Plan Review Notes For Permit 03031778 |
Permit Number |
03031778 |
|
Review Stop |
B |
Sequence Number |
32 |
|
Notes |
Date |
Text |
2005-05-17 00:00:00 | ****CORRECTIONS**** | | CLARIFICATION LETTER PREPARED BY WILLIAM | | COOK, PE DATED 10/18/04 | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)PLEASE INCLUDE CERTIFICATE OF | | AUTHORIZATION NUMBER ON ALL DOCUMENTS. | | THE SEAL ALSO REQUIRES A DATE. | | FAC61G15-23.002. | | | | 2.)PROVIDE THE CALCULATIONS REFERRED | | TO IN THE LETTER REGARDING THE 1/2" SHIM | | GAP.DO THE ANCHORS STILL MEET THE | | MINIMUM EMBEDMENT REQUIREMENT WITH THE | | ADDITIONAL 1/4" OF SHIM SPACE? | | | | 3.)ALL SUBMITTALS ARE TO BE REVIEWED | | BY EOR OR DOR PRIOR TO SUBMITTAL TO THE | | CITY. | | |
|