Plan Review Notes
Plan Review Notes For Permit 03031778
Permit Number 03031778
Review Stop P
Sequence Number 2
Notes
Date Text
2003-09-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 CITY WPB CODE
  
 A) FOLLOWING COMMENTS FROM THE FIRST RE-
 VIEW HAVE NOT BEEN ADDRESSED OR ANSWERED
 SUFFICIENTLY. THE NUMBER OF THE COMMENT
 FROM THE FIRST REVIEW WILL BE USED FOR
 CLAIRTY.
 7) SHT A-4.01 DETAIL #1 CLEAR FLOOR
 SPACE REQUIRED FOR ALL FIXTURES PER FHA-
 DESIGN MANUAL PAGE 7.43 (ALL UNITS).
 12) SHT A-2.11 SCUPPER DETAIL, SUBMIT
 INFO. FOR SCUPPERS SHOW ALL MEASUREMENTS
 & INDICATE SLOPEAT THE BOTTOM OF THE
 TRENCH IF ANY. SHOW LONGEST TRENCH MEAS-
 UREMENT. SECTION 104.2.1
 13) PLEASE IDENTIFY ALL WORK/LIVE LOFTS.
 TOILET ROOMS SHALL COMPLY WITH 11-4.22.
 ALL UNITS SHALL HAVE A DRINKING FOUNTAIN
 PER TABLE 403.1. (ALSO SEE 410.1)
 14) SUBMIT WORKSHEET FROM R. COMPO FOR
 GREASE INTERCEPTOR. ORD. 2938-96
 16) SHTS P2.1/P2.2 SEPARATE GAS PERMIT
 REQUIRED. THE FOLLOWING INFORMATION IS
 REQUIRED PRIOR TO PERMIT ISSUANCE.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - RISER NOT SUBMITTED IN
 ISOMETRIC FORM & ALL CUT SECTIONS OF
 PIPE LENGTHS NOT SHOWN.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 - INDICATE IF PIPE WILL BE WELDED OR
 SCREW PIPE. IF WILDED PIPE, WELDERS
 CERTIFICATE, AND PICTURE I.D. WILL BE
 REQUIRED WITH THE WELDING PROCEDURE BE-
 FOR STARTING.
 PLANS INDICATE 7" W.C.TABLES IN FBC-2001
 FUEL GAS SHOW MINIMUM GAS PRESSURE AT
 14" W.C. PLEASE VERIFY THE DELIVERY
 PRESSURE WITH GAS PROVIDER. PROVIDE
 TABEL USED FOR SIZING GAS PIPE. SUGGEST
 A 2 LB SYSTEM BE USED AS THE PIPE SIZE
 IS NOT SUFFICIENT FOR 1/2 LB PRESSURE.
 21) SHT P-4.1 KITCHEN SINK SHALL NOT
 DRAIN INTO THE WET VENT OF THE BATHROOM
 GROUP. SECTION 909.1.
 22) SHT P-4.2 SANT. RISER DOES NOT RE-
 FLECT THE FLOOR PLAN AT TUB & SHOWER.
 SHOWER NOT VENTED. SECTION 901.2.1
 23) SHT P-4.4 SANT. RISER DOES NOT RE-
 FLECT THE FLOOR PLAN. TUB NOT VENTED,
 SHOWER NOT VENTED. 104.2.1 - 901.2.1
 31) SHTS FOR ALL UNITS, WATER HAMMER
 ARRESTORS REQUIRED AT ICE MAKER LINE.
 SECTION 604.9
 33) SHT P-4.18 SANT. RISER KITCHEN SINK
 SHALL NOT DRAIN INTO WET VENT FOR BATH-
 ROOM GROUP. SECTION 909.1
 34) SHT P-5.1 RISER SR4 N/203/19 DFU NOT
 ADDED TO TOTAL FOR RISER.
 37) SHT P-5.4 DETAIL #1 RPZ BACKFLOW TO
 BE MAX. 4' ABOVE FLOOR FOR SERVICING AND
 TESTING.
 40) SHT P-5.5 INDICATES DETAIL FOR
 GREASE TRAP ON SHT P-7.1, BUT NO DETAIL
 FOUND. PROVIDE DETAIL.
