Plan Review Notes
Plan Review Notes For Permit 03031778
Permit Number 03031778
Review Stop M
Sequence Number 15
Notes
Date Text
2005-07-09 00:00:00PLAN DENIED
 1) PLEASE SHOW RETURN AIR IN BEDROOMS ON
 PLAN FOR SUITES
 C,D,E,H,J,L,L-05,L-08,L-09,M-01,M-38,
 N-03,S-130,U-134 PER SECTION 601.4FBC
 (M)2001
 2) PLEASE SHOW HOW RETURN AIR IS GETTING
 BACK TO A/C FROM SUITES BY SHADING IN
 RETURN AIR PLENUMS.
 3) PLEASE HAVE MANUFACTURES INSTRUCTIONS
 ON THE LENGTH OF THE EXHAUST FOR THE
 GENERATOR FOR FINAL INSPECTION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732