2003-04-16 00:00:00BUILDING PLAN REVIW
 CONTINUED 4/16/03
  
 *****STAIR TOWERS******
 42) SECTION 1005.6.6 APPROVED BARRIERS:
 A STAIRWAY IN A SMOKEPROOF ENCLOSURE
 SHALL NOT CONTINUE BELOW GRADE LEVEL
 UNLESS AN APPROVED BARRIER IS PROVIDED
 AT THE GROUND LEVEL TO PREVENT PERSONS
 FROM ACIDENTALLY CONTINUING INTO THE
 BASEMENT.
 1007.1.5 ENCLOSED EXIT STAIRWAYS
 THAT CONTINUE BEYOND THE FLOOR OF DIS-
 CHARGE SHALL BE INTERRUPTED AT THE FLOOR
 OF DISCHARGE BY PARTITIONS, DOORS OR
 OTHER EFFECTIVE MEANS.
 STAIR TOWERS 1, 2& 3 HAVE THIS CONDI
 TION THAT REQUIRES SOME MEANS TO PREVENT
 A PERSON FROM TURNINGIN THE WRONG
 DIRECTION AND DECENDING INTO THE
 BASEMENTS.
  
 43)SECTION 1006.1.3.2 EXTERIOR WALLS OF
 AN ENCLOSED STAIRWAY SHALL COMPLY WITH
 THE REQUIREMENTS OF TABLE 600 FOR EXTER-
 IOR WALLS. WHERE NONRATED WALLS OR
 UNPROTECTED OPENINGS ARE USED TO ENCLOSE
 THE EXTERIOR OF THE STAIRWAY, THE BUILD
 ING ENCLOSURE WALLS WITHIN 10 FT HORIZON
 TALLY OF THE NONRATED WALLS OR UNPROTECT
 ED OPENINGS SHALL BE CONSTRUCTED AS REQU
 IRED FOR STAIRWAY ENCLOSURES, INCLUDING
 OPENING PROTECTIVES, BUT NEED NOT EXCEED
 1-HR FIRE RATING W 3/4 HOUR OPENING PROT
 ECTIVE. THIS CONSTRUCTION SHALL EXTEND
 VERTICALLY FROM THE GROUD TO A POINT
 10 FT ABOVE THE TOP MOST LANDING OF THE
 STAIRWAY OR TO THE ROOF LINE, WHICHEVER
 IS LOWER.
 STAIRWELLS 1,2 & 3 HAVE THIS CONFIG
 URATION WHERE THE WINDOWS/ DOORS EITHER
 SIDE OF THE OPENING OR ABOVE THE OPENING
 ARE NOT RATED.
 STAIRWELL # 3 SEE 1005.6.8.1 FOR
 SMOKEPROOF ENCLOSURE BY NATURAL VENTIL-
 ATION VESTIBULE AS OPTION.
  
 43) RETAIL AREAS, 1004.1.2 EVERY ROOM OR
 TENANT SPACE WHICH HAS AN OCCUPANT LOAD
 OF 50 OR MORE PERSONS SHALL NOT HAVE
 LESS THAN 2 EGRESS DOORS, REMOTELY
 PLACED. IF THESE SPACES ARE FITTED OUT
 AS RESTARAUNTS, THE BACK EXIT IF THROUGH
 THE KITHEN CAN'T BE COUNTED AS AN EXIT!
 JUST A WORD OF CAUTION!
  
 44) 1012.1.2 EGRESS DOORS SHALL SWING IN
 THE DIRECTION OF TRAVEL (1) WHEN SERVING
 AN OCCUPANT LOAD OF 50 OR MORE, SEE
 GYMNASIUN DOOR! PROVIDE ADDITIONAL INFO
 FOR THE CARD READER ON THIS DOOR, LOSS
 OF POWER FAIL SAFE OPEN OR FAIL SAFE
 SECURE?
  
 45) ID-9-0 ELEVATORS 3003.4.1 PROVIDE
 LAYOUT INDICATING STRETCHER REQUIREMENTS
  
 46) ELEVATOR SIGNAGE 3003.3.
  
 47)1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 0BOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 SHEET A-10.02 DETAIL # 2/ WHAT IS THE
 OVERFLOW SCUPPER SIZE?
  
 48) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 49) 1511.7 ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGTH IN ACCORDANCE WITH TABLE 1511.7.
  
 50) SHEET A-5.14 LOWER PARKING FLOOR,
 THE 7'-0" CLEAR FLOOR HEIGHT MUST BE
 MAINTAINED, THIS IS A MINIMUM!!!!
  
 51) INDICATE WHAT HR RATING THE CONCRETE
 BLOCK USED WILL BE, EQUIVALENT THICKNESS
 WILL BE FOR THE MANUFACTURER USED?
 TABLE 709.3.1.
  
 52) SHEET A10.07 FABRIC CANOPY- FABRIC
 IS TO BE FIRE RETARDANT TREATED FABRIC.
 F102.2.8.
  
 53) SHEET A-10.10 TEAHOUSE/ TRILLIS
 NO TYPE VI CONSTRUCTION IN THE FIRE
 DISTRICT
  
 54) ID-2.2 MAIN LOBBY CURVED SOFFITS,
 DROPPED CEILING, FIBERGLASS PLASTIC
 DOME( ID-4.1 DETAIL 6) ADDITIONAL INFO,
 HOW TO HANG, MAN SPEC FLAME SPREAD/
 SMOKE DEVELOPMENT?
  
 55) ID-4.2 MAIL KIOSK DETAILS 3&6, REACH
 RANGES?11-4.2.5/11-4.2.6 FL ACC CODE.
  
 56)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW