Plan Review Notes For Permit 03031778 |
Permit Number |
03031778 |
|
Review Stop |
M |
Sequence Number |
15 |
|
Notes |
Date |
Text |
2005-07-09 00:00:00 | PLAN DENIED | | 1) PLEASE SHOW RETURN AIR IN BEDROOMS ON | | PLAN FOR SUITES | | C,D,E,H,J,L,L-05,L-08,L-09,M-01,M-38, | | N-03,S-130,U-134 PER SECTION 601.4FBC | | (M)2001 | | 2) PLEASE SHOW HOW RETURN AIR IS GETTING | | BACK TO A/C FROM SUITES BY SHADING IN | | RETURN AIR PLENUMS. | | 3) PLEASE HAVE MANUFACTURES INSTRUCTIONS | | ON THE LENGTH OF THE EXHAUST FOR THE | | GENERATOR FOR FINAL INSPECTION. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|