Date |
Text |
2005-08-04 00:00:00 | REVISION DENIED/OK |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| |
| 1. SHT P-1.2 REVISIONS 1, 13, 17 NOT |
| FOUND ON REVISED SHEET. MANY CHANGES TO |
| SHEET NOT CLOUDED OR NUMBERED. INDICATE |
| ALL REVISIONS TO SHEET BY CLOUDING AND |
| NUMBERING. SECTION 104.2.1. |
| 2. SHT P-1.3 REVISION 1 DESCRIPTION |
| UNCLEAR. REVISIONS 11 & 17 NOT FOUND. |
| MANY CHANGES TO SHEET NOT CLOUDED OR |
| NUMBERED. INDICATE ALL REVISIONS TO |
| SHEET BY CLOUDING AND NUMBERING. SECTION |
| 104.2.1. |
| 3. SHT P-2.1 NOTE TO CONTRACTOR READS |
| "GAS PIPING SHALL BE WELDED SCHEDULE 40 |
| BLACK STEEL". PRIOR TO ISSUING THE |
| PERMIT & PLANS, THE ENGINEER INDICATED |
| THAT THE GAS PIPING WILL BE SCREW PIPE |
| AND NOT WELD PIPE. PLEASE CHANGE THIS ON |
| THE NOTE. - ORIGINAL ISSUED SET OF PLANS |
| HAD MEASURMENTS FOR EACH SECTION OF GAS |
| PIPE HAND DRAWN BY THE ENGINEER. THESE |
| MEASURMENTS SHALL BE ON THE REVISED |
| SHEET. SOME CHANGES TO SHEET ARE NOT |
| CLOUDED OR NUMBERED. INDICATE ALL |
| REVISIONS TO SHEET BY CLOUDING AND |
| NUMBERING. SECTION 104.2.1. |
| 4. SHTS P-2.9 AND P-2.10 REVISION 1 NOT |
| FOUND, (P-2.9). GIVE A DISCRIPTION OF |
| WHAT REVISION 20 IS FOR. LINES SHOWN DO |
| NOT CONNECT TO ANY SYSTEM, NO PIPE SIZES |
| SHOWN. WHAT IS THE INTENT OF THESE |
| LINES? SECTION 104.2.1. SECONDARY ROOF |
| DRAINS ARE NOT SHOWN FOR THIS AREA OF |
| THE DECK AS REQUIRED IN SECTION 1107. |
| PLEASE INDICATE THE LOCATION. SECTION |
| 104.2.1. |
| 5. SHT P-2.11 INDICATES 4" PATIO |
| OVERFLOW DRAINS FOR ONE SET OF LINES |
| ADJACENT TO THE MATCH LINE. IS THIS THE |
| REQUIREMENT FOR ALL LINES SHOWN ON THIS |
| SHEET AS REVISION 20? IS THIS THE |
| REQUIREMENT FOR ALL SHEETS SHOWING THESE |
| LINES? IF SO PLEASE INDICATE IN SOME WAY |
| TO CLARIFY THESE COMMENTS. SECTION |
| 104.2.1. |
| 6. SHTS P-2.11, P-2.12, THESE AREAS |
| REQUIRED SECONDARY ROOF DRAINS. PLEASE |
| SHOW THE LOCATION OF SECONDARY ROOF |
| DRAINS PER SECTION 1107. |
| 7. SHT P-4.1 OK |
| 8. SHT P-4.2 MAXIMUM 8' FROM TRAP TO |
| VENT PER TABLE 906.1 - SCALES OUT TO |
| ABOUT 10' ON DETAIL 1. |
| 9. SHT P-4.3 OK |
| 10. SHT P-4.4 OK |
| 11. SHT P-4.5 OK |
| 12. SHT P-4.6 OK |
| 13. SHT P-4.7 OK |
| 14. SHT P-4.8 OK |
| 15. SHT P-4.9 OK |
| 16. SHT P-4.10 MAXIMUM 8' FROM TRAP TO |
| VENT PER TABLE 906.2 - SCALES OUT TO |
| ABOUT 11' ON DETAIL 1. - CHANGE TO FLOOR |
| PLAN SHALL BE REFLECTED BY A CHANGE TO |
| THE SANT. RISER DIAGRAM. SECTION |
| 104.2.1. |
| 17. SHT P-4.11 OK |
| 18. SHT P-4.12 OK |
| 19. SHT P-4.13 REVISION 1 NOT FOUND. |
| SECTION 104.2.1. |
| 20. SHT P-4.14 REVISION 1 NOT FOUND. |
| SECTION 104.2.1. |
| 21. SHT P-4.15 REVISION 1 NOT FOUND. |
| SECTION 104.2.1. |
| 22. SHT P-4.16 MAXIMUM 8' FROM TRAP TO |
| VENT PER TABLE 906.2. - SCALES OUT TO |
| ABOUT 11' ON DETAIL 2. |
| 23. SHT P-4.17 HAND DRAWN CHANGE TO |
| SHEET DATED 11-19-03 HAVE NOT BEEN |
| CHANGED AND ARE SHOWN AS DRAWN |
| ORIGINALLY. THESE WERE CODE COMPLIANCE |
| CHANGES AND SHALL BE REFLECTED ON THIS |
| SHEET AS REQUIRED AT TIME PERMIT ISSUED. |
| NO REVISION SHOWN CHANGING DETAILS 1 AND |
| 4 AT THE KITCHEN SINK FOR THE LOCATION |
| OF THE AAV. SECTION 104.2.1. |
| 24. SHT P-4.18 OK |
| ALL OK SHEETS DATE STAMPED AND RETURNED |
| WITH DENIED SHEETS AND WILL NOT BE |
| REQUIRED TO BE RESUBMITTED. |
| |