Plan Review Notes
Plan Review Notes For Permit 03031778
Permit Number 03031778
Review Stop P
Sequence Number 28
Notes
Date Text
2005-08-04 00:00:00REVISION DENIED/OK
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P-1.2 REVISIONS 1, 13, 17 NOT
 FOUND ON REVISED SHEET. MANY CHANGES TO
 SHEET NOT CLOUDED OR NUMBERED. INDICATE
 ALL REVISIONS TO SHEET BY CLOUDING AND
 NUMBERING. SECTION 104.2.1.
 2. SHT P-1.3 REVISION 1 DESCRIPTION
 UNCLEAR. REVISIONS 11 & 17 NOT FOUND.
 MANY CHANGES TO SHEET NOT CLOUDED OR
 NUMBERED. INDICATE ALL REVISIONS TO
 SHEET BY CLOUDING AND NUMBERING. SECTION
 104.2.1.
 3. SHT P-2.1 NOTE TO CONTRACTOR READS
 "GAS PIPING SHALL BE WELDED SCHEDULE 40
 BLACK STEEL". PRIOR TO ISSUING THE
 PERMIT & PLANS, THE ENGINEER INDICATED
 THAT THE GAS PIPING WILL BE SCREW PIPE
 AND NOT WELD PIPE. PLEASE CHANGE THIS ON
 THE NOTE. - ORIGINAL ISSUED SET OF PLANS
 HAD MEASURMENTS FOR EACH SECTION OF GAS
 PIPE HAND DRAWN BY THE ENGINEER. THESE
 MEASURMENTS SHALL BE ON THE REVISED
 SHEET. SOME CHANGES TO SHEET ARE NOT
 CLOUDED OR NUMBERED. INDICATE ALL
 REVISIONS TO SHEET BY CLOUDING AND
 NUMBERING. SECTION 104.2.1.
 4. SHTS P-2.9 AND P-2.10 REVISION 1 NOT
 FOUND, (P-2.9). GIVE A DISCRIPTION OF
 WHAT REVISION 20 IS FOR. LINES SHOWN DO
 NOT CONNECT TO ANY SYSTEM, NO PIPE SIZES
 SHOWN. WHAT IS THE INTENT OF THESE
 LINES? SECTION 104.2.1. SECONDARY ROOF
 DRAINS ARE NOT SHOWN FOR THIS AREA OF
 THE DECK AS REQUIRED IN SECTION 1107.
 PLEASE INDICATE THE LOCATION. SECTION
 104.2.1.
 5. SHT P-2.11 INDICATES 4" PATIO
 OVERFLOW DRAINS FOR ONE SET OF LINES
 ADJACENT TO THE MATCH LINE. IS THIS THE
 REQUIREMENT FOR ALL LINES SHOWN ON THIS
 SHEET AS REVISION 20? IS THIS THE
 REQUIREMENT FOR ALL SHEETS SHOWING THESE
 LINES? IF SO PLEASE INDICATE IN SOME WAY
 TO CLARIFY THESE COMMENTS. SECTION
 104.2.1.
 6. SHTS P-2.11, P-2.12, THESE AREAS
 REQUIRED SECONDARY ROOF DRAINS. PLEASE
 SHOW THE LOCATION OF SECONDARY ROOF
 DRAINS PER SECTION 1107.
 7. SHT P-4.1 OK
 8. SHT P-4.2 MAXIMUM 8' FROM TRAP TO
 VENT PER TABLE 906.1 - SCALES OUT TO
 ABOUT 10' ON DETAIL 1.
 9. SHT P-4.3 OK
 10. SHT P-4.4 OK
 11. SHT P-4.5 OK
 12. SHT P-4.6 OK
 13. SHT P-4.7 OK
 14. SHT P-4.8 OK
 15. SHT P-4.9 OK
 16. SHT P-4.10 MAXIMUM 8' FROM TRAP TO
 VENT PER TABLE 906.2 - SCALES OUT TO
 ABOUT 11' ON DETAIL 1. - CHANGE TO FLOOR
 PLAN SHALL BE REFLECTED BY A CHANGE TO
 THE SANT. RISER DIAGRAM. SECTION
 104.2.1.
 17. SHT P-4.11 OK
 18. SHT P-4.12 OK
 19. SHT P-4.13 REVISION 1 NOT FOUND.
 SECTION 104.2.1.
 20. SHT P-4.14 REVISION 1 NOT FOUND.
 SECTION 104.2.1.
 21. SHT P-4.15 REVISION 1 NOT FOUND.
 SECTION 104.2.1.
 22. SHT P-4.16 MAXIMUM 8' FROM TRAP TO
 VENT PER TABLE 906.2. - SCALES OUT TO
 ABOUT 11' ON DETAIL 2.
 23. SHT P-4.17 HAND DRAWN CHANGE TO
 SHEET DATED 11-19-03 HAVE NOT BEEN
 CHANGED AND ARE SHOWN AS DRAWN
 ORIGINALLY. THESE WERE CODE COMPLIANCE
 CHANGES AND SHALL BE REFLECTED ON THIS
 SHEET AS REQUIRED AT TIME PERMIT ISSUED.
 NO REVISION SHOWN CHANGING DETAILS 1 AND
 4 AT THE KITCHEN SINK FOR THE LOCATION
 OF THE AAV. SECTION 104.2.1.
 24. SHT P-4.18 OK
 ALL OK SHEETS DATE STAMPED AND RETURNED
 WITH DENIED SHEETS AND WILL NOT BE
 REQUIRED TO BE RESUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]