Date |
Text |
2005-07-12 00:00:00 | ELECTRICAL REVISIONS DATED 6/6/05 |
| |
| *********** UNSAT ***************** |
| |
| 1)NOTE: PLEASE SEE MIN OPENINGS AND |
| OPENING SIZES FOR ELECTRICAL ROOMS. |
| PLEASE SEE MAIN ELECTRICAL ROOM HAD |
| CHANGED AND NO REVISION IS SHOWN FOR |
| 110.26 |
| THIS WAS GONE OVER DURING A WALK THROUGH |
| AT SAID PROJECT A FEW MONTHS BACK. |
| |
| 2)NOTE: PLEASE LABEL AND INDICATE ALL |
| MAINS ON ELECTRICAL ROOM PLANS AND ON |
| RISER. |
| PLEASE ALSO SEE METER-CENTER "A" IS |
| SHOWN AS MAIN #1?? |
| |
| 3)NOTE: PLEASE SEE NUMEROUS RECEPTS |
| REQUIRED PER 210.52 HAVE NOW BEEN |
| REMOVED FROM PLANS. |
| THESE WERE ON ORIGINAL PLANS. |
| THIS WAS GONE OVER WITH ELECTRICAL |
| CONTRACTOR, GEN CONTRACTOR, ENGINEERING |
| STAFF AT JOBSITE WHICH THE DECISION THAT |
| ALL RECEPTS ARE REQUIRED AND SHALL BE |
| INSTALLED. MANY OF THESE HAVE NOW BEEN |
| REMOVED FROM PLANS?? |
| |
| 4)NOTE: PLEASE SEE MISSING RECEPTS IN |
| MANY UNITS REQUIRED PER 210.52C1-5 |
| |
| 5)NOTE: PLEASE SHOW ALL RECEPTS REQUIRED |
| TO BE GFI/GFI PROTECTEDON PLANS. |
| PLEASE SEE KITCHEN COUNTERSPACES, BATHS |
| ETC. 210.8A6, 210.8A3 |
| |
| 6)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH PANEL SCHEDULES |
| SUBMITTED FOR UNITS. PLEASE ALSO SEE |
| OTHER NOTES; |
| |
| 7)NOTE: PLEASE CORRELATE CIRCUITS; SOME |
| SHOWN ON PLANS, HOWEVER PANEL SCHEDULE |
| INDICATES THESE CIRCUITS AS A |
| "SPACE"/"SPARE". |
| PLEASE SEE MIN SMALL APPLIANCE CIRCUITS, |
| SOME CIRCUITS SHOWN FOR FRIG IS ALSO |
| SMALL APPL ETC. |
| |
| 8)NOTE: PLEASE SEE OSME UNITS NO LONGER |
| CONTAIN ROOM DESIGNATIONS? |
| PLEASE SHOW. |
| |
| 9)NOTE: PLEASE SEE MANY OF THE |
| ELECTRICAL PANELS ARE SHOWN AS 120A?? |
| PLEASE SEE SOME ARE HAVE 125A FEEDS AND |
| SOME HAVE 200A FEEDS. BOTH OF WHICH ARE |
| ON 120A(?) PANELS. |
| |
| 10)NOTE: PLEASE SOME UNITS INDICATE TWO |
| A/C SYSTEMS , HOWEVER LOAD CALCUALTIONS |
| DO NOT SEEM TO CORRELATE WITH NUMBER OF |
| A/C UNITS AND LOADS. |
| PLEASE SHOW KW RATINGS FOR EACH AHU ON |
| ALL PANEL SCHEDULES. |
| PLEASE ADJUST ALL. |
| |
| 11)NOTE: PLEASE SEE COMPLETE SHIFT OF |
| ELECTRICAL ONC/21. |
| |
| 12)NOTE: PLEASE SEE RISER NOW SHOWS A |
| NEW PANEL "B", HOWEVER NO INFORMATION ON |
| PANEL OR PANEL SCHEDULE WAS SUBMITTED. |
| PLEASE SEE 240.21,408.16 ETC? |
| |
| 13)NOTE: PLEASE CORRELATE FEEDERS ON |
| RISER WITH FEEDERS ON HEDP FOR SC. |
| |
| 14)NOTE: PLEASE VERIFY DEDICATED |
| CIRCUITS FOR EACH OF THE ELEVATOR |
| MACHINE RMS 620.23,24 |
| |
| 15)NOTE: PLEASE VERIFY CIRCUITING OF |
| EGRESS PATHS IN HALLWAYS AND STAIRWELLS. |
| ALTERNATING CIRCUITS OR POSSIBLE BATTERY |
| BACK UP FIXTURES. |
| LS 101 7-9 |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |