Date |
Text |
2003-09-12 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 11 |
| FBC-2001 BUILDING |
| FHA-98 DESIGN MANUAL |
| FLORIDA ADMINISTRATIVE CODE |
| CITY WPB CODE |
| |
| A) FOLLOWING COMMENTS FROM THE FIRST RE- |
| VIEW HAVE NOT BEEN ADDRESSED OR ANSWERED |
| SUFFICIENTLY. THE NUMBER OF THE COMMENT |
| FROM THE FIRST REVIEW WILL BE USED FOR |
| CLAIRTY. |
| 7) SHT A-4.01 DETAIL #1 CLEAR FLOOR |
| SPACE REQUIRED FOR ALL FIXTURES PER FHA- |
| DESIGN MANUAL PAGE 7.43 (ALL UNITS). |
| 12) SHT A-2.11 SCUPPER DETAIL, SUBMIT |
| INFO. FOR SCUPPERS SHOW ALL MEASUREMENTS |
| & INDICATE SLOPEAT THE BOTTOM OF THE |
| TRENCH IF ANY. SHOW LONGEST TRENCH MEAS- |
| UREMENT. SECTION 104.2.1 |
| 13) PLEASE IDENTIFY ALL WORK/LIVE LOFTS. |
| TOILET ROOMS SHALL COMPLY WITH 11-4.22. |
| ALL UNITS SHALL HAVE A DRINKING FOUNTAIN |
| PER TABLE 403.1. (ALSO SEE 410.1) |
| 14) SUBMIT WORKSHEET FROM R. COMPO FOR |
| GREASE INTERCEPTOR. ORD. 2938-96 |
| 16) SHTS P2.1/P2.2 SEPARATE GAS PERMIT |
| REQUIRED. THE FOLLOWING INFORMATION IS |
| REQUIRED PRIOR TO PERMIT ISSUANCE. |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. - RISER NOT SUBMITTED IN |
| ISOMETRIC FORM & ALL CUT SECTIONS OF |
| PIPE LENGTHS NOT SHOWN. |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| - INDICATE IF PIPE WILL BE WELDED OR |
| SCREW PIPE. IF WILDED PIPE, WELDERS |
| CERTIFICATE, AND PICTURE I.D. WILL BE |
| REQUIRED WITH THE WELDING PROCEDURE BE- |
| FOR STARTING. |
| PLANS INDICATE 7" W.C.TABLES IN FBC-2001 |
| FUEL GAS SHOW MINIMUM GAS PRESSURE AT |
| 14" W.C. PLEASE VERIFY THE DELIVERY |
| PRESSURE WITH GAS PROVIDER. PROVIDE |
| TABEL USED FOR SIZING GAS PIPE. SUGGEST |
| A 2 LB SYSTEM BE USED AS THE PIPE SIZE |
| IS NOT SUFFICIENT FOR 1/2 LB PRESSURE. |
| 21) SHT P-4.1 KITCHEN SINK SHALL NOT |
| DRAIN INTO THE WET VENT OF THE BATHROOM |
| GROUP. SECTION 909.1. |
| 22) SHT P-4.2 SANT. RISER DOES NOT RE- |
| FLECT THE FLOOR PLAN AT TUB & SHOWER. |
| SHOWER NOT VENTED. SECTION 901.2.1 |
| 23) SHT P-4.4 SANT. RISER DOES NOT RE- |
| FLECT THE FLOOR PLAN. TUB NOT VENTED, |
| SHOWER NOT VENTED. 104.2.1 - 901.2.1 |
| 31) SHTS FOR ALL UNITS, WATER HAMMER |
| ARRESTORS REQUIRED AT ICE MAKER LINE. |
| SECTION 604.9 |
| 33) SHT P-4.18 SANT. RISER KITCHEN SINK |
| SHALL NOT DRAIN INTO WET VENT FOR BATH- |
| ROOM GROUP. SECTION 909.1 |
| 34) SHT P-5.1 RISER SR4 N/203/19 DFU NOT |
| ADDED TO TOTAL FOR RISER. |
| 37) SHT P-5.4 DETAIL #1 RPZ BACKFLOW TO |
| BE MAX. 4' ABOVE FLOOR FOR SERVICING AND |
| TESTING. |
| 40) SHT P-5.5 INDICATES DETAIL FOR |
