Plan Review Notes For Permit 03031778 |
Permit Number |
03031778 |
|
Review Stop |
B |
Sequence Number |
37 |
|
Notes |
Date |
Text |
2005-05-17 00:00:00 | ****CORRECTIONS**** | | STUCCO/PERLITE SUBMITTAL | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)WAS STUCCO USED FOR CALCULATED FIRE | | RESISTANCE ON THE ORIGINAL PLAN?IF | | NOT, SUBMIT A LETTER STATING THIS FROM | | DOR.IF IT WAS, SHOW THAT REQUIRED FIRE | | RESISTANCE IS STILL MET WITH THE | | SUBSTITUTION OF PERLITE FOR SAND IN THE | | STUCCO. | | |
|