2003-10-29 00:00:00********* NOTES REDLINED ***********
  
 1)NOTE: GFI RECEPTS TO BE W/IN 3' OF
 LAV/ SINKS IN BATHROOMS.
 E-4.11(L-19), E-4.16 (R1(N)
  
 2)NOTE: RECEPT SPACING PER 210.52
 E-4.5 (16,18,20), 4.5 (T1), 4.18 (M/01,
 M38
  
 3)NOTE: COLOR CODING REDLINED FOR CITY
 OF WEST PALM BEACH AMEDMENTS.
 PLANS MENTION PALM BEACH COUNTY.
  
 THE ABOVE HAS BEEN REDLINED ON EACH SET
 AND PLANS DO NOT NEED TO BE REVISED AT
 THIS TIME FOR THIS.
 ELECTRICAL PLANS HAVE BEEN PASSED, PEND-
 -ING COMMENTS FROM ANY OTHER REVIEWERS
 THAT MAY OR MAY NOT HAVE COMMENTS THAT
 MAY AFFECT ELECTRICAL PLANS.
 ELEECTRICAL SHEETS ONLY HAVE BEEN
 STAMPED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 PLANS SUBMITTED FOR TEMPORARY ELECTRICAL
 SERVICE MUST BE SUBMITTED UNDER SEPARATE
 PERMIT APPLICATION.
 PLEASE ALSO HAVE PLANS DONE AND AN
 ENGINEER PER FS 471.003
 PLANS MUST CONTAIN ALL INFORMATION AS
 SET FORTH UNDER FAC 61G15-23.002