2003-04-15 00:00:00 | PLEASE SEE COMMENTS STARTED 4/14 AND |
| COMPLETED 4/15/03 |
2003-04-14 00:00:00 | ************* UNSAT ***************** |
| |
| 1)NOTE: PLEASE PROVIDE NOTE ON ELECTRIC- |
| -AL RISER DIAGRAM: ELECTRICAL CONTRACTOR |
| TO PROVIDE SPARE CONDUITS TO ANY |
| PANELS AND/OR EQUIPMENT THAT MAY NEED TO |
| BE FED FROM TEMPORARY POWER BEFORE |
| MAIN SERVICE IS RELEASED ON BLDG. |
| PLEASE ALSO NOTE: TEMPORARY SERVICE MUST |
| BE OF ADEQUATE SIZE. |
| |
| 2)NOTE: PLEASE SEE DOUBLE PRINT ON TITLE |
| BLOCK FOR ENGINEER OF RECORD. PLEASE |
| REPRINT FOR CLARITY. FAC 61G15-23.002 |
| |
| 3)NOTE: PLEASE SUBMIT AND SHOW AIC |
| RATINGS FOR ALL NEW EQUIPMENT BEING |
| INSTALLED. MAINS/PANELS/BREAKERS ARE |
| ALL TO BE RATED FOR THE AVAILABLE FAULT |
| CURRENT. PER 110-9 IT IS NOTED, ELECTRI- |
| -CAL CONTRACTOR TO PROVIDE SIGNED AND |
| SEALED SHOP DRAWINGS FOR THIS. |
| PLEASE NOTE, THIS MUST BE SUBMITTED WITH |
| PLANS FROM THE ENGINEER OF RECORD. |
| |
| 4)NOTE: PLEASE SEE E3.1. GENERATOE SHOWN |
| AS 600W? PLEASE CORRELATE W/ RISER |
| DIAGRAM. |
| |
| 5)NOTE: PLEASE SHOW(MAP) LOCATION AROUND |
| FUEL FILL AREA REMOTE FROM GENERATOR |
| PER NEC 500. |
| |
| 6)NOTE: PLEASE SHOW/LIST GROUNDING FOR |
| ALL TRANSFORMERS PER 250-30 |
| |
| 7)NOTE: PLEASE SEE E3.1, SHOWS 2-4" |
| CONDUITS FOR 400A SE RATED SWITCH, |
| PLEASE SEE RISER, SHOWS ONLY ONE CONDUIT |
| FROM FPL.? PLEASE CORRELATE. |
| |
| 8)NOTE: PLEASESUBMIT/SHOW MORE ON |
| SERVICE FOR FUTURE TENANT SPACES. |
| SERVICE, MAINS ETC? |
| PLEASE CLARFIY IF 400A SE RATED MAIN IS |
| FOR FUTURE TENANTS? |
| |
| 9)NOTE: PLEASE SEE CODE REFERENCED FOR |
| GROUNDING ELECTRODE IS FROM THE 96 NEC. |
| (250-81) PLEASE NOTE:250-66 99NEC |
| |
| 10)NOTE: PLEASE NOTE, AS PER PLANS, |
| MAINS IN BLDG ARE NOT GROUPED. PLANS |
| ARE SHOWING 13 MAINS IN BLDG WHICH DOES |
| NOT INCLUDE FIRE PUMP.230-2/230-70, |
| 230-72, 225-38 ETC. |
| MAINS ARE TO BE LOCATED AT THE NEAREST |
| POINT OF ENTRANCE TO A BLDG.E |
| PLEASE ALSO NOTE, FIRE AND LIFE SAFTEY |
| ISSUES COME INTO PLAY W/ THE MAJOR |
| TRAVEL DISTANCES AND NUMEROUS LOCATIONS |
| TO TURN POWER OFF IN BLDG. |
| PLEASE ALSO NOTE, SERVICES CROSSING |
| EACH OTHER, AND/OR HOUSE (277/480V) |
| POWER. |
| |
| 11)NOTE: PLEASE CLARIFY HDP, RISER SHOWS |
| PLEASE SEE 240-3B FOR SIZING OF SEC`S |
| FROM FPL. SHOWS ONLY, 4-500MCM`S IN |
| 4-SETS.310-16/110-14 |
| |
| 12)NOTE: PLEASE INDICATE AND SHOW REQ`D |
| GFI PROTECTION FOR HDP. 230-95/215-10 ET |
| |
| 13)NOTE: PLEASE CLARIFY/INDICATE METER |
| TYPES FOR HOUSE AND FIRE PUMP? OF THE |
| CT TYPE? |
| |
| 14)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| PROETECTED CIRCUITS ON EACH PANEL SCHED- |
| -ULE PER 210-12 |
| |
