Text |
2005-03-23 00:00:00 | REVISION DENIED |
| |
| A) THE FOLLOWING SHEETS SUBMITTED FOR |
| REVISION HAVE BEEN DENIED. |
| SHTS SUBMITTED ON 6/8/4 P-2.2 |
| SHTS SUBMITTED ON 2/7/5 P-1.2, P-1.3, |
| P-2.2, P-2.6, P-5.1, P-5.3.1, P-5.3.2, & |
| P-5.5 |
| B) THE FOLLOWING ARE THE COMMENTS FOR |
| THOSE DENIED SHEETS. |
| 1) SHT P-1.2 8" SANT. @ 1459 DFU @ |
| 1/16"/FT NOT APPROVED. TABLE 710.1 - |
| SR32 NOT SHOWN ON BLDG. SANT. DRAIN. |
| 2) SHT P-1.3 10" (10830SF) INTO CATCH |
| BASIN COL. LINE 12/N-O PICKS UP 4 |
| BALCONY DRAINS @ 1190SF. PLEASE INDICATE |
| WHERE THE OTHER 9640SF ENTER THE STORM |
| LINE? SECTION 104.2.1. |
| 3) SHT P-2.2 NOTE ON SHEET STATES: "GAS |
| PIPING TO BE WELDED SCHEDULE 40 BLACK |
| STEEL". PREVIOUS REVISION AND |
| CONVERSATION WITH THE ENGINEER INDICATED |
| THAT THE PIPING WILL BE SCREW PIPE. |
| PLEASE CLARIFY. IS THIS A REVISION |
| CHANGING TO WELD PIPE? SECTION 104.2.1. |
| 4) SHT P2.6 INDICATE THE SLOPE OF THE |
| SANITARY FROM THE CLEANOUT AT COL. LINE |
| 10/U TO COL. LINE 10/O. MAXIMUM 1400 DFU |
| FOR 8" PIPE @ 1/16"/FT. TABLE 710.1- |
| STORM PIPING, 12" REQUIRED AT 25,280SF. |
| MAXIMUM 18,400SF ON 10" PIPE. TABLE |
| 1106.3. |
| 5) SHT P-5.1 RISERS SR1, SR2, SR3, & |
| SR5. CHANGES FAXED FROM RICHARD TAVERES |
| ON MARCH 11, 2005 SHALL BE REVISED ON |
| THESE RISERS. - ALSO ALL WASTE STACKS |
| THAT HAVE HAD THE AIR ADMITTENCE VALVES |
| REMOVED SHALL REVISE RISERS TO REMOVE |
| THE RELIEF VENTS THAT WILL NOT BE |
| REQUIRED. (EXAMPLE SR3, & SR4 W/M & |
| KITCHEN SINK RISERS). SEC 104.2.1. |
| 6) SHT P-5.3.1 SR 66, SR67, SR87, SR91, |
| SR92, & SR93 SHALL BE REVISED TO REFLECT |
| THE CHANGES FAXED FROM R. TAVERES 3/11/5 |
| AND REMOVE ALL RELIEF VENTS FROM RISERS |
| FOR THE W/M AND KITCHEN SINKS WHERE THE |
| AAV'S HAVE BEEN REMOVED. SEC 104.2.1. |
| 7) SHT P-5.3.2 SR123, & SR125 REVISE |
| SHEET TO REFLECT FAXED CHANGED FROM R. |
| TAVERES 3/11/5 AND ALL WASTE STACKS FOR |
| THE KITCHEN SINKS AND W/M THAT HAVE |
| DELETED THE AAV'S. NO RELIEF VENTS |
| REQUIRED. SECTION 104.2.1. |
| 8) SHT P-5.5 8"(1459 DFU) DOWNSTREAM OF |
| SR7 SHALL BE INCREASED TO 10" OR RUN AT |
| 1/8"/FT SLOPE. TABLE 710.1 |
| 9) SHT P-5.5 PIPE LENGTHS FOR GAS LINES |
| TO RETAIL #1 & #2 REQUIRED. (THESE WERE |
| ON THE STAMPED SET OF PLANS AT THE TIME |
| THE PERMIT WAS ISSUED). SECTION 104.2.1. |
| 10) SHT P-5.5 6" PIPE BETWEEN SR110 & |
| SR107 SHALL BE INCREASED TO 8" PIPE OR |
| SLOPED AT 1/4"/FT THE ENTIRE LENGTH OF |
| THE RUN. TABLE 710.1 & SEC 704.1. |
| 11) SHT P-5.5 8" DOWNSTREAM OF SR90 |
| SHALL BE INCREASED TO 10" OR ENTIRE |
| LENGHT OF RUN TO BE RUN AT 1/8"/FT. |
| TABLE 710.1 & 704.1. |
| 12) SHT P-5.5 12" PIPE (4078 DFU) TO |
| CONNECTION AT SEWER TO RUN AT 1/8"/FT OR |
| INCREASED TO 15" PIPE. TABLE 710.1 & |
| 704.1. |
| C) THE REVISIONS FOR THE FOLLOWING |
| SHEETS HAVE BEEN APPROVED: |
| DATED 6/8/4 -SHTS P-2.3, P-2.9, P-4.1 |
| THRU P-4.12, P-4.18, P-5.4 & P-6.1 |
| DATED 2/7/5 - SHTS P-2.4, P-2.5, P-2.7, |
| P-4.1 THRU P-4.12, P-4.18, P-5.2, P-5.3 |
| DATED 10/1/4 SHT P-5.6 |
| TWO COPIES OF THESE REVISIONS WITH DATE |
| STAMP SHALL BE RETURNED - ONE COMPLETE |
| SET OF PLANS WITH RED LINE MARKINGS WILL |
| BE RETAINED FOR COMPARISON AND FILE. |
| |