Date |
Text |
2003-08-29 00:00:00 | 1) SHAFTWAY SIGNS SHALL BE AT LEAST |
| 6" HIGH. |
| |
| 2) KNOX-BOXES WILL BE REQUIRED. |
| |
| 3) HOW DOES THE CARD SWIPE DEVICE USED |
| FOR ACCESS NEAR SAUNA 165 EFFECT |
| EXITING. |
| |
| 4) PLEASE REVIEW ID-12 WHERE THE TRASH |
| CHUTE OPENS INTO THE CORRIDOR NEAR |
| THE TOP OF THE PAGE. IT APPEARS THE DOOR |
| OPENS INTO THE CORRIDOR MORE THAN |
| 50 PERCENT. |
| |
| 5) EXPANDED STYRENE OBSERVED ON A-10.10. |
| PLEASE SEE APPENDIX F, OF THE LOCAL |
| AMENDMENTS TO THE FLORIDA BUILDING |
| CODE. |
| |
| 6) LOFT STAIRS ON PAGE A-10.07 ARE |
| NOT WIDE ENOUGH. IF OCCUPANT LOADS |
| OF LESS THAN 50 ARE EXPECTED THEN |
| STAIR CAN BE 36" WIDE. |
| |
| 7) FE CABINET ON A-10.07 INDICATES |
| BREAK GLASS. HOW IS BREAK GLASS DONE. |
| NO BREAK GLASS ROD SHOWN. |
| |
| 8) PLEASE CONFIRM THAT THE EXIT SIGNS |
| SHOWN ON A-10.03 COMPLIES WITH |
| CHAPTER 7, OF THE LIFE SAFETY CODE. |
| |
| 9) EXTERIOR GRADE PLYWOOD SHOWN ON |
| SOME ROOF DETAILS. PLEASE SEE APPENDIX |
| F, OF THE LOCAL AMENDMENTS TO THE |
| FLORIDA BUILDING CODE. |
| |
| 10) TRASH CHUTE SECTION MAKES NO |
| REFERENCE ABOUT FIRE RATED DOORS, |
| FIRE SPRINKLERS, OR BOTTOM DOOR. |
| |
| 11) PLEASE DESCRIBE VOID AREA ON |
| PAGE A-6.06. |
| |
| 12) IT APPEARS THAT THE BUILDING |
| CAN BE CONSIDERED A HIGH-RISE BUILDING |
| ACCORDING TO THE BUILDING SECTIONS. |
| |
| 13) ITEMS ON THE BUILDING STILL APPEAR |
| TO PROTECT OVER THE PROPERTY LINES |
| ACCORDING TO THE BUILDING SECTION |
| DIAGRAMS. |
| |
| 14) IT APPEARS THAT EXITING ON LEVELS |
| B1 AND B2 PASSES BY IN SOME CASES |
| PARKING SPACES THAT PERSONS MUST |
| BACKUP. |
| |
| 15) SIGNS WILL BE NEEDED TO IDENTIFY |
| THE STRETCHER ACCESSIBLE ELEVATORS. |
| |
| 16) IT APPEARS THAT THE DOOR AT |
| GROUND LEVEL FOR STAIR # 3 OPENS |
| DIRECTLY INFRONT OF A WALL. |
| |
| 17) PLEASE INDICATE HOW STAIR # 1 |
| LEADS DIRECTLY TO THE EXTERIOR. IT |
| APPEARS TO TERMINATE WITHIN THE |
| BUILDING. |
| |
| 18) IF LESS THAN THREE STEPS ARE PLANNED |
| FOR A LOCATION, THEN THE MINIMUM TREAD |
| DEPTH MUST BE AT LEAST 13" WIDE. |
| |
| 19) STAIRS THAT FACE CITY STREETS AT |
| GROUND LEVEL DO NOT APPEAR TO HAVE |
| HANDRAILS. |
| |
| 20) SECOND FLOOR LIFE SAFETY PLAN CHART |
| INDICATES AN OCCUPANT LOAD OF 560 |
| PERSONS. YOUR COMMENTS OF 540 OCCUPANTS |
| ALLOWED AND 526 PERSONS ALLOWED DO |
| NOT ALIGN THEMSELVES WITH ONE ANOTHER. |
| |
| 21) COULD NOT LOCATE ANY STAIRS TO |
| THE ROOF ON THE ROOF PLAN. |
| |
| 22) THE FIRE ALARM ANNUNCIATOR SHOULD |
| BE INSTALLED NEAR THE MAIN ENTRY DOORS |
| NOT IN THE FIRE COMMAND ROOM WHERE THE |
| MAIN PANEL WILL BE LOCATED. |
| |
| 23) PLEASE EXPLAIN NOTE # 12 ON FIRE |
| ALARM SEQUENCE OF OPERATIONS. |
| |
| 24) FIRE SPRINKLER PROTECTION WILL |
| BE REQUIRED TO BE INSTALLED IN THE |
| RETAIL SPACES OF THE BUILDING PRIOR |
| TO RECEIVING A C OF O. |
| |
| 25) THE FIRE COMMAND ROOM NOTES ON |
| E-2.5 IS NOT CORRECT. PLEASE SEE |
| FBC, SECTION 412 FIRE COMMAND ROOMS. |
| |
| 26) ALL MECHANICAL, ELECTRICAL, AND |
| SERVICE ROOMS SHALL BE EQUIPPED WITH |
| SMOKE DETECTORS. |
| |
| 27) NO EXIT SIGNS SHOWN IDENTIFYING |
| EXIT LOCATIONS FROM POOL AND PLANTER |
| AREA. |
| |
| 28) ALL HOSE VALVES SHALL BE PROVIDED |
| WITH 2 1/2 TO 1 1/2 REDUCERS. |
| |
| 29) WHERE IS THE FIRE PROTECTION FOR |
| THE UNIT LOWER LEVEL FLOOR PLAN |
| BETWEEN THE TWO DOORS NEAR THE |
| HANDICAPPED BATHROOM ON FP-4.10. |
| |
| 30) NO STANDPIPE INDICATED ON FP -1.1. |
| |
| 31) FDC ON PAGE FP-2.2 IS FACING THE |
| WRONG WAY. |
| |
| 32) UNIT C/17 ON PAGE FP-4.4 DOES NOT |
| APPEAR TO HAVE ENOUGH SPRINKLER |
| COVERAGE. |
| |
| 33) PLEASE PROVIDE A DIAGRAM FOR |
| THE SMOKE MANAGEMENT PANEL IN THE |
| FIRE ALARM CONTROL ROOM. |
| |
| 34) STAIRWELL PRESSURIZATION WATER |
| COLUMN REQUIREMENTS SHALL BE NOTED |
| ON THE PLANS. ALSO TESTING REQUIREMENTS |
| SHALL BE DOCUMENTED. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 835-2910 |