Plan Review Notes For Permit 03031778 |
Permit Number |
03031778 |
|
Review Stop |
B |
Sequence Number |
15 |
|
Notes |
Date |
Text |
2004-06-17 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 03031778 | | ADD: 610 CLEMATIS ST | | CONT: THE WHITING TURNER | | TEL: (954)868-4244 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | RE: SHOP DRAWINGS | | ACTION: DENIED | | | | 1) LOW PRESSURES ON END ZONES SEE | | ENGINEERS VALUES | | 2) MULLIONS: LIMITATIONS SEE PRODUCT | | APPROVALS 96" LIMITATION. (3.1) | | 3)1707.4.5.2 MULLIONS SHALL BE DESIGN- | | ED TO TRANSFER THE DESIGN PRESSURE LOADS | | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES | | TO THE ROUGH OPENING SUBTRATE. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|