Plan Review Notes For Permit 03031778
Permit Number 03031778
Review Stop P
Sequence Number 1
Notes
Date Text
2003-04-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA-98 DESIGN MANUAL
 CITY WPB CODE
  
 1) SHT C2.1 CONTROL STRUCTURE, SHOWS 15"
 INLET FROM RAIN WATER LEADERS, BUT NO
 INLET FROM EXFILTRATION TRENCH. PLEASE
 CLAIRFY.
 2) SHT C2.1 DRAINAGE STRUCTURE, SHOWS
 24" FROM CONTROL STRUCTURE & 18" TO THE
 TRENCH. PLEASE CLAIRFY.
 3) SHT C-2.0 EMERGNECY OVERFLOW FROM THE
 CONTROL STRUCTURE DRAINS BY SUMP VAULT.
 THE SUMP PUMP THEN DRAINS TO CONTROL
 STRUCTURE. PLEASE CLAIRFY
 4) SHT L-5.1 RAIN SENSOR REQUIRED. ALSO
 SEPARATE IRRIGATION PERMIT REQUIRED.
 5) SHT L-5.4 RPZ BACKFLOWS ARE REQUIRED
 FOR EXTERNAL IRRIGATION.
 6) SHT F1 BACKWASH SHALL DRAIN TO SANT.
 7) SHT A-4.01 DETAIL #1 CLEAR FLOOR
 SPACE REQUIRED FOR ALL FIXTURES PER FHA-
 DESIGN MANUAL PAGE 7.43 (ALL UNITS)
 8) SHT A-4.01 DETAIL #4 LAV ELEVATION,
 MAXIMUM 34" TO LAV PER FHA DESIGN MANUAL
 PAGE 7.52 (ALL UNITS)
 9) SHT A-4.01 DETAIL #5 TUB BACKING, PER
 FHA DESIGN MANUAL PAGE 6.9 (ALL UNITS)
 10) SHT A-4.01 DETAIL #6, SHOW SIDE RE-
 INFORCEMENT PER FHA DESIGN MANUAL PAGE
 6.5 (ALL UNITS)
 11) SHT A-4.01 DETAILS REFER TO SHT A-XX
 BUT SHT A-XX NOT FOUND. PLEASE CLAIRFY.
 12) SHT A-10.02 DETAIL #2 SCUPPER, SHOW
 WIDTH & HEIGHT. SCUPPER SHALL BE INSTALL
 ED PER SECTION 1503.4.2. SHOW HEIGHT
 TO FLOW LINE OFF ROOF
 13) PLEASE IDENTIFY ALL WORK/LIVE LOFTS.
 TOILET ROOMS SHALL COMPLY WITH 11-4.22.
 ALL UNITS SHALL HAVE A DRINKING FOUNTAIN
 PER TABLE 403.1. (ALSO SEE 410.1)
 14) SHT P-1.2 GREASE TRAPS TO BE SIZED
 BY RODNEY COMPO, ENVIRONMENTAL COMPLIAN-
 CE. UTILITY ORD #2938-96. PLEASE CONTACT
 @ (561) 837-4074.
 15) SHT P-1.3 15" STORM @ 53,900 SQ. FT.
 SHALL BE RUN AT A MINIMUM OF 1/4" PER FT
 PLEASE INDICATE ON PLANS.
 16) SHTS P2.1/P2.2 SEPARAGE GAS PERMIT
 REQUIRED. THE FOLLOWING INFORMATION IS
 REQUIRED PRIOR TO PERMIT ISSUANCE.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34). (REQUIRED AT BUILDOUT)
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304. (REQD AT BUILDOUT)
 F. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506. (REQD. AT BUILD0UT)
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2. (IF LP)
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H). (IF LP)
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. (REQD AT
 BUILDOUT)
 PLEASE PROVIDE THE TABLE THAT WAS USED
 TO SIZE PIPE FOR 8500 CFH @ 500 FEET.
