Plan Review Notes
Plan Review Notes For Permit 03031778
Permit Number 03031778
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-04-03 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 2) SUITABLE ROADS ARE TO BE PROVIDED FOR
 FIRE AND PARAMEDICAL EQUIPMENT DURING
 CONSTRUCTION.
  
 3) ALL CONSTRUCTION RELATED WORK SHALL
 COMPLY WITH NFPA 241.
  
 4) BUILDING IS LOCATED IN THE CITY
 FIRE LIMITS. CERTAIN RESTRICTIONS APPLY.
 PLEASE SEE APPENDIX F, LOCAL AMENDMENTS
 TO THE FLORIDA BUILDING CODE.
  
 5) ELECTRONIC SWITCHES ARE REQUIRED ON
 THE FIRE LINE OS & Y VALVES.
  
 6) ALL RAMPS AND STAIRS SHALL BE
 EQUIPPED WITH HANDRAILS.
  
 7) PLEASE REVIEW NFPA 1, WITH REGARDS TO
 PROPANE GRILLS BEING LOCATED ABOVE
 THE FIRST FLOOR IN A MULTI-FAMILY
 DWELLING.
  
 8) SEVERAL DRAWINGS DEPICT EXTERIOR
 DOORS ON THE DATURA STREET SIDE
 OPENING OVER STAIRS.
  
 9) POLYSTYRENE MOLDING NOTED ON TYPICAL
 BALCONY DETAILS. PLEASE SEE APPENDIX F,
 LOCAL AMENDMENTS TO THE FLORIDA BUILDING
 CODE.
  
 10) A TWO HOUR FIRE RATING IS REQUIRED
 BETWEEN THE PARKING GARAGE AND OTHER
 PORTIONS OF THE BUILDING. OPENING
 PROTECTIVES SHALL BE AT LEAST 1 1/2
 HOURS.
  
 11) PLEASE INDICATE WHICH ELEVATORS
 COMPLY WITH THE STRETCHER REQUIREMENTS
 OF THE FBC.
  
 12) VERIFY DOUBLE DOOR SWING IN
 CORRIDOR 119.
  
 13) THE FIRE CONTROL ROOM SHOULD HAVE
 A DOOR FROM THE RESIDENTIAL LOBBY SIDE.
  
 14) IT APPEARS SOME NOTES ON ROOF PLAN
 ARE ILLEGIBLE.
  
 15) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR HANDRAILS.
  
 16) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 17) THE SIGNAGE SHOULD BE REVISED TO
 READ "ELECTRICAL ROOM, NO STORAGE BY
 ORDER OF THE FIRE MARSHAL".
  
 18) ALL ELEVATORS TO COMPLY WITH 61C-5.
  
 19) PLEASE ADVISE WHAT THE FIRE ALARM
 ACTIVATION MESSAGE WILL SAY.
  
 20) PLEASE INDICATE WHERE THE APARTMENTS
 THAT HAVE SPEAKER STROBES IN THEM.
  
 21) PLEASE ADD NOTE-SMOKE DETECTORS ARE
 TO BE INSTALLED A MINIMUM OF THREE FEET
 FROM AC DIFFUSERS.
  
 22) ALL SHAFTWAYS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST BE
 MARKED SHAFTWAY IN RED LETTERS.
  
 23) SOME MORE EXIT SIGNS APPEAR TO
 BE NEEDED ON SOME OF THE ELECTRICAL
 PAGES.
  
 24) SOME EXIT SIGNS APPEAR TO OPPOSE
 ONE ANOTHER.
  
 25) FABRIC AWNINGS ARE NOTED. THESE
 MUST BE FIRE RETARDANT.
  
 26) SOUTH COURTYARD ELEVATION APPEARS
 TO EXTEND OVER PROPERTY LINE.
  
 27) PLEASE INDICATE WHICH STAIRTOWERS
 LEAD DIRECTLY TO THE EXTERIOR. AT LEAST
 50 PERCENT OF THE EXIT STAIRS MUST
 LEAD DIRECTLY TO THE EXTERIOR.
  
 28) ACCORDING TO THE GROUND FLOOR,
 RESTAURANTS ARE PROPOSED. HOW AND
 WHERE WILL THE KITCHEN HOOD SYSTEMS
 EXHAUST.
  
 29) PLEASE EXPLAIN EXITING RATIONALE
 FROM THE GARAGE.
  
 30) PLEASE PROVIDE INFORMATION ON TYPE
 OF CONSTRUCTION THE BUILDING WILL BE.
  
 31) STAIR # 6 APPEARS TO EXIT INTO
 RETAIL # 1. IS THIS PROPER.
  
 32) STAIR # 8 APPEARS TO TERMINATE
 INTO STORAGE # 2.
  
 33) ANY EXIT CORRIDORS ADJACENT TO
 STAIRTOWERS SHOULD HAVE THE SAME FIRE
 RATING AS THE STAIR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497