Plan Review Notes
Plan Review Notes For Permit 03031778
Permit Number 03031778
Review Stop P
Sequence Number 20
Notes
Date Text
2004-12-27 00:00:00SUBMITTAL DENIED FOR PROPOSED PAN FOR
 ELECTRIC ROOM/VAULT. MORE INFORMATION IS
 REQUIRED. PLEASE INDICATE SIZE AND USE
 OF PIPE PAN IS MADE FOR. PLEASE SHOW ALL
 MEASUREMENTS FOR PAN. LENGTH, WIDTH,
 HEIGHT. DRAIN CAN NOT CAUSE A NUISANCE
 BY DRAINING INTO A STAIRWAY OR WALKWAY.
  
 SUBMITTAL DENIED FOR TRENCH DRAINS.
 PLEASE SUBMIT MORE INFORMATION FROM THE
 MANUF. SHOWING APPROVAL AND OR STANDARDS
 WHICH THE TRENCH DRAINS MEET. LOBBY
 TRENCH DRAINS DO NOT INDICATE WHO MANUF.
 THE DRAINS AND IT SEEMS LIKE THE
 SPECIFICATIONS ARE GENERAL
 SPECIFICATIONS THAT ARE REQUIRED TO BE
 MET, BUT DOES NOT INDICATE THAT THE
 TRENCH DRAINS ARE MEETING THE
 STANDARDS.
 THE TRENCH DRAINS FOR THE POOL AREA DO
 NOT SEEM TO BE COMPLETE. ONE PAGE STATES
 MATERALS AND STANDARDS, BUT NO STANDARDS
 ARE REFERED TO.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]