Plan Review Notes For Permit 03031778 |
Permit Number |
03031778 |
|
Review Stop |
P |
Sequence Number |
20 |
|
Notes |
Date |
Text |
2004-12-27 00:00:00 | SUBMITTAL DENIED FOR PROPOSED PAN FOR | | ELECTRIC ROOM/VAULT. MORE INFORMATION IS | | REQUIRED. PLEASE INDICATE SIZE AND USE | | OF PIPE PAN IS MADE FOR. PLEASE SHOW ALL | | MEASUREMENTS FOR PAN. LENGTH, WIDTH, | | HEIGHT. DRAIN CAN NOT CAUSE A NUISANCE | | BY DRAINING INTO A STAIRWAY OR WALKWAY. | | | | SUBMITTAL DENIED FOR TRENCH DRAINS. | | PLEASE SUBMIT MORE INFORMATION FROM THE | | MANUF. SHOWING APPROVAL AND OR STANDARDS | | WHICH THE TRENCH DRAINS MEET. LOBBY | | TRENCH DRAINS DO NOT INDICATE WHO MANUF. | | THE DRAINS AND IT SEEMS LIKE THE | | SPECIFICATIONS ARE GENERAL | | SPECIFICATIONS THAT ARE REQUIRED TO BE | | MET, BUT DOES NOT INDICATE THAT THE | | TRENCH DRAINS ARE MEETING THE | | STANDARDS. | | THE TRENCH DRAINS FOR THE POOL AREA DO | | NOT SEEM TO BE COMPLETE. ONE PAGE STATES | | MATERALS AND STANDARDS, BUT NO STANDARDS | | ARE REFERED TO. | | | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|