| GREASE TRAP ON SHT P-7.1, BUT NO DETAIL |
| FOUND. PROVIDE DETAIL. |
| 42) SHT P-5.5 DFU'S FROM GREASE TRAP NOT |
| ADDED TO SYSTEM. RECALCULATE DFU'S. SHOW |
| SLOPE OF PIPE ON RISER DIAGRAM. |
| 49) SHT P-5.6 PLEASE INDICATE MATERIAL |
| FOR RELIEF VALVE & EMERGENCY PAN DRAIN |
| RISERS. RESPONSE ON DETAIL #4 CALLS FOR |
| CAST IRON DRAIN FOR HEATER PANS. PLEASE |
| NOTE THAT MINIMUM SIZE FOR CAST IRON IS |
| 2". PLEASE CLAIRFY. |
| 52) SHT P-7.1 AIR CHAMBER DETAIL. AIR |
| CHAMBERS ARE NOT APPROVED. PLEASE DELETE |
| DETAIL. |
| ********NEW COMMENTS********* |
| 1B) SHT P-1.2 COL. LINE 2/F NO CHANGE |
| NOTED. CLO. LINE 2/K REVISION NOT CLOUD- |
| ED. 104.2.1 |
| 2B) SHT P-1.2 COL. LINE 11/R.2 SQUARE |
| FOOTAGE DIFFERENT FROM RISER. PLEASE |
| CLAIRFY 104.2.1 |
| 3B) SHT P-1.2 15" STORM (58,220 SF) IN- |
| DICATE SLOPE OF PIPE FOR HORIZONTAL OFF- |
| SET. (SHT P1.3 INDICATES 54,570 SF, |
| RISER SHT P5.6 INDICATES 63,464 SF BUT |
| ADDS UP TO 64,689 SF. PLEAS CLAIRFY. |
| PLEASE CHECK ALL SQUARE FOOTAGE FOR |
| STORM PIPING. FLOOR PLAN AND RISERS FOR |
| NOT REFLECT.104.2.1 |
| 4B) SHTS P-1.3 & P-5.5 FLOOR PLAN & SANT |
| RISER DIAGRAM. LOCKING VALVE FOR FOUNT- |
| AIN POOL DRAINAGE NOT SHOWN ON FLOOR |
| PLAN. 104.2.1 |
| 5B) SHTS P=2.1 & P-5.6 6" RWL ON FLOOR |
| PLAN SHOWS 6,150 SF - RISER SHOWS 6,750 |
| SF. PLEASE CLAIRFY. |
| 6B) SHTS P-2.1 & P-5.2 RISERS 27 THRU 41 |
| AT COL. LINE 8 SHOW 300 DFU'S ON FLOOR |
| PLAN, BUT 370 DFU'S ON RISER. PLEASE |
| CLAIRFY. 104.2.1 |
| 7B) SHT P-2.2 POOL DRAIN LINE SHALL |
| CONNECT TO STORM. |
| 8B) SHT P-2.2 SHUT OFF VALVE REQUIRED |
| FOR BLDG WATER SERVICE. 606.1(2) |
| 9B) SHTS P-2.3 & P-5.5 8" SHOWS 1298 DFU |
| ON FLOOR PLAN, BUT 1321 DFU ON RISER. |
| PLEASE CLAIRFY. 104.2.1 |
| 10B) SHTS P-2.4 & P-5.5 RISER DOES NOT |
| REFLECT THE FLOOR PLAN. BRANCH TO TOILET |
| ROOMS CONNECT TO DRAIN AFTER SR128 ON |
| THE FLOOR PLAN, BUT PRIOR TO SR128 ON |
| RISER DIAGRAM. PLEASE CLAIRFY. 104.2.1 |
| 11B) SHTS P-2.4 & P-5.6 FLOOR PLAN SHOWS |
| 8" @ 10,050 SF, BUT RISER SHOWS 10" @ |
| 9,450 SF. PLEASE CLAIRFY. 104.2.1 |
| 12B) SHTS P-2.4 & P-5.6 FLOOR PLAN SHOWS |
| 1-1/2" CONDENSATE. NOT SHOWN ON RISER. |
| PLEASE CLAIRFY. 104.2.1 |
| 13B) SHTS P-2.5 & P-5.6 FLOOR PLAN SF & |
| RISER SF DO NOT REFLECT.104.2.1 |
| 14B) SHT P-2/5 SHOWS 4" RWL SHOWS 3,300 |
| SF UP, BUT 6" RWL DOWN AT 2,7OO SF. |
| PLEASE CLAIRFY. 6" REQUIRED ON HORIZON- |
| TAL OFFSETS. TABLE 1106.3 - 104.2.1 |
| 15B) SUBMIT STORM RISERS. SHOW OFFSETS, |
| PIPE SIZES, SQUARE FOOTAGE ECT. |
