2003-08-15 00:00:00 | FAILED: |
| 1. SHEET C-1.1 SHOWS STAIRS LEADING TO |
| GROUND FLOOR ON DATURA ARE EXTENDED INTO |
| THE SIDEWALKS, THIS WILL CREATE A PUBLIC |
| SAFETY ISSUE. |
| 2. SHEET C-1.1 CALLS FOR MILLING OF 7" |
| IN DATURA AND CLIMATIS, PLEASE VERIFY |
| THE ADEQUACY OF THE EXISTING BASE. |
| DETAILS FOR RECONSTRUCTION SHOULD BE |
| SHOWN. |
| 3. PLEASE CALL OUT THE ACCESS RAMP TO |
| ROSEMARY STREET. |
| 4. SHEET C-2.1 SHOWS TWO DETAILS FOR THE |
| CONTROL STRUCTURES #5, ONE SHOULD BE FOR |
| #6, PLEASE VERIFY. ALSO CHECK THE |
| "STRUCTURE TABLE" FOR INVERT AND RIM |
| ELEVATIONS. |
| 5. PLEASE ADD NOTE TO G.C. TO CONTACT |
| PARKING ADMINISTRATION, SUE OLEY @ |
| 659-8022 EXT. 8122 TO COORDINATE THE |
| RELOCATION OF THE PARKING METERS ON |
| DATURA AND CLIMATIS. |
| 6. BEGIN MILLING AND RESURFACING ON |
| DATURA TO INCLUDE NEWLY INSTALLED |
| MANHOLED #2. |
| 7. PLEASE CLARIFY THE CONNECTION FOR 2" |
| PVC IRRIGATION SERVICE LINE, SHEET C-3.1 |
| AND C-3.2 . |
| 8. PLEASE ADD NOTE TO G.C. THAT IT SHALL |
| BE THE RESPONSIBILITY OF THE CONTRACTOR |
| TO RESTORE THE EXISTING SIDEWAKS, CURB |
| & GUTTERS, TREES LIGHT POLES, PARKING |
| METTERS, IRRIGATION SYS, ETC. ADJACENT |
| TO PROPERTY ALL SIDES TO THE ORIGINAL OR |
| BETTER IF DAMAGE DURING THE CONSTRUCTION |
| 9. PLEASE SUBMIT STORM WATER CALCULATION |
| FOR OUR REVIEW, THIS SUBMITTAL SHOULD |
| INCLUDE PERVIOUS AND IMPERVIOUS AREA |
| CALCULATIONS FOR THE ENTIRE SITE, AND |
| ALSO A COPY OF SFWMD PERMIT.(SIGNED & |
| SEALED) |
| 10. PLEASE NOTE THAT CIVIL PLANS SHOULD |
| INCLUDE POLLUTION/ EROSION PREVENTION |
| PLAN AND NOTE TO G.C. TO INSTALL IN |
| FIELD PRIOR TO ANY CONSTRUCTION. |
| 11. FDC ( FIRE DEPARTMENT CONNECTION) |
| MUST BE SHOWN ON CIVIL PLANS, 150' MAX. |
| FROM A EXISTING FIRE HYDRANT. |
| 12. PLEASE NOTE THAT A SEPARATE PERMIT |
| APPLICATION AND FEES FOR UNDERGROUND |
| UTILITIES AND SITE WORK WILL BE REQUIRED |
| |
| IF ANY QUESTION PLEASE CONTACT 805-6723 |
| MOHAMMAD R. AMINI |