Plan Review Notes
Plan Review Notes For Permit 03031778
Permit Number 03031778
Review Stop P
Sequence Number 23
Notes
Date Text
2005-03-23 00:00:00REVISION DENIED
  
 A) THE FOLLOWING SHEETS SUBMITTED FOR
 REVISION HAVE BEEN DENIED.
 SHTS SUBMITTED ON 6/8/4 P-2.2
 SHTS SUBMITTED ON 2/7/5 P-1.2, P-1.3,
 P-2.2, P-2.6, P-5.1, P-5.3.1, P-5.3.2, &
 P-5.5
 B) THE FOLLOWING ARE THE COMMENTS FOR
 THOSE DENIED SHEETS.
 1) SHT P-1.2 8" SANT. @ 1459 DFU @
 1/16"/FT NOT APPROVED. TABLE 710.1 -
 SR32 NOT SHOWN ON BLDG. SANT. DRAIN.
 2) SHT P-1.3 10" (10830SF) INTO CATCH
 BASIN COL. LINE 12/N-O PICKS UP 4
 BALCONY DRAINS @ 1190SF. PLEASE INDICATE
 WHERE THE OTHER 9640SF ENTER THE STORM
 LINE? SECTION 104.2.1.
 3) SHT P-2.2 NOTE ON SHEET STATES: "GAS
 PIPING TO BE WELDED SCHEDULE 40 BLACK
 STEEL". PREVIOUS REVISION AND
 CONVERSATION WITH THE ENGINEER INDICATED
 THAT THE PIPING WILL BE SCREW PIPE.
 PLEASE CLARIFY. IS THIS A REVISION
 CHANGING TO WELD PIPE? SECTION 104.2.1.
 4) SHT P2.6 INDICATE THE SLOPE OF THE
 SANITARY FROM THE CLEANOUT AT COL. LINE
 10/U TO COL. LINE 10/O. MAXIMUM 1400 DFU
 FOR 8" PIPE @ 1/16"/FT. TABLE 710.1-
 STORM PIPING, 12" REQUIRED AT 25,280SF.
 MAXIMUM 18,400SF ON 10" PIPE. TABLE
 1106.3.
 5) SHT P-5.1 RISERS SR1, SR2, SR3, &
 SR5. CHANGES FAXED FROM RICHARD TAVERES
 ON MARCH 11, 2005 SHALL BE REVISED ON
 THESE RISERS. - ALSO ALL WASTE STACKS
 THAT HAVE HAD THE AIR ADMITTENCE VALVES
 REMOVED SHALL REVISE RISERS TO REMOVE
 THE RELIEF VENTS THAT WILL NOT BE
 REQUIRED. (EXAMPLE SR3, & SR4 W/M &
 KITCHEN SINK RISERS). SEC 104.2.1.
 6) SHT P-5.3.1 SR 66, SR67, SR87, SR91,
 SR92, & SR93 SHALL BE REVISED TO REFLECT
 THE CHANGES FAXED FROM R. TAVERES 3/11/5
 AND REMOVE ALL RELIEF VENTS FROM RISERS
 FOR THE W/M AND KITCHEN SINKS WHERE THE
 AAV'S HAVE BEEN REMOVED. SEC 104.2.1.
 7) SHT P-5.3.2 SR123, & SR125 REVISE
 SHEET TO REFLECT FAXED CHANGED FROM R.
 TAVERES 3/11/5 AND ALL WASTE STACKS FOR
 THE KITCHEN SINKS AND W/M THAT HAVE
 DELETED THE AAV'S. NO RELIEF VENTS
 REQUIRED. SECTION 104.2.1.
 8) SHT P-5.5 8"(1459 DFU) DOWNSTREAM OF
 SR7 SHALL BE INCREASED TO 10" OR RUN AT
 1/8"/FT SLOPE. TABLE 710.1
 9) SHT P-5.5 PIPE LENGTHS FOR GAS LINES
 TO RETAIL #1 & #2 REQUIRED. (THESE WERE
 ON THE STAMPED SET OF PLANS AT THE TIME
 THE PERMIT WAS ISSUED). SECTION 104.2.1.
 10) SHT P-5.5 6" PIPE BETWEEN SR110 &
 SR107 SHALL BE INCREASED TO 8" PIPE OR
 SLOPED AT 1/4"/FT THE ENTIRE LENGTH OF
 THE RUN. TABLE 710.1 & SEC 704.1.
 11) SHT P-5.5 8" DOWNSTREAM OF SR90
 SHALL BE INCREASED TO 10" OR ENTIRE
 LENGHT OF RUN TO BE RUN AT 1/8"/FT.
 TABLE 710.1 & 704.1.
 12) SHT P-5.5 12" PIPE (4078 DFU) TO
 CONNECTION AT SEWER TO RUN AT 1/8"/FT OR
 INCREASED TO 15" PIPE. TABLE 710.1 &
 704.1.
 C) THE REVISIONS FOR THE FOLLOWING
 SHEETS HAVE BEEN APPROVED:
 DATED 6/8/4 -SHTS P-2.3, P-2.9, P-4.1
 THRU P-4.12, P-4.18, P-5.4 & P-6.1
 DATED 2/7/5 - SHTS P-2.4, P-2.5, P-2.7,
 P-4.1 THRU P-4.12, P-4.18, P-5.2, P-5.3
 DATED 10/1/4 SHT P-5.6
 TWO COPIES OF THESE REVISIONS WITH DATE
 STAMP SHALL BE RETURNED - ONE COMPLETE
 SET OF PLANS WITH RED LINE MARKINGS WILL
 BE RETAINED FOR COMPARISON AND FILE.
  
 REVIEW BY KEN STEVENS