| 16B) SHT P-2.5 BATHROOM GROUPS SR48 & 49 |
| NOT SHOWN ON FLOOR PLAN. 104.2.1 |
| 17B) SHT P-2.5 SR 28 NOT SHOWN ON FLOOR |
| PLAN. 104.2.1 |
| 18B) SHTS P-2.6 & P-5.6 FLOOR PLAN DOES |
| NOT REFLECT THE RISER DIAGRAM. POOL AREA |
| TRENCH DRAINS NOT SHOWN. 104.2.1 |
| 19B) SUBMIT CALCULATION FOR RWLS LARGER |
| THAN 8". TABLE 1106.2 ONLY ADDRESSES |
| PIPE SIZE TO 8" 104.2.1.2 |
| 20B) SHTS P-2.6 & P-5.3 FLOOR PLAN SHOWS |
| SR72 WITH 42 DFU'S AND RISER SHOWS 14 |
| DFU'S. PLEASE CLAIRFY. 104.2.1 |
| 21B) SHT P-2.6 ACCUMULATIVE DFU'S APPEAR |
| TO BE INCORRECT AFTER SR73. PLEASE RE- |
| CALCULATE. 104.2.1 |
| 22B) SHT P-2.8 COL LINE 3 BETWEEN COL'S |
| C & D, A 6" RWL IN 8" CMU WALL NEXT TO |
| STAIRWAY. PLEASE INDICATE HOW 2 HOUR |
| FIRE RATING WILL BE MAINTAINED. S-704 |
| 23B) SHT P-2.8 SIZE SANT PIPE FOR SR9, |
| SR10, & SR11. TABLE 710.1(2) |
| 24B) SHTS P-2.9, P-2.10, P-2.11, & P-2. |
| 12, SANITARY RISER DIAGRAM LOCATIONS NOT |
| SHOWN. 104.2.1 |
| 25B) SHT P-4.3 TUB NOT E/03 & TUB AND |
| LAV NOT VENTED B/11 901.2.1 |
| 26B) SHT P-4.5 FIXTURES NOT VENTED AND |
| RISER DOES NOT REFLECT FLOOR PLAN. |
| 901.2.1 - 104.2.1 |
| 27B) SHT P-4.6 TUB NOT VENTED AND DOES |
| NOT REFLECT FLOOR PLAN. 901.2.1/104.2.1. |
| 28B) SHT P-4.7 TUB NOT VENTED. W/M SHALL |
| NOT DRAIN THROUGH BATHROOM FIXTURES. |
| 901.2.1/909.1 |
| 29B) SHT P-4.9 TUB NOT VENTED. A-13 SEC. |
| 901.2.1 |
| 30B) SHT P-4.10 SHOWER NOT VENTED. L-05 |
| 901.2.1 |
| 31B) SHT P-4.12 TUB NOT VENTED. A-17 |
| 901.2.1 |
| 32B) SHT P-4.13 TUB NOT VENTED. U-1 |
| 901.2.1 - KITCHEN SINK & WASH MACHINE |
| SHALL NOT DRAIN THROUGH BATHROOM GROUP |
| R1(S). 909.1 |
| 33B) SHT P-4.14 SHOWER NOT VENTED. S1(S) |
| 901.2.1 |
| 34B) SHT P-4.15 TUB NOT VENTED. T1 |
| 901.2.1 |
| 35B) SHT P-4.17 SHOWER NOT VENTED. S1(N) |
| 901.2.1. CLAIRFY #10 AND TWO LINES ON |
| RISER DIAGRAM UPPER LEVEL. AN AAV IS |
| SHOWN UNDER SINK WITH ANOTHER IN WALL?? |
| S1(N) |
| 36B) ALL SANITARY RISER DIAGRAMS. THE |
| HORIZONTAL BRANCH DRAIN SHALL COMFORM |
| TO SECTION 917.3.1 OR 917.3.2. SECTION |
| 917.3. THE HORIZONTAL BRANCH SHALL BE |
| PROVIDED WITH A RELIEF VENT THAT SHALL |
| CONNECT TO A VENT STACK, OR A STACK VENT |
| OR EXTEND OUTDOORS TO THE OPEN AIR. |
| 37B) ONE SET OF MECHANICAL PLANS HAS RED |
| LINE INFORMATION. THIS MAY ASSIST IN |
| EXPLAINING LOCATION & COMMENTS. RETURN |
| WITH COMMENT RESPONSE WHEN RESUBMITTING |
| FOR PLAN REVIEW TO HELP EXPEDITE REVIEW. |
| *********WHEN RESUBMITTING PLANS******** |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| REVIEW BY KEN STEVENS |