2006-11-25 23:42:59 | REVISION DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| |
| 1. SHT P-2.3 AAV NOT APPROVED WITH OUT A RELIEF VENT. |
| SECTION 917.3.2. |
| |
| 2. SHT P-2.10 REVISION 22 BY L/22 INDICATES A 4" |
| TERRACE OVERFLOW STORM DRAIN (TYPICAL). NO OVERFLOW |
| DRAIN FOUND. PLEASE CLARIFY. SECTION 106.1.1. |
| |
| 3. SHT P-4.3 DETAILS 4 & 6. UR-1 & UR-4 GT NOT VENTED. |
| SECTION 901.2.1. |
| |
| 4. SHT P-4.4 DETAILS 4 & 6. UR-2 SHOWER IS NOT VENTED, |
| AND UR-3 GT NOT VENTED. SECTION 901.2.1. |
| |
| 5. SHT P-4.6 DETAILS 4 & 6. UR-2 & UR-4 SHOWER NOT |
| VENTED. SECTION 901.2.1. |
| |
| 6. SHT P-4.7 DETAIL 4. UR-2 W/M NOT VENTED. SECTION |
| 901.2.1. |
| |
| 7. SHT P-4.9 DETAIL 6. UR-2 GT NOT VENTED. SECTION |
| 901.2.1. |
| |
| 8. SHT P-4.10 DETAIL 4. UR-1 SHOWER NOT VENTED. SECTION |
| 901.2.1. |
| |
| 9. SHT P-4.13 DETAIL 6. UR-1 W/M & KS NOT VENTED. |
| SECTION 901.2.1. |
| |
| 10. SHT P-4.14 DETAIL 4. W/M & KS NOT VENTED AND THE |
| SHOWER IS NOT VENTED. SECTION 901.2.1. |
| |
| 11. SHT P-4.15 DETAIL 4. W/M & KS NOT VENTED. SECTION |
| 901.2.1. |
| |
| 12. SHT P-4.16 DETAILS 4 & 6. W/M & KS NOT VENTED. |
| SECTION 901.2.1. |
| |
| 13. SHT P-4.17 DETAIL 4. W/M & KS NOT VENTED, AND |
| SHOWER NOT VENTED. UPPER FLOOR ALL FIXTURES NOT VENTED. |
| SECTION 901.2.1. |
| |
| 14. SHT P-4.18 DETAIL 5. KS NOT VENTED. SECTION |
| 901.2.1. |
| |
| 15. SHT P-5.1 THRU P-5.3, P-5.3.1, P-5.3.2 VENT STACK |
| SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK AT OR |
| BELOW THE LOWEST BRANCH LINE. SECTION 903.4. |
| |
| P-5.4 CONST. NOTES #4 BLACK IRON PIPE IS NOT APPROVED |
| FOR WATER DISTRIBUTION. TABLE 605.5. |
| |
| REVIEW BY KEN STEVENS |