2003-11-13 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 11 |
| FBC-2001 BUILDING |
| FHA-98 DESIGN MANUAL |
| FLORIDA ADMINISTRATIVE CODE |
| CITY WPB CODE |
| |
| A) THE FOLLOWING COMMENTS FROM THE FIRST |
| AND SECOND REVIEWS HAVE NOT BEEN ADD- |
| RESSED OR ANSWERED SUFFICIENTLY. THE |
| NUMBER OF THE COMMENT FROM THE FIRST |
| REVIEW WILL BE USED FOR CLAIRITY. |
| 7) SHT A-401 DETAIL #1 CLEAR FLOOR SPACE |
| REQUIRED FOR ALL FIXTURES PER FHA DESIGN |
| MANUAL PAGE 7.43. (ALL UNITS) "THE CLEAR |
| FLOOR SPACE DIMENSIONS ARE TO BE APPLIED |
| OR SUPERIMPOSED OVER A PLAN DURING THE |
| DESIGN PROCESS TO DETERMINE IF SPACE RE- |
| QUIREMENTS AT TOILETS ARE BEING MET. |
| 13) PLEASE IDENTIFY ALL WORK/LIVE LOFTS. |
| TOILET ROOMS SHALL COMPLY WITH 11-4.22. |
| ALL UNITS SHALL HAVE A DRINKING FOUNTAIN |
| PER TABLE 403.1. ALSO SEE 410.1. - THE |
| TYPE OF OWNERSHIP DOES NOT DETERMINE IF |
| REQUIREMENTS ARE TO BE MET, BUT RATHER |
| THE OCCUPANCY OF THE UNIT THAT DETERMINE |
| ACCESSIBILITY AND MINIMUM FACILITIES. |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. SOME LENGTH MISSING FROM |
| RISER DIAGRAM. 104.2.1 |
| B.SHTS P-2.1 & P-2.2 INDICATE A 2 LB. |
| SYSTEM, BUT SHT P-5.5 STILL INDICATES A |
| 7" W/C. PLEASE CLAIRFY. 104.2.1 |
| 22) SHT P-4.2 SANT. RISER DOES NOT REFL- |
| LECT THE FLOOR PLAN AND SHOWER IS NOT |
| VENTED. (H/10). 901.2.1 |
| 23) SHT P-4.4 FLOOR PLAN TO REFLECT THE |
| SANT. RISER DIAGRAM AT TUB BATH. 104.2.1 |
| 33) SHT P-4.18 SANT RISER AND FLOOR PLAN |
| THE KITCHEN SINK SHALL NOT DRAIN INTO |
| THE WET VENT FOR THE BATHROOM GROUP. |
| SECTION 909.1 |
| ---COMMENTS FROM SECOND REVIEW |
| THE NUMBERS WILL REMAIN THE SAME FOR |
| CLAIRITY. |
| 6B) SHTS P-2.1 & P-5.2 RISERS 27 THRU 41 |
| AT COL. LINE 8 SHOWS 300 DFU'S ON FLOOR |
| PLAN, BUT 370 DFU'S ON RISER. PLEASE |
| CLAIRFY. (RISER 38 NOT SHOWN ON FLOOR |
| PLAN, BUT IS SHOWN ON THE SANT. RISER |
| DIAGRAM). 104.2.1 |
| 9B) SHTS P-2.3 & P-5.5, 8" SHOWS 1298 |
| DFU ON FLOOR PLAN BUT NOT RISER SHOWS |
| 1365 DFU. RISER AND FLOOR PLAN SHALL RE- |
| FLECT. PLEASE CLAIRFY. 104.2.1 |
| 10B) SHTS P-2.4 & P-5.5 RISER DOES NOT |
| REFLECT THE FLOOR PLAN. BRANCH TO TOILET |
| ROOMS CONNECT TO DRAIN AFTER SR128 ON |
| THE FLOOR PLAN, BUT PRIOR TO SR 128 ON |
| THE RISER DIAGRAM. PLSE CLAIRFY 104.2.1 |
| 11B) SHTS P-2.4 & P-5.6 FLOOR PLAN SHOWS |
| 8" @ 9450 SF, BUT RISER SHOWS 10" @ |
| 9450 SF. PIPE SIZES MUST CORRELATE. |
| 15B) SUBMIT STORM RISERS, SHOW OFFSETS, |
| PIPE SIZES, SQUARE FOOOTAGE ECT. THE |
| HORIZONTAL STORM DRAIN IS SHOWN BUT THE |
| VERTICAL STORM RISERS ARE NOT SUBMITTED. |
| 104.2.1 |
| 19B) SUBMIT CALCULATIONS FOR RWL'S LARG- |
| ER THAN 8". TABLE 1106.2 ONLY ADDRESSES |
| PIPE SIZE TO 8". 104.2.1 - THIS WILL BE |
| REQUIRED FOR PERMIT. |
| 25B) SHT P-4.3 TUB NOT VENTED, B/11 AND |
| ALL AAV'S REQUIRES ACCESS, AND VENTILA- |
| TION. 917.5 |
| 26B) SHT P-4.5 TUB NOT VENTED AND RISER |
| DOES NOT REFLECT THE FLOOR PLAN. UR-1 |
| HORIZONTAL DRY VENT NOT ALLOWED. 905.3 |
| THIS VENT IS NOT REQUIRED. UR-3. 104.2.1 |
| AAV REQUIRES ACCESS AND VENTILATION. |
| 917.5. "S" TRAP ON LAV (NO VENT) 1002.3 |
| (5) - SEE RED LINES |
| 27B) SHT P-4.6 SHOWER NOT VENTED, ACCESS |
| & VENTILATION REQUIRED FOR AAV, NO HORI- |
| ZONTAL DRY VENTS NOT ALLOWED. |
| 28B) SHT P-4.7 ACCESS AND VENTILATION |
| REQUIRED FOR AAV, RISER DOES NOT REFLECT |
| THE FLOOR PLAN. |
| 29B) SHT P-4.9 ACCESS AND VENTILATION |
| REQUIRED FOR AAV'S. 917.5 |
| 30B) SHT P-4.10 SHOWER NOT VENTED L-05 |
| 901.2.1 |
| 31B) ACCESS AND VENTILATION REQUIRED FOR |
| AAV'S 917.5 |
| 32B) SHT P-4.13 TUB NOT VENTED U-1 |
| 33B) SHT P-4.14 SHOW VENT ON FLOOR PLAN |
| 104.2.1 |
| 34B) SHT P-4.15 SHOWER NOT VENTED, AND |
| VENT NOT REQUIRED ON TUB. |
| 35B) SHT P-4.17 ACCESS AND VENTILATION |
| REQUIRED FOR AAV. HORIZONTAL DRY VENT |
| NOT ALLOWER FOR SHOWER. 905.3 |
| 36B) THE RELIEF VENTS REQUIRED BY SEC |
| 917.3.2 FOR FLOORS 2, 3, & R SHALL BE |
| TIED INTO THE BRANCH LINES FOR THESE |
| FLOORS. THE VENT LINES SHALL BE SHOWN |
| ON THE RISERS. SEE EXAMPLE ON SR/20 |
| |
| REVIEW BY KEN STEVENS |