Plan Review Notes
Plan Review Notes For Permit 03031778
Permit Number 03031778
Review Stop E
Sequence Number 17
Notes
Date Text
2005-12-19 00:00:00******* UNSAT ********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES DUE TO
 INFORMATION ADDED TO PLANS.
  
  
  
 1)NOTE: PLEASE SEE MIN CLEARENCE
 REQUIREMENTS FOR MAIN ELECTRICAL ROOM.
 PLEASE ALSO SEE THAT A MIN 6' OPENING
 AND DOUBLE WORKING SPACE.
 THIS WAS NOTED AS BEING CORRECTED ,
 HOWEVER PLANS STILL SHOWN WITH OUT
 CHANGES MADE.
 110.26
  
 2)NOTE: PLEASE SEE V-33 RM W/O RECEPTS,
 PLEASE SEE OTHER LOCATIONS ON NUMEROUS
 UNITS MISSING RECEPTS REQUIRED PER
 210.52
 PLEASE SEE REDLINED PLANS.
  
 3)NOTE: PLEASE SEE V-33, PLEASE
 CORRELATE THE NUMBER OF COMPLETE A/C
 SYSTEMS ON SCHEDULE, LOAD CALCS AND
 PLANS.
 SHOWS TWO, ONE AND ONE.
 215.5
  
 4)NOTE: PLEASE COMPLETE ROOM AND AREA
 DESIGNATIONS ON PLANS. PLEASE SEE
 REDLINED PLANS FOR UNITS INCOMPLETE AT
 THIS TIME. SOME FROM PREVIOUS REVIEW
 WERE DONE.
 215.5
 NEED TO VERIFY, PLEASE SEE NEXT COMMENT.
  
 5)NOTE: PLEASE SEE MANY DINING RM AREAS
 WHICH INDICATE 15A, #14 AWG FOR DINING
 RM CIRCUIT.
 PLEASE SEE 210.52B1, 210.11C
 MUST BE 20A AND #12.
 D36,28, G14, H10 ETC
  
 6)NOTE: PLEASE SEE UNIT J-12, UNIT WALLS
 NOT COMPLETE 210.52
 PLEASE ALSO SEE SD'S ON TWO CIRCUITS.
 PLEASE SEE NFPA-72 WHICH REQUIRES SD'S
 TO BE WIRED "INLINE".
  
 7)NOTE: PLEASE SEE MISSING DOORS ON
 UNITS C-21, J-12ETC.
  
 8)NOTE: PLEASE SEE MANY UNITS WHERE SD'S
 ARE MISSING THE CIRCUITING NUMBERS, NEED
 TO VERIFY.
 215.5, NFPA-72
  
 9)NOTE: PLEASE SEE REDLINED PLANS FOR
 MISSING GFI RECEPTS PER 210.52C1, SEEMS
 TO BE ONLY A COUPLE AT THIS TIME.
 S1(S),
  
 10)NOTE: PLEASE CORRELATE THE NUMBER OF
 SM APPL CIRCUITS ON PLANS, PANEL
 SCHEDULE AND LOAD CALCS. A-13
  
 11)NOTE: PLEASE SEE MANY UNITS WHERE
 MORE THEN ONE BATHROOM IS ON THE SAME
 CIRCUIT. THIS INLCUDES , RECEPTS AND
 LIGHTS ON SAME CIRCUIT, HOWEVER THIS
 CIRCUIT ALSO FEEDS OTHER BATHROOMS.
 PLEASE ALSO SEE BATH CIRCUIT ON WITH
 LIVING RM.
 PLEASE SEE A17, U-1, R1(S) S1(S) Q1,
 R1,(N) ETC ETC.
 MOST OF THESE ARE REDLINED.
 PLEASE SEE 210.52D, AND 210.11C3, WHICH
 PERMITS EITHER MORE THAN ONE BATH GFI ON
 THE SAME CIRCUIT, BUT MUST NOT HAVE ANY
 LIGHTING OR OTHER LOADS ON THAT 20A,#12
 GFI CIRCUIT, OR
 BATH GFI AND LTS MAY ON TOGETHER, BUT
 SHALL NOT FEED ANY OTHER RECEPTS,LTS OR
 OTHER LOADS OUTSIDE THAT PARTICULAR
 BATHRM.
  
 12)NOTE: PLEASESEE MIN CLEARENCE FOR
 CLOASET LT IN UNIT S1(N), 410.8
  
 13)NOTE: PLEASE INDICATE THE GROUNDING
 ELECTRODE SYSTEM FOR GENERATOR.
 250.30
  
 14)NOTE: PLEASE VERIFY BASEMENT SUMP
 PUMPS COMING FROM THE NON-EMERGENCY OF
 HOUSE POWER.
 THIS IS NOT AN ELECTRICAL NEC CODE
 COMMENT, ONLY TO VERIFY.
  
 ** PLEASE SEE MANY OF THE ABOVE ITEMS
 ARE REDLINED ON PLANS FOR AREAS OF
 COMMENTS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND IF THEREARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  