 PLEASE INDICATE WHO PROVIDES TABLE REF-
 ERENCED. (TABLE NEEDS TO BE APPROVED)
 ---SUGGESTION--- A 2LB SYSTEM OR A 5LB
 SYSTEM WILL ENABLE THE SYSTEM TO USE A
 SMALLER SIZE SUPPLY PIPE--------
 17) SHT P-2.2 6" RPZ BACKFLOW PREVENTER
 SHALL BE LOCATED A MAXIMUM OF 4 FT ABOVE
 THE FLOOR FOR SERVICING AND TESTING.
 18) SHT P-2.4 CONDENSATE IS NOT ALLOWED
 TO DRAIN INTO SANITARY SYSTEM. CITY CODE
 90-125(B)(5).
 19) SHTS P-2.25/.26/.26/.28 & A-2.11
 SUBMIT CALCULATIONS FOR PRIMARY AND SEC-
 ONDARY ROOF DRAINS. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS. SHOW
 ALL AREA OF ROOFS THAT DRAIN DOWN ON THE
 ROOF FROM ABOVE. SHOW LOCATION OF ALL
 SECONDARY OVERFLOW DRAINS OR SCUPPERS.
 SECTIONS 1106 & 1107 AND ALL SUBSECTIONS
 20) SHT P-2.8 CONDENSATE SHALL RUN SEP-
 ARATELY OUT OF BLDG OR TO CATCH BASINS.
 PLEASE PROVIDE SEPARATE CONDENSATE IS0-
 METRIC RISER. SHOW BLDG COND. DRAIN AND
 ALL RISERS AND INDICATE LOAD AS IT ACCU-
 MULATES.
 21) SHT P-4.1 SANITARY RISER DOES NOT
 REFLECT THE FLOOR PLAN. KITCHEN SINK
 SHALL NOT DRAIN INTO THE WET VENT OF THE
 BATHROOM GROUP. 909.1 - THE KITCHEN SINK
 SHALL DRAIN DOWNSTREAM OF THE BATHROOM
 GROUP. - TUB NEEDS TRAP.
 22) SHT P-4.2 SANT. RISER DOES NOT RE-
 FLECT FLOOR PLAN. H/10 & J/12
 23) SHT P-4.4 SANT. RISER DOES NOT RE-
 FLECT FLOOR PLAN. C-21
 24) SHT P-4.6 SANT. RISER DOES NOT RE-
 FLECT FLOOR PLAN. P/36
 25) SHT P-4.7 SANT. RISER DOES NOT RE-
 FLECT FLOOR PLAN. N/03
 26) SHT P-4.7 SANT. RISER DOES NOT RE-
 FLECT FLOOR PLAN. F/28 - KITCHEN SINK
 SHALL NOT DRAIN THROUGH WET VENTED BATH-
 ROOM GROUP 909.1. KIT. SINK SHALL DRAIN
 DOWNSTREAM OF BATHROOM GROUP.
 27) SHT P-4.9 SANT RISER DOES NOT RE-
 FLECT FLOOR PLAN.WASH MACHINE & KIT.
 SINK SHALL DRAIN DOWNSTREAM OF BATHROOM
 GROUP. 909.1D/28 - D/36
 28) SHT P-4.9 SANT. RISER DOES NOT RE-
 FLECT FLOOR PLAN A13. NO SANT LINE TO
 WATER CLOSET ON FLOOR PLAN.
 29) SHT P-4.12 NO SANITARY LINE TO WATER
 CLOSET ON LOWER FLOOR PLAN.
 30) SHT P-4.16 WATER RISER DOES NOT RE-
 FLECT FLOOR PLAN.
 31) SHTS FOR ALL UNITS, WATER HAMMER
 ARRESTOR REQUIRED AT ICE MAKER LINE IN
 ALL UNITS. PLEASE REVISE.
