Plan Review Notes For Permit 03031778 |
Permit Number |
03031778 |
|
Review Stop |
M |
Sequence Number |
10 |
|
Notes |
Date |
Text |
2005-01-27 00:00:00 | SUBMITTALS: | | ACCESS PANELS, CONDENSING UNIT STANDS, | | AHU STANDS, DUCTWORK MATERIALS & GEN | | SHROUD, DUCT INSULATION, BATH EXHAUST | | FANS, PIPING SUBMITTALS. | | | | PROVISO: | | CONDENSING UNIT STANDS SHALL COMPLY | | WITH THE 2001 FBC 1511.7 FOR CLEARANCE | | REQUIREMENTS BETWEEN THE ROOF SURFACE & | | THE BOTTOM OF THE SUPPORT RAIL. | | | | PVC TRAPS ARE NOT TO BE USED IN PLENUMS | | PER 2001 FBC(M)602.2.1. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561805-6719. |
|