2005-12-19 00:00:00 | ******* UNSAT ******** |
| |
| PLEASE SEE SOME NOTES FROM PREVIOUS |
| REVIEW AND SOME NEW NOTES DUE TO |
| INFORMATION ADDED TO PLANS. |
| |
| |
| |
| 1)NOTE: PLEASE SEE MIN CLEARENCE |
| REQUIREMENTS FOR MAIN ELECTRICAL ROOM. |
| PLEASE ALSO SEE THAT A MIN 6' OPENING |
| AND DOUBLE WORKING SPACE. |
| THIS WAS NOTED AS BEING CORRECTED , |
| HOWEVER PLANS STILL SHOWN WITH OUT |
| CHANGES MADE. |
| 110.26 |
| |
| 2)NOTE: PLEASE SEE V-33 RM W/O RECEPTS, |
| PLEASE SEE OTHER LOCATIONS ON NUMEROUS |
| UNITS MISSING RECEPTS REQUIRED PER |
| 210.52 |
| PLEASE SEE REDLINED PLANS. |
| |
| 3)NOTE: PLEASE SEE V-33, PLEASE |
| CORRELATE THE NUMBER OF COMPLETE A/C |
| SYSTEMS ON SCHEDULE, LOAD CALCS AND |
| PLANS. |
| SHOWS TWO, ONE AND ONE. |
| 215.5 |
| |
| 4)NOTE: PLEASE COMPLETE ROOM AND AREA |
| DESIGNATIONS ON PLANS. PLEASE SEE |
| REDLINED PLANS FOR UNITS INCOMPLETE AT |
| THIS TIME. SOME FROM PREVIOUS REVIEW |
| WERE DONE. |
| 215.5 |
| NEED TO VERIFY, PLEASE SEE NEXT COMMENT. |
| |
| 5)NOTE: PLEASE SEE MANY DINING RM AREAS |
| WHICH INDICATE 15A, #14 AWG FOR DINING |
| RM CIRCUIT. |
| PLEASE SEE 210.52B1, 210.11C |
| MUST BE 20A AND #12. |
| D36,28, G14, H10 ETC |
| |
| 6)NOTE: PLEASE SEE UNIT J-12, UNIT WALLS |
| NOT COMPLETE 210.52 |
| PLEASE ALSO SEE SD'S ON TWO CIRCUITS. |
| PLEASE SEE NFPA-72 WHICH REQUIRES SD'S |
| TO BE WIRED "INLINE". |
| |
| 7)NOTE: PLEASE SEE MISSING DOORS ON |
| UNITS C-21, J-12ETC. |
| |
| 8)NOTE: PLEASE SEE MANY UNITS WHERE SD'S |
| ARE MISSING THE CIRCUITING NUMBERS, NEED |
| TO VERIFY. |
| 215.5, NFPA-72 |
| |
| 9)NOTE: PLEASE SEE REDLINED PLANS FOR |
| MISSING GFI RECEPTS PER 210.52C1, SEEMS |
| TO BE ONLY A COUPLE AT THIS TIME. |
| S1(S), |
| |
| 10)NOTE: PLEASE CORRELATE THE NUMBER OF |
| SM APPL CIRCUITS ON PLANS, PANEL |
| SCHEDULE AND LOAD CALCS. A-13 |
| |
| 11)NOTE: PLEASE SEE MANY UNITS WHERE |
| MORE THEN ONE BATHROOM IS ON THE SAME |
| CIRCUIT. THIS INLCUDES , RECEPTS AND |
| LIGHTS ON SAME CIRCUIT, HOWEVER THIS |
| CIRCUIT ALSO FEEDS OTHER BATHROOMS. |
| PLEASE ALSO SEE BATH CIRCUIT ON WITH |
| LIVING RM. |
| PLEASE SEE A17, U-1, R1(S) S1(S) Q1, |
| R1,(N) ETC ETC. |
| MOST OF THESE ARE REDLINED. |
| PLEASE SEE 210.52D, AND 210.11C3, WHICH |
| PERMITS EITHER MORE THAN ONE BATH GFI ON |
| THE SAME CIRCUIT, BUT MUST NOT HAVE ANY |
| LIGHTING OR OTHER LOADS ON THAT 20A,#12 |
| GFI CIRCUIT, OR |
| BATH GFI AND LTS MAY ON TOGETHER, BUT |
| SHALL NOT FEED ANY OTHER RECEPTS,LTS OR |
| OTHER LOADS OUTSIDE THAT PARTICULAR |
| BATHRM. |
| |
| 12)NOTE: PLEASESEE MIN CLEARENCE FOR |
| CLOASET LT IN UNIT S1(N), 410.8 |
| |
| 13)NOTE: PLEASE INDICATE THE GROUNDING |
| ELECTRODE SYSTEM FOR GENERATOR. |
| 250.30 |
| |
| 14)NOTE: PLEASE VERIFY BASEMENT SUMP |
| PUMPS COMING FROM THE NON-EMERGENCY OF |
| HOUSE POWER. |
| THIS IS NOT AN ELECTRICAL NEC CODE |
| COMMENT, ONLY TO VERIFY. |
| |
| ** PLEASE SEE MANY OF THE ABOVE ITEMS |
| ARE REDLINED ON PLANS FOR AREAS OF |
| COMMENTS. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW AND IF THEREARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |