2006-11-25 23:42:59REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P-2.3 AAV NOT APPROVED WITH OUT A RELIEF VENT.
 SECTION 917.3.2.
  
 2. SHT P-2.10 REVISION 22 BY L/22 INDICATES A 4"
 TERRACE OVERFLOW STORM DRAIN (TYPICAL). NO OVERFLOW
 DRAIN FOUND. PLEASE CLARIFY. SECTION 106.1.1.
  
 3. SHT P-4.3 DETAILS 4 & 6. UR-1 & UR-4 GT NOT VENTED.
 SECTION 901.2.1.
  
 4. SHT P-4.4 DETAILS 4 & 6. UR-2 SHOWER IS NOT VENTED,
 AND UR-3 GT NOT VENTED. SECTION 901.2.1.
  
 5. SHT P-4.6 DETAILS 4 & 6. UR-2 & UR-4 SHOWER NOT
 VENTED. SECTION 901.2.1.
  
 6. SHT P-4.7 DETAIL 4. UR-2 W/M NOT VENTED. SECTION
 901.2.1.
  
 7. SHT P-4.9 DETAIL 6. UR-2 GT NOT VENTED. SECTION
 901.2.1.
  
 8. SHT P-4.10 DETAIL 4. UR-1 SHOWER NOT VENTED. SECTION
 901.2.1.
  
 9. SHT P-4.13 DETAIL 6. UR-1 W/M & KS NOT VENTED.
 SECTION 901.2.1.
  
 10. SHT P-4.14 DETAIL 4. W/M & KS NOT VENTED AND THE
 SHOWER IS NOT VENTED. SECTION 901.2.1.
  
 11. SHT P-4.15 DETAIL 4. W/M & KS NOT VENTED. SECTION
 901.2.1.
  
 12. SHT P-4.16 DETAILS 4 & 6. W/M & KS NOT VENTED.
 SECTION 901.2.1.
  
 13. SHT P-4.17 DETAIL 4. W/M & KS NOT VENTED, AND
 SHOWER NOT VENTED. UPPER FLOOR ALL FIXTURES NOT VENTED.
 SECTION 901.2.1.
  
 14. SHT P-4.18 DETAIL 5. KS NOT VENTED. SECTION
 901.2.1.
  
 15. SHT P-5.1 THRU P-5.3, P-5.3.1, P-5.3.2 VENT STACK
 SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK AT OR
 BELOW THE LOWEST BRANCH LINE. SECTION 903.4.
  
 P-5.4 CONST. NOTES #4 BLACK IRON PIPE IS NOT APPROVED
 FOR WATER DISTRIBUTION. TABLE 605.5.
  