 42) SHT P-5.5 DFU'S FROM GREASE TRAP NOT
 ADDED TO SYSTEM. RECALCULATE DFU'S. SHOW
 SLOPE OF PIPE ON RISER DIAGRAM.
 49) SHT P-5.6 PLEASE INDICATE MATERIAL
 FOR RELIEF VALVE & EMERGENCY PAN DRAIN
 RISERS. RESPONSE ON DETAIL #4 CALLS FOR
 CAST IRON DRAIN FOR HEATER PANS. PLEASE
 NOTE THAT MINIMUM SIZE FOR CAST IRON IS
 2". PLEASE CLAIRFY.
 52) SHT P-7.1 AIR CHAMBER DETAIL. AIR
 CHAMBERS ARE NOT APPROVED. PLEASE DELETE
 DETAIL.
 ********NEW COMMENTS*********
 1B) SHT P-1.2 COL. LINE 2/F NO CHANGE
 NOTED. CLO. LINE 2/K REVISION NOT CLOUD-
 ED. 104.2.1
 2B) SHT P-1.2 COL. LINE 11/R.2 SQUARE
 FOOTAGE DIFFERENT FROM RISER. PLEASE
 CLAIRFY 104.2.1
 3B) SHT P-1.2 15" STORM (58,220 SF) IN-
 DICATE SLOPE OF PIPE FOR HORIZONTAL OFF-
 SET. (SHT P1.3 INDICATES 54,570 SF,
 RISER SHT P5.6 INDICATES 63,464 SF BUT
 ADDS UP TO 64,689 SF. PLEAS CLAIRFY.
 PLEASE CHECK ALL SQUARE FOOTAGE FOR
 STORM PIPING. FLOOR PLAN AND RISERS FOR
 NOT REFLECT.104.2.1
 4B) SHTS P-1.3 & P-5.5 FLOOR PLAN & SANT
 RISER DIAGRAM. LOCKING VALVE FOR FOUNT-
 AIN POOL DRAINAGE NOT SHOWN ON FLOOR
 PLAN. 104.2.1
 5B) SHTS P=2.1 & P-5.6 6" RWL ON FLOOR
 PLAN SHOWS 6,150 SF - RISER SHOWS 6,750
 SF. PLEASE CLAIRFY.
 6B) SHTS P-2.1 & P-5.2 RISERS 27 THRU 41
 AT COL. LINE 8 SHOW 300 DFU'S ON FLOOR
 PLAN, BUT 370 DFU'S ON RISER. PLEASE
 CLAIRFY. 104.2.1
 7B) SHT P-2.2 POOL DRAIN LINE SHALL
 CONNECT TO STORM.
 8B) SHT P-2.2 SHUT OFF VALVE REQUIRED
 FOR BLDG WATER SERVICE. 606.1(2)
 9B) SHTS P-2.3 & P-5.5 8" SHOWS 1298 DFU
 ON FLOOR PLAN, BUT 1321 DFU ON RISER.
 PLEASE CLAIRFY. 104.2.1
 10B) SHTS P-2.4 & P-5.5 RISER DOES NOT
 REFLECT THE FLOOR PLAN. BRANCH TO TOILET
 ROOMS CONNECT TO DRAIN AFTER SR128 ON
 THE FLOOR PLAN, BUT PRIOR TO SR128 ON
 RISER DIAGRAM. PLEASE CLAIRFY. 104.2.1
 11B) SHTS P-2.4 & P-5.6 FLOOR PLAN SHOWS
 8" @ 10,050 SF, BUT RISER SHOWS 10" @
 9,450 SF. PLEASE CLAIRFY. 104.2.1
 12B) SHTS P-2.4 & P-5.6 FLOOR PLAN SHOWS
 1-1/2" CONDENSATE. NOT SHOWN ON RISER.
 PLEASE CLAIRFY. 104.2.1
 13B) SHTS P-2.5 & P-5.6 FLOOR PLAN SF &
 RISER SF DO NOT REFLECT.104.2.1
 14B) SHT P-2/5 SHOWS 4" RWL SHOWS 3,300
 SF UP, BUT 6" RWL DOWN AT 2,7OO SF.
 PLEASE CLAIRFY. 6" REQUIRED ON HORIZON-
 TAL OFFSETS. TABLE 1106.3 - 104.2.1
 15B) SUBMIT STORM RISERS. SHOW OFFSETS,
 PIPE SIZES, SQUARE FOOTAGE ECT.
