Date Text
2003-11-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 CITY WPB CODE
  
 A) THE FOLLOWING COMMENTS FROM THE FIRST
 AND SECOND REVIEWS HAVE NOT BEEN ADD-
 RESSED OR ANSWERED SUFFICIENTLY. THE
 NUMBER OF THE COMMENT FROM THE FIRST
 REVIEW WILL BE USED FOR CLAIRITY.
 7) SHT A-401 DETAIL #1 CLEAR FLOOR SPACE
 REQUIRED FOR ALL FIXTURES PER FHA DESIGN
 MANUAL PAGE 7.43. (ALL UNITS) "THE CLEAR
 FLOOR SPACE DIMENSIONS ARE TO BE APPLIED
 OR SUPERIMPOSED OVER A PLAN DURING THE
 DESIGN PROCESS TO DETERMINE IF SPACE RE-
 QUIREMENTS AT TOILETS ARE BEING MET.
 13) PLEASE IDENTIFY ALL WORK/LIVE LOFTS.
 TOILET ROOMS SHALL COMPLY WITH 11-4.22.
 ALL UNITS SHALL HAVE A DRINKING FOUNTAIN
 PER TABLE 403.1. ALSO SEE 410.1. - THE
 TYPE OF OWNERSHIP DOES NOT DETERMINE IF
 REQUIREMENTS ARE TO BE MET, BUT RATHER
 THE OCCUPANCY OF THE UNIT THAT DETERMINE
 ACCESSIBILITY AND MINIMUM FACILITIES.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. SOME LENGTH MISSING FROM
 RISER DIAGRAM. 104.2.1
 B.SHTS P-2.1 & P-2.2 INDICATE A 2 LB.
 SYSTEM, BUT SHT P-5.5 STILL INDICATES A
 7" W/C. PLEASE CLAIRFY. 104.2.1
 22) SHT P-4.2 SANT. RISER DOES NOT REFL-
 LECT THE FLOOR PLAN AND SHOWER IS NOT
 VENTED. (H/10). 901.2.1
 23) SHT P-4.4 FLOOR PLAN TO REFLECT THE
 SANT. RISER DIAGRAM AT TUB BATH. 104.2.1
 33) SHT P-4.18 SANT RISER AND FLOOR PLAN
 THE KITCHEN SINK SHALL NOT DRAIN INTO
 THE WET VENT FOR THE BATHROOM GROUP.
 SECTION 909.1
 ---COMMENTS FROM SECOND REVIEW
 THE NUMBERS WILL REMAIN THE SAME FOR
 CLAIRITY.
 6B) SHTS P-2.1 & P-5.2 RISERS 27 THRU 41
 AT COL. LINE 8 SHOWS 300 DFU'S ON FLOOR
 PLAN, BUT 370 DFU'S ON RISER. PLEASE
 CLAIRFY. (RISER 38 NOT SHOWN ON FLOOR
 PLAN, BUT IS SHOWN ON THE SANT. RISER
 DIAGRAM). 104.2.1
 9B) SHTS P-2.3 & P-5.5, 8" SHOWS 1298
 DFU ON FLOOR PLAN BUT NOT RISER SHOWS
 1365 DFU. RISER AND FLOOR PLAN SHALL RE-
 FLECT. PLEASE CLAIRFY. 104.2.1
 10B) SHTS P-2.4 & P-5.5 RISER DOES NOT
 REFLECT THE FLOOR PLAN. BRANCH TO TOILET
 ROOMS CONNECT TO DRAIN AFTER SR128 ON
 THE FLOOR PLAN, BUT PRIOR TO SR 128 ON
 THE RISER DIAGRAM. PLSE CLAIRFY 104.2.1
 11B) SHTS P-2.4 & P-5.6 FLOOR PLAN SHOWS
 8" @ 9450 SF, BUT RISER SHOWS 10" @
 9450 SF. PIPE SIZES MUST CORRELATE.
 15B) SUBMIT STORM RISERS, SHOW OFFSETS,
 PIPE SIZES, SQUARE FOOOTAGE ECT. THE
 HORIZONTAL STORM DRAIN IS SHOWN BUT THE
 VERTICAL STORM RISERS ARE NOT SUBMITTED.
 104.2.1
 19B) SUBMIT CALCULATIONS FOR RWL'S LARG-
 ER THAN 8". TABLE 1106.2 ONLY ADDRESSES
 PIPE SIZE TO 8". 104.2.1 - THIS WILL BE
 REQUIRED FOR PERMIT.
 25B) SHT P-4.3 TUB NOT VENTED, B/11 AND
 ALL AAV'S REQUIRES ACCESS, AND VENTILA-
 TION. 917.5
 26B) SHT P-4.5 TUB NOT VENTED AND RISER
 DOES NOT REFLECT THE FLOOR PLAN. UR-1
 HORIZONTAL DRY VENT NOT ALLOWED. 905.3
 THIS VENT IS NOT REQUIRED. UR-3. 104.2.1
 AAV REQUIRES ACCESS AND VENTILATION.
 917.5. "S" TRAP ON LAV (NO VENT) 1002.3
 (5) - SEE RED LINES
 27B) SHT P-4.6 SHOWER NOT VENTED, ACCESS
 & VENTILATION REQUIRED FOR AAV, NO HORI-
 ZONTAL DRY VENTS NOT ALLOWED.
 28B) SHT P-4.7 ACCESS AND VENTILATION
 REQUIRED FOR AAV, RISER DOES NOT REFLECT
 THE FLOOR PLAN.
 29B) SHT P-4.9 ACCESS AND VENTILATION
 REQUIRED FOR AAV'S. 917.5
 30B) SHT P-4.10 SHOWER NOT VENTED L-05
 901.2.1
 31B) ACCESS AND VENTILATION REQUIRED FOR
 AAV'S 917.5
 32B) SHT P-4.13 TUB NOT VENTED U-1
 33B) SHT P-4.14 SHOW VENT ON FLOOR PLAN
 104.2.1
 34B) SHT P-4.15 SHOWER NOT VENTED, AND
 VENT NOT REQUIRED ON TUB.
 35B) SHT P-4.17 ACCESS AND VENTILATION
 REQUIRED FOR AAV. HORIZONTAL DRY VENT
 NOT ALLOWER FOR SHOWER. 905.3
 36B) THE RELIEF VENTS REQUIRED BY SEC
 917.3.2 FOR FLOORS 2, 3, & R SHALL BE
 TIED INTO THE BRANCH LINES FOR THESE
 FLOORS. THE VENT LINES SHALL BE SHOWN
 ON THE RISERS. SEE EXAMPLE ON SR/20
  
 REVIEW BY KEN STEVENS