Plan Review Notes For Permit 03031778
Permit Number 03031778
Review Stop P
Sequence Number 13
Notes
Date Text
2004-08-07 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FHA-98 DESIGN MANUAL
  
 1) THESE REVISIONS ARE SHOWING NEW REV-
 ISION NUMBERS AND THESE REVISION PLANS
 ARE NOT CHECKED FOR PREVIOUS REVISIONS
 THAT MAY OR MAY NOT HAVE BEEN OMITTED OR
 RETAINED. SECTION 104.2.1
 2) SEPARATE PERMIT REQUIRED FOR FOUNTAIN
 SHOWN ON SHEETS F1 & F2.
 3) SHT A-3-2AB MISLABELED AS A-3-2AE.
 SECTION 104.2.1
 4) SHEET AFTER A-3-4BC HAS NO SHEET NUM-
 BER AND FIXTURES HAVE BEEN DELETED. NO
 W/C OR LAV SHOWN. SECTION 104.2.1
 5) SHT A-3-4CD INDICATE DEPTH OF DRYWELL
 SECTION 104.2.1.
 6) NUMEROUS ARCHITECTURAL SHEETS HAVE
 WHITE OUT DELETING BATHROOM TYPE AND "B"
 WRITTEN IN. THIS IS NOT APPROVED. MAKE
 ALL CHANGES WITH NEW SHEETS SIGNED/SEAL-
 ED & DATED BY ARCHITECT OF RECORD. SECT-
 ION 104 104.2.1.3.
 7) SHT A-4.18 BATHROOM TYPE IS NOT SHOWN
 AS REQUIRED BY FHA DESIGN MAN. REQUIRE-
 MENT #7B
 8) SHTS P-2.4 & P-5.5 FLOOR DRAIN ADDED
 TO TRASH ROOM SHT P-2.4 IS NOT SHOWN ON
 THE BLDG. SANT. RISER DIAGRAM SHT P-5.5
 SECTION 104.2.1
 9) SHTS P-2.5, P-5.5 & P-5.6, BLDG. SANT
 RISER DIAGRAM DOES NOT REFLECT CHANGES
 IN FLOOR PLAN. ALSO RISER SR/58 IS NOT
 SHOWN ON BLDG. SANT. RISER. - BLDG.
 STORM RISER DOES NOT REFLECT CHANGES OF
 SHT P-2.5, MISSING PIPE SIZES, SQUARE
 FOOTAGE, AND LAYOUT CHANGES. SEC 104.2.1
 10) SHTS P-2.6, P-5.5 & P-5.6 RISERS DO
 NOT REFLECT CHANGES IN FLOOR PLAN. PIPE
 SIZES, SQUARE FOOTAGE, LAYOUT CHANGES.
 SECTION 104.2.1.
 11) SHTS P-4.1 THRU P-4.18 & SHTS P-5.1,
 P-5.2, P-5.3, P-5.3.1, & P-5.3.2. UNIT
 TYPES WASTE & VENT RISERS SHOW BRANCH
 LINES TO FIXTURES CONNECTING TO THE
 STACK ON THE SAME FLOOR AS THE FIXTURES.
 (WASTE STACK) - BUT RISER DIAGRAMS SHOW
 CONNECTIONS TO THE STACK ON THE FLOOR
 BELOW CREATING AN "S" TRAP NOT APPROVED
 BY SECTION SECTION 1002.3. PLEASE CLARI-
 FY. SECTION 104.2.1
 12) SHT P-5.6 SIZE PIPE FRON TRENCH
 DRAINS TO DRAINAGE STRUCTURE AND SHOW
 TOTAL SQUARE FEET. SECTION 104.2.1
 ALSO THE OTHER 3 REVISION AREAS HAVE NO
 CHANGES FROM PREVIOUS REVIEW DATED
 2-12-4.
 13) SHT P-5.5 GAS ISOMETRICS - MEASURE-
 MENTS FOR CUT SECTIONS OF PIPE WERE DE-
 LETED FROM STAMPED SET OF PLANS. THESE
 MEASUREMENTS ARE REQUIRED ON PLANS.
 SECTION 104.2.1 AND FUEL GAS CODE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]