Plan Review Notes
Plan Review Notes For Permit 03031778
Permit Number 03031778
Review Stop B
Sequence Number 19
Notes
Date Text
2004-08-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03031778
 ADD: 610 CLEMATIS ST
 CONT: THE WHITING-TURNER CO
 TEL: (561)###-####
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 REVISIONS
 ACTION: DENIED
  
 1) AS ASKED FROM FIRST MEETING OVER RE-
 VISIONS THE SUBMITTED PLANS DO NOT MATCH
 THE APPROVED CITY PLANS AS FAR AS THE
 NUMBERING SYSTEM. CITY APPROVED PLANS
 MAY HAVE UP TO 13 REVISIONS ON THE NEW
 PLANS SEQUENCE STARTS OVER AGAIN.
  
 2) REVISIONS FULL ROLL ARCH & STRUC
 DRAWINGS DENIED:
 REVISIONS WHITE OUT USED,
 104.2.1.3 THE BUILDING OFFICIAL
 MAY SET STANDARDS THROUGH DEPARTMENTAL
 POLICY STANDARDS FOR PLANS AND SPRCIFICA
 TIONS. "NO WHITE OUT".
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 WHERE THE WHITE OUT WAS USED THE
 REVISION DOES NOT HAVE THE SIGNATURE &
 DATE OF THE ARCHITECT OF RECORD.
 A-4.03 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.04 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.04ASEC 1 WHITE OUT/ HAND WRITTEN "B"
 ELE DON,T NUMBERING SEQUENCE
 A-4.06 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.07 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.07 MISSING ELE 1,2,3 OR MIS-
 LABELED
 A-4.08 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.09 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.10 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A4-10.1SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.11 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.16 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.16ASEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.18 SEC 1 WHITE OUT/ TYPE_ BLANK
 A-4.21 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.21ASEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.24 SEC 1 WHITE OUT/ HAND WRITTEN "B"
  
 3) SHEET F1/F2 FOUNTAIN SHEETS:
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 4) FOUNTAIN SHEETS F1/F2 REQUIRE SEPER-
 ATE PERMITS, NOT PART OF THIS PERMIT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026