |
| PARTNERS |
| BORAS GRANDASEN (305) 860-3822 |
| HECTOR VALVERDE (305) 859-2050 |
| |
| ENG:DER DE LOS ENGINEREERING INC |
| (305) 665-2778 |
| |
| 1) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| 2) THRESHOLD BUILDING FL. S.S.553.71(7) |
| THRESHOLD COMPANY AND INSPECTOR TO BE |
| SIGNED ON WITH CITY BEFORE ISSUANCE. |
| CONTACT: DON NEELY 805-6665 |
| 3) SHEETS A-3.1AB/ A-3.1BC THE ENTERIOR |
| DOORS TO UNITS ARE TO BE THE "PRIMARY |
| ENTRY DOORS" FAIR HOUSING ACT INDICATE |
| MAIN ENTRY ON PLAN NOT SECONDARY. |
| 4) POOL DECK SHEET A-2.06 THERE IS ONLY |
| ONE ELEVATION GIVEN, FOR THE WALKING SUR |
| FACES, PROVIDE SLOPE FOR RAMPS AND ELE- |
| VATIONS, TO SEE IF HANDRAILS ARE RE- |
| QUIRED. |
| 5) SHEET A-3-5DA CORRIDOR 154 LEVEL 42 |
| (NORTH) INDICATES THE USAGE OF RAMPS, |
| BUT NO ELEVATION IS PROVIDED NOR SLOPE |
| FOR THE RAMPS? |
| 6)1606.1.4(1) IN WIND BORNE DEBRIS |
| REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| ASSUMED TO BE OPENINGS UNLESS SUCH |
| GLAZING IS IMPACT RESISTANT OR PROTECTED |
| WITH AN IMPACT RESISTANT COVERING MEET- |
| ING THE REQUIREMENTS OF SSTD 12, ASTM |
| E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| A) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| OF GRADE SHALL MEET THE REQUIREMENTS OF |
| LARGE MISSLE TEST. |
| SHEET S-1.4.1- S-1.4.3 INDICATE |
| THE OPENING PRESSURES FOR THE VARIOUS |
| WALL OPENINGS. THE ONLY PROBLEM IS NO |
| END ZONES ARE GIVEN FOR THE WALL, CREAT- |
| ING A HIGHER PRESSURE ZONE,ALSO AT THE |
| ROOF OR TOP FLOORS. UNDER ASCE7-88 THE P |
| RESSURES FOR A 80' BUILDING AT ZONE@ 7 |
| END ZONE 110.3, EVALUATE ROOF LOADS AT |
| ROOF LEVEL. WHY SUCH A DIFFERENCE? |
| 7) THE PRODUCT APPROVALS MIAMI-DADE |
| ARE MISSING THE TECHNICAL SHEETS. THESE |
| SHEETS INDICATE WHAT THE PRESSURES ARE |
| APPROVED FOR, ALSO IF REINFORCEMENT |
| IS REQUIRED. |
| 8) FENESTRATION TESTING REPORTS RE- |
| QUIRE SITE SPECIFIC ENGINEERING: |
| SITE SPECIFIC ENGINEERING (PRODUCT |
| APPROVAL) REQUIRES THE WET SIGNATURE, |
| DATE AND EMBOSSED SEAL OF THE ENGINEER |
| CERTIFYING THE PRODUCT AND SIGNATURE |
| AND SEAL OF THE DESIGN PROFESSIONAL |
| OF RECORD.SEE ATTACHMENT. |
| 9) DEPENDING ON THE REPORT A SEPARATE |
| MULLION REPORT MAY BE REQUIRED. |
| 1707.4.5.1 MULLIONS OCCURRING |
| BETWEEN INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED TESTING |
| LABORATORY OR BE ENGINEERED. |
| 10) 1707.4.4.2 TAPERED BUCKS: |
| SHALL EXTEND BEYOND THE INTERIOR FACE |
| OF THE WINDOW OR DOOR FRAME SUCH THAT |
| FULL SUPPORT OF THE FRAME IS SUPPORTED. |
| 11) SHEET A-1 GENERAL NOTES: 34, MINI |
| MUM FLAME SPREAD TO BE IN CONFORMANCE |
| WITH, ID-11.1 INTERIOR FINISHES, NO IN- |
| FORMATION ABOUT TABLE 803.3 FLAME SPREAD |
| / SMOKE DEVELOPMENT.ANSWER COMPLIANCE |
| BUT WHERE? |
| 12) EXTERIOR WALLS PRESSURE TREATED |
| FURRING ALLOWED IF THE FOLLOWING REQUIRE |
| MENTS ARE MET, 803.9.1. ANSWER SEE NOT |
| A8.03 NO MENTION OF 803.9.1!!!! |
| 13) GYMNASIUM A-2 ASSEMBLY INDICATE |
| 2HR WALLS W/ 1 1/2 HR PROTECTIVE. |
| ANSWER COMPLIANCE, WHERE? |
| 14) SHEET A-10.02 DETAILS 1&6 EXPAND- |
| ED POLYSTRYRENE MOLDING, THIS MATERIAL I |
| S NOT ALLOWED IN THE FIRE DISTRICT SEE |
| 102.7 ARCHITECTURAL TRIM. ANSWER: SEE AT |
| TACHED PRODUCT CONTROL APPROVAL.??????? |
| 15) SEE DOOR G-37 PART OF EGRESS, |
| STAIR TOWER# 1, SHOULD SWING OUT. |
| 16)BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| JIM WITMER |
| BUILDING PLAN REVIEW |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |