Plan Review Notes
Plan Review Notes For Permit 03031778
Permit Number 03031778
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2003-08-29 00:00:001) SHAFTWAY SIGNS SHALL BE AT LEAST
 6" HIGH.
  
 2) KNOX-BOXES WILL BE REQUIRED.
  
 3) HOW DOES THE CARD SWIPE DEVICE USED
 FOR ACCESS NEAR SAUNA 165 EFFECT
 EXITING.
  
 4) PLEASE REVIEW ID-12 WHERE THE TRASH
 CHUTE OPENS INTO THE CORRIDOR NEAR
 THE TOP OF THE PAGE. IT APPEARS THE DOOR
 OPENS INTO THE CORRIDOR MORE THAN
 50 PERCENT.
  
 5) EXPANDED STYRENE OBSERVED ON A-10.10.
 PLEASE SEE APPENDIX F, OF THE LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING
 CODE.
  
 6) LOFT STAIRS ON PAGE A-10.07 ARE
 NOT WIDE ENOUGH. IF OCCUPANT LOADS
 OF LESS THAN 50 ARE EXPECTED THEN
 STAIR CAN BE 36" WIDE.
  
 7) FE CABINET ON A-10.07 INDICATES
 BREAK GLASS. HOW IS BREAK GLASS DONE.
 NO BREAK GLASS ROD SHOWN.
  
 8) PLEASE CONFIRM THAT THE EXIT SIGNS
 SHOWN ON A-10.03 COMPLIES WITH
 CHAPTER 7, OF THE LIFE SAFETY CODE.
  
 9) EXTERIOR GRADE PLYWOOD SHOWN ON
 SOME ROOF DETAILS. PLEASE SEE APPENDIX
 F, OF THE LOCAL AMENDMENTS TO THE
 FLORIDA BUILDING CODE.
  
 10) TRASH CHUTE SECTION MAKES NO
 REFERENCE ABOUT FIRE RATED DOORS,
 FIRE SPRINKLERS, OR BOTTOM DOOR.
  
 11) PLEASE DESCRIBE VOID AREA ON
 PAGE A-6.06.
  
 12) IT APPEARS THAT THE BUILDING
 CAN BE CONSIDERED A HIGH-RISE BUILDING
 ACCORDING TO THE BUILDING SECTIONS.
  
 13) ITEMS ON THE BUILDING STILL APPEAR
 TO PROTECT OVER THE PROPERTY LINES
 ACCORDING TO THE BUILDING SECTION
 DIAGRAMS.
  
 14) IT APPEARS THAT EXITING ON LEVELS
 B1 AND B2 PASSES BY IN SOME CASES
 PARKING SPACES THAT PERSONS MUST
 BACKUP.
  
 15) SIGNS WILL BE NEEDED TO IDENTIFY
 THE STRETCHER ACCESSIBLE ELEVATORS.
  
 16) IT APPEARS THAT THE DOOR AT
 GROUND LEVEL FOR STAIR # 3 OPENS
 DIRECTLY INFRONT OF A WALL.
  
 17) PLEASE INDICATE HOW STAIR # 1
 LEADS DIRECTLY TO THE EXTERIOR. IT
 APPEARS TO TERMINATE WITHIN THE
 BUILDING.
  
 18) IF LESS THAN THREE STEPS ARE PLANNED
 FOR A LOCATION, THEN THE MINIMUM TREAD
 DEPTH MUST BE AT LEAST 13" WIDE.
  
 19) STAIRS THAT FACE CITY STREETS AT
 GROUND LEVEL DO NOT APPEAR TO HAVE
 HANDRAILS.
  
 20) SECOND FLOOR LIFE SAFETY PLAN CHART
 INDICATES AN OCCUPANT LOAD OF 560
 PERSONS. YOUR COMMENTS OF 540 OCCUPANTS
 ALLOWED AND 526 PERSONS ALLOWED DO
 NOT ALIGN THEMSELVES WITH ONE ANOTHER.
  
 21) COULD NOT LOCATE ANY STAIRS TO
 THE ROOF ON THE ROOF PLAN.
  
 22) THE FIRE ALARM ANNUNCIATOR SHOULD
 BE INSTALLED NEAR THE MAIN ENTRY DOORS
 NOT IN THE FIRE COMMAND ROOM WHERE THE
 MAIN PANEL WILL BE LOCATED.
  
 23) PLEASE EXPLAIN NOTE # 12 ON FIRE
 ALARM SEQUENCE OF OPERATIONS.
  
 24) FIRE SPRINKLER PROTECTION WILL
 BE REQUIRED TO BE INSTALLED IN THE
 RETAIL SPACES OF THE BUILDING PRIOR
 TO RECEIVING A C OF O.
  
 25) THE FIRE COMMAND ROOM NOTES ON
 E-2.5 IS NOT CORRECT. PLEASE SEE
 FBC, SECTION 412 FIRE COMMAND ROOMS.
  
 26) ALL MECHANICAL, ELECTRICAL, AND
 SERVICE ROOMS SHALL BE EQUIPPED WITH
 SMOKE DETECTORS.
  
 27) NO EXIT SIGNS SHOWN IDENTIFYING
 EXIT LOCATIONS FROM POOL AND PLANTER
 AREA.
  
 28) ALL HOSE VALVES SHALL BE PROVIDED
 WITH 2 1/2 TO 1 1/2 REDUCERS.
  
 29) WHERE IS THE FIRE PROTECTION FOR
 THE UNIT LOWER LEVEL FLOOR PLAN
 BETWEEN THE TWO DOORS NEAR THE
 HANDICAPPED BATHROOM ON FP-4.10.
  
 30) NO STANDPIPE INDICATED ON FP -1.1.
  
 31) FDC ON PAGE FP-2.2 IS FACING THE
 WRONG WAY.
  
 32) UNIT C/17 ON PAGE FP-4.4 DOES NOT
 APPEAR TO HAVE ENOUGH SPRINKLER
 COVERAGE.
  
 33) PLEASE PROVIDE A DIAGRAM FOR
 THE SMOKE MANAGEMENT PANEL IN THE
 FIRE ALARM CONTROL ROOM.
  
 34) STAIRWELL PRESSURIZATION WATER
 COLUMN REQUIREMENTS SHALL BE NOTED
 ON THE PLANS. ALSO TESTING REQUIREMENTS
 SHALL BE DOCUMENTED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910