Plan Review Notes
Plan Review Notes For Permit 03031778
Permit Number 03031778
Review Stop P
Sequence Number 17
Notes
Date Text
2004-11-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
  
 1) SHT P-1.2 UNABLE TO LOCATE REVISION
 NUMBER ONE. MANY CHANGES ON PLANS WITH
 NO CLOUDS OR REVISION NUMBERS - CLOUD
 AND NUMBER ALL REVISIONS SUBMITTED FOR
 REVIEW. SECTION 104.2.1
 2) SHT P-1.3 10" (10,830 INDICATE SF FOR
 ALL PIPING UPSTREAM OF 10" BETWEEN COLS.
 J & S AT COL. 14. - NO REVISION NUMBER
 FOR CLOUD AT COLS. 1.1 THRU 7.1 BETWEEN
 COLS. T.1 & U.4. SHOW REVISION NUMBER.
 SECTION 104.2.1
 3) SHT P2.2 NOTE TO CONTRACTOR: ENGINEER
 INDICATED THAT GAS PIPING WAS TO BE
 SCREW PIPING. NOTE STATES WELDED PIPE.
 PLEASE CLARIFY. SECTION 104.2.1
 4) REMOVE ALL SHEETS NOT PART OF THE
 REVISION. DO NOT SUBMIT VOIDED SHEETS.
 SECTION 1014.2.1.3
 5) SHT P-2.4 INDICATE WHAT BLDG DEPT
 COMMENTS GENERATED REVISIONS 1 & 13.
 REVISION 11 & 12 WERE NOT FOUND.
 ORIGNIAL PERMIT STAMPED SET OF PLANS ALL
 READY HAS REVISIONS 1 & 13. PLEASE
 CLARIFY. SECTION 104.2.1
 6) SHT P-2.5 DOWNSTREAM OF SR/46 SHOWS
 202 DFU, 4' PIPE, THEN SR/48 ADDS 33 DFU
 FOR 193 DFU. PLEASE CLAARIFY. DOWNSTREAM
 OF SR/49 TOTAL IS 277 (193 & 44). PLEASE
 CLARIFY. PLEASE RECHECK ALL DFU'S IN THE
 SYSTEM. - PREVIOUS REVISIONS 11 & 13 ON
 THE PERMIT STAMPED SET OF PLANS. PLEASE
 CLARIFY. SECTION 104.2.1
 7) SHT P-2.6 SUBMIT BLDG DEPT COMMENTS
 THAT RESULTED IN REVISIONS 1 & 13. THESE
 NUMBERS WERE ON STAMPED SET OF PLANS.
 PLEASE CLARIFY. - THERE ARE MORE
 REVISIONS TO THE STAMPED SET OF PLANS
 THAT ARE NOT CLOUDED OR NUMBERED.
 SECTION 104.2.1
 8) SHTS P-4.4 & P-5.1 RISER UR-3 TUB NOT
 VENTED ON THE RISER OR ON THE FLOOR
 PLAN
 SECTIONS 104.2.1/901.2.1
 9) SHT P-5.2 VENTING CHANGES NOT CLOUDED
 OR NUMBERED. INDICATE COMMENTS REFERRED
 TO FOR REV'S 1 & 13. RISERS DO NOT
 REFLECT THE CHANGES FROM COMMENT #11
 FROM THE PREVIOUS REVISION REVIEW. -
 THIS COMMENT FOR SHEETS P-5.3, P-5.3.2,
 ALSO. SHT 104.2.1
 10) SHT P-5.5 REVISIONS WITH NO CLOUD OR
 NUMBER ON SANT. LINE FROM SR/192 TO
 SANT
 DOWNSTREAM OF GREASE INTERCEPTOR, AND 2
 AREAS OF RISER DO NOT REFLECT FLOOR PLAN
 AT SR/128 & AT SR/6 & SR/7 (SEE SHT
 P-2.4) - 8"(1471 DFU), 12 FROM (3975
 DFU) THRU 12" (4269 DFU) SHALL BE
 MINIMUM 1/8" PER FT. SLOPE. INDICATE ON
 PLANS. SECTION 104.2.1. - SHOW LENGTH OF
 PIPE FOR GAS ISOMETRIC MISSING FROM
 STAMPED SET OF PLANS.
 11) SEE ATTACHED SHEET FROM PREVIOUS
 REVISION REVIEW. SOME COMMENTS WERE NOT
 ADDRESSED AND STILL APPLY.
  
  
  
 REVIEW BY KEN STEVENS