 32) SHT P-4.17 SANT. RISER DOES NOT RE-
 FLECT THE FLOOR PLAN.
 33) SHT P-4.18 SANT. RISER 909.1 KITCHEN
 SINK SHALL NOT DRAIN INTO WET VENT FOR
 BATHROOM GROUP.
 34) SHT P-5.1 RISER SR4 N/203/(19) DFU
 NOT ADDED TO TOTAL FOR RISER.
 35) SHT P-5.3 RISER SR15 SHOWS 123 DFU,
 ACTUALLY 133 DFU.
 36) SHT P-5.4 DETAIL #5 PLEASE SHOW SIZE
 OF SUPPLY TO URNAL.
 37) SHT P-5.4 DETAIL #1 RPZ BACKFLOW TO
 BE MAX. 4' ABOVE FLOOR FOR SERVICING AND
 TESTING.
 38) SHT P-5.4 DETAIL #1 RPZ BACKFLOW RE-
 QUIRED FOR FOUNTAIN WATER SERVICE.
 39) SHT P-5.5 RISERS #'S 39, 40, 41, 42,
 43, 44, & 45 NOT FOUND. PLEASE SUBMIT
 INFORMATION ON THESE RISERS.
 40) SHT P-5.5 INDICATES DETAIL FOR
 GREASE TRAP ON SHT P-7.1, BUT NO DETAIL
 WAS FOUND. SEE ATTACHED SHEET FOR APP-
 ROVED GREASE TRAP DETAIL. SUBMIT ON PLAN
 NOTE 2-WAY CLEAN OUTS REQD. ENTERING &
 EXITING EACH GREASE TRAP.
 41) SHT P-5.5 CORRECT ALL AREAS WHERE
 RED LINED. SHOW ALL PIPE SIZES AND DFU
 NOT SHOWN.
 42) SHT P-5.5 DFU'S FROM GREASE TRAP NOT
 ADDED TO SYSTEM. RECALCULATE DFU'S. SHOW
 SLOPE OF PIPE ON RISER DIAGRAM.
 43) SHT P-5.6 CONDENSATE RISER SHALL NOT
 TERMINATE IN A/C ROOM IF USED AS A PLEN-
 UM.
 44) SHT P-5.6 6" @ 6150 SQ FT NOT APP-
 ROVED. MINIMUM OF 1/4" PER FT OR LARGER
 SIZE PIPE. PLEASE SHOW SLOPE OR INCREASE
 PIPE SIZE.
 45) SHT P-5.6 5" REQUIRED @ 1950 SQ FT.
 46) SHT P-5.6 SHOW AREA DRAINED AT 4"
 TRENCH DRAINS ON RISER DIAGRAM.
 47) SHT P-5.6 SHOW PIPE SIZE FOR ENTRY
 TRENCH DRAINS ON RISER.
 48) SHT P-5.6 STORM ISOMETRIC, 15" PIPE
 DRAINING 61,089 SQ FT SHALL BE MINIMUM
 OF 1/4" PER FOOT. PLEASE INDICATE ON
 RISER.
 49) SHT P-5.6 PLEASE INDICATE MATERIAL
 FOR RELIEF VALVE & EMERGENGY PAN DRAIN
 RISERS. (PVC NOT APPROVED)
 50) SHT P-6.1 CONDENSATE SHALL RUN SEP-
 ARETELY. (SEE COMMENT #20)
 51) SHT P-6.1 PLUMBING FIXTURE SCHEDULE,
 HANDICAP WATER CLOSET TO BE 17" TO 19"
 TO SEAT. 11-4.16.3
 52) SHT P-6.1 PLUMBING FIXTURE SCHEDULE,
 6" ROOF DRAIN, VENT NOT REQUIRED. TRAP
 NOT APPROVED.
 SHT P7.1 AIR CHAMBER DETAIL, AIR CHAMB-
 ERS ARE NOT APPROVED. PLEASE DELETE DE-
 TAIL.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692