Date |
Text |
2003-04-03 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| TO, DURING AND AFTER CONSTRUCTION. |
| |
| 2) SUITABLE ROADS ARE TO BE PROVIDED FOR |
| FIRE AND PARAMEDICAL EQUIPMENT DURING |
| CONSTRUCTION. |
| |
| 3) ALL CONSTRUCTION RELATED WORK SHALL |
| COMPLY WITH NFPA 241. |
| |
| 4) BUILDING IS LOCATED IN THE CITY |
| FIRE LIMITS. CERTAIN RESTRICTIONS APPLY. |
| PLEASE SEE APPENDIX F, LOCAL AMENDMENTS |
| TO THE FLORIDA BUILDING CODE. |
| |
| 5) ELECTRONIC SWITCHES ARE REQUIRED ON |
| THE FIRE LINE OS & Y VALVES. |
| |
| 6) ALL RAMPS AND STAIRS SHALL BE |
| EQUIPPED WITH HANDRAILS. |
| |
| 7) PLEASE REVIEW NFPA 1, WITH REGARDS TO |
| PROPANE GRILLS BEING LOCATED ABOVE |
| THE FIRST FLOOR IN A MULTI-FAMILY |
| DWELLING. |
| |
| 8) SEVERAL DRAWINGS DEPICT EXTERIOR |
| DOORS ON THE DATURA STREET SIDE |
| OPENING OVER STAIRS. |
| |
| 9) POLYSTYRENE MOLDING NOTED ON TYPICAL |
| BALCONY DETAILS. PLEASE SEE APPENDIX F, |
| LOCAL AMENDMENTS TO THE FLORIDA BUILDING |
| CODE. |
| |
| 10) A TWO HOUR FIRE RATING IS REQUIRED |
| BETWEEN THE PARKING GARAGE AND OTHER |
| PORTIONS OF THE BUILDING. OPENING |
| PROTECTIVES SHALL BE AT LEAST 1 1/2 |
| HOURS. |
| |
| 11) PLEASE INDICATE WHICH ELEVATORS |
| COMPLY WITH THE STRETCHER REQUIREMENTS |
| OF THE FBC. |
| |
| 12) VERIFY DOUBLE DOOR SWING IN |
| CORRIDOR 119. |
| |
| 13) THE FIRE CONTROL ROOM SHOULD HAVE |
| A DOOR FROM THE RESIDENTIAL LOBBY SIDE. |
| |
| 14) IT APPEARS SOME NOTES ON ROOF PLAN |
| ARE ILLEGIBLE. |
| |
| 15) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| REQUIREMENTS FOR HANDRAILS. |
| |
| 16) PLEASE INDICATE INTERIOR FINISH |
| CLASSIFICATION FOR WALLS AND CEILINGS. |
| |
| 17) THE SIGNAGE SHOULD BE REVISED TO |
| READ "ELECTRICAL ROOM, NO STORAGE BY |
| ORDER OF THE FIRE MARSHAL". |
| |
| 18) ALL ELEVATORS TO COMPLY WITH 61C-5. |
| |
| 19) PLEASE ADVISE WHAT THE FIRE ALARM |
| ACTIVATION MESSAGE WILL SAY. |
| |
| 20) PLEASE INDICATE WHERE THE APARTMENTS |
| THAT HAVE SPEAKER STROBES IN THEM. |
| |
| 21) PLEASE ADD NOTE-SMOKE DETECTORS ARE |
| TO BE INSTALLED A MINIMUM OF THREE FEET |
| FROM AC DIFFUSERS. |
| |
| 22) ALL SHAFTWAYS THAT ARE LARGE ENOUGH |
| FOR PERSONS TO FALL INTO MUST BE |
| MARKED SHAFTWAY IN RED LETTERS. |
| |
| 23) SOME MORE EXIT SIGNS APPEAR TO |
| BE NEEDED ON SOME OF THE ELECTRICAL |
| PAGES. |
| |
| 24) SOME EXIT SIGNS APPEAR TO OPPOSE |
| ONE ANOTHER. |
| |
| 25) FABRIC AWNINGS ARE NOTED. THESE |
| MUST BE FIRE RETARDANT. |
| |
| 26) SOUTH COURTYARD ELEVATION APPEARS |
| TO EXTEND OVER PROPERTY LINE. |
| |
| 27) PLEASE INDICATE WHICH STAIRTOWERS |
| LEAD DIRECTLY TO THE EXTERIOR. AT LEAST |
| 50 PERCENT OF THE EXIT STAIRS MUST |
| LEAD DIRECTLY TO THE EXTERIOR. |
| |
| 28) ACCORDING TO THE GROUND FLOOR, |
| RESTAURANTS ARE PROPOSED. HOW AND |
| WHERE WILL THE KITCHEN HOOD SYSTEMS |
| EXHAUST. |
| |
| 29) PLEASE EXPLAIN EXITING RATIONALE |
| FROM THE GARAGE. |
| |
| 30) PLEASE PROVIDE INFORMATION ON TYPE |
| OF CONSTRUCTION THE BUILDING WILL BE. |
| |
| 31) STAIR # 6 APPEARS TO EXIT INTO |
| RETAIL # 1. IS THIS PROPER. |
| |
| 32) STAIR # 8 APPEARS TO TERMINATE |
| INTO STORAGE # 2. |
| |
| 33) ANY EXIT CORRIDORS ADJACENT TO |
| STAIRTOWERS SHOULD HAVE THE SAME FIRE |
| RATING AS THE STAIR. |
| |