 16B) SHT P-2.5 BATHROOM GROUPS SR48 & 49
 NOT SHOWN ON FLOOR PLAN. 104.2.1
 17B) SHT P-2.5 SR 28 NOT SHOWN ON FLOOR
 PLAN. 104.2.1
 18B) SHTS P-2.6 & P-5.6 FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAGRAM. POOL AREA
 TRENCH DRAINS NOT SHOWN. 104.2.1
 19B) SUBMIT CALCULATION FOR RWLS LARGER
 THAN 8". TABLE 1106.2 ONLY ADDRESSES
 PIPE SIZE TO 8" 104.2.1.2
 20B) SHTS P-2.6 & P-5.3 FLOOR PLAN SHOWS
 SR72 WITH 42 DFU'S AND RISER SHOWS 14
 DFU'S. PLEASE CLAIRFY. 104.2.1
 21B) SHT P-2.6 ACCUMULATIVE DFU'S APPEAR
 TO BE INCORRECT AFTER SR73. PLEASE RE-
 CALCULATE. 104.2.1
 22B) SHT P-2.8 COL LINE 3 BETWEEN COL'S
 C & D, A 6" RWL IN 8" CMU WALL NEXT TO
 STAIRWAY. PLEASE INDICATE HOW 2 HOUR
 FIRE RATING WILL BE MAINTAINED. S-704
 23B) SHT P-2.8 SIZE SANT PIPE FOR SR9,
 SR10, & SR11. TABLE 710.1(2)
 24B) SHTS P-2.9, P-2.10, P-2.11, & P-2.
 12, SANITARY RISER DIAGRAM LOCATIONS NOT
 SHOWN. 104.2.1
 25B) SHT P-4.3 TUB NOT E/03 & TUB AND
 LAV NOT VENTED B/11 901.2.1
 26B) SHT P-4.5 FIXTURES NOT VENTED AND
 RISER DOES NOT REFLECT FLOOR PLAN.
 901.2.1 - 104.2.1
 27B) SHT P-4.6 TUB NOT VENTED AND DOES
 NOT REFLECT FLOOR PLAN. 901.2.1/104.2.1.
 28B) SHT P-4.7 TUB NOT VENTED. W/M SHALL
 NOT DRAIN THROUGH BATHROOM FIXTURES.
 901.2.1/909.1
 29B) SHT P-4.9 TUB NOT VENTED. A-13 SEC.
 901.2.1
 30B) SHT P-4.10 SHOWER NOT VENTED. L-05
 901.2.1
 31B) SHT P-4.12 TUB NOT VENTED. A-17
 901.2.1
 32B) SHT P-4.13 TUB NOT VENTED. U-1
 901.2.1 - KITCHEN SINK & WASH MACHINE
 SHALL NOT DRAIN THROUGH BATHROOM GROUP
 R1(S). 909.1
 33B) SHT P-4.14 SHOWER NOT VENTED. S1(S)
 901.2.1
 34B) SHT P-4.15 TUB NOT VENTED. T1
 901.2.1
 35B) SHT P-4.17 SHOWER NOT VENTED. S1(N)
 901.2.1. CLAIRFY #10 AND TWO LINES ON
 RISER DIAGRAM UPPER LEVEL. AN AAV IS
 SHOWN UNDER SINK WITH ANOTHER IN WALL??
 S1(N)
 36B) ALL SANITARY RISER DIAGRAMS. THE
 HORIZONTAL BRANCH DRAIN SHALL COMFORM
 TO SECTION 917.3.1 OR 917.3.2. SECTION
 917.3. THE HORIZONTAL BRANCH SHALL BE
 PROVIDED WITH A RELIEF VENT THAT SHALL
 CONNECT TO A VENT STACK, OR A STACK VENT
 OR EXTEND OUTDOORS TO THE OPEN AIR.
 37B) ONE SET OF MECHANICAL PLANS HAS RED
 LINE INFORMATION. THIS MAY ASSIST IN
 EXPLAINING LOCATION & COMMENTS. RETURN
 WITH COMMENT RESPONSE WHEN RESUBMITTING
 FOR PLAN REVIEW TO HELP EXPEDITE REVIEW.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  