| 15)NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| ED PER 210-8A-6THIS WOULD INCLUDE ANY |
| ISLAND RECEPTS. |
| |
| 16)NOTE: PLEASE SEE PLANS AND UNITS, |
| MISSING RECEPTS PER 210-52. 2',6',12' |
| RULE. |
| |
| 17)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRLEATE W/ SUBMITTED PANEL |
| SCHEDULES. |
| |
| 18)NOTE: PLEASE SEE V/33, APPEARS TO |
| HAVE 2-WATER HEATERS AND 2-A/C UNITS? |
| PLEASE CLARIFY. |
| |
| 19)NOTE: PLEASE SEE MISSING COUNTERSPACE |
| RECEPTS PER 210-52-1 |
| |
| 20)NOTE: PLEASE CLARIFY GFI PROTECTION |
| FOR WHIRLPOOL TUBS 680-70 |
| |
| 21)NOTE: PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S) PER 210-52D/210-11C-3 |
| MUST BE 20A/ #12AWG. |
| |
| 22)NOTE: PLEASE CLARIFY SQ FT SHOWN FOR |
| UNIT D36, "L"UNITS? "L" UNITS ARE SHOWN |
| MUCH LARGER ON SMAE SCLE THAN D36 , YET |
| SQFT ON LOAD CALCS AND PANEL SCHEDULE |
| DO NOT SEEM TO REFLECT THIS. |
| PLEASE VERIFY OTHE UNITS ALSO. |
| |
| 23)NOTE: PLEASE VERIFY SQ FT ON OTHER |
| UNITS ALSO. SOME OTHERS DO NOT SEEM TO |
| SCALE OUT. |
| |
| 24)NOTE: PLEASE SEE OTHER UNITS FOR |
| MISSING RECEPTS PER 210-52/210-52C-1 |
| |
| 25)NOTE: PLEASE SEE MISSING RECEPT W/IN |
| 3' OF LAV IN "L" UNITS. 210-52D |
| |
| 26)NOTE: PLEASE NOTE: ALL SD`S TO BE A |
| MIN OF 3' FROM BATHS AND KITCHENS. |
| NFPA-72 8-1.4.2 |
| |
| 27)NOTE: PLEASE SEE MISSING RECEPT W/IN |
| 3' OF LAV`S IN OTHER UNITS ALSO 210-52D |
| |
| 28)NOTE: PLEASE CLARIFY EGRESS LIGHTING |
| CONTROL IN MULTI-LEVEL UNIT A/13. |
| FOR STAIRWAY ,210-70 |
| PLEASE ALSO SEE A17 |
| |
| 29)NOTE:PLEASE CLARIFY MEANS OF EGRESS |
| LIGHTING/CONTROL OR AUTOMATIC MEANS |
| FOR GRADE LEVEL UNITS W/ ACCESS TO |
| STREET. |
| |
| 30)NOTE: PLEASE SHOW LIGHTING AND RECEPT |
| -S SHOWN 2.9/2.10 ETC ON UNITS,, G-14, |
| K-16,K18,K-20, L-22 ETC.OR NOTE |
| LOCATION FO LIGHTING AND RECEPT. |
| |
| 31)NOTE: PLEASE SEEMISSING RECEPTS |
| FOR 12" OF COUNTERSPACE,210-52C1 |
| |
| 32)NOTE: PLEASE SEE WHIRLPOOL TUB SHOWN |
| IN MIDDLE OF MASTER BEDROOM FLOOR IN |
| UNIT C/17, E 4.8 |
| |
| 33)NOTE: AS PER 210-52, RAIL AREA IN |
| BEDROOMS ON MULTI-LEVEL UNITS ARE |
| CONSIDERED WALL SPACE. RECEPT RE`D. |
| |
| 34)NOTE: PLEASE CLARFIY MEANS OF EGREES |
| CONTROL COMING INTO S1(N) FROM HALL INTO |
| LIVING ROOM.210-70 |
| |
| 35)NOTE: PLEASE CLARIFY METER CENTER "A" |
| SHOWS 150A MAINS AND ONLY 7 V/33 UNITS? |
| |
| 36)NOTE: PLEASE SHOW SPECS ON PANEL |
| SCHEDULES. FEEDERS ARE NOTED AS 125A AND |
| 150ABUT PANELS DO NOT INDICATE SIZE |
| ETC. |
| |
| 37)NOTE: PLEASE NOTE, POOL WILL BE REQ`D |
| TO BE UNDER SEPARATE PERMIT FOR STRUC/ |
| ELEC/PLUMB. PLEASE ALSO NOTE, A SEPARATE |
| ELECTRCIAL WIRING DIAGRAM FOR PUMPS/ |
| HEATERS AND EQUIPMENT WILL BE REQ`D TO |
| BE SUBMITTED W/ POOL PERMIT. |
| |
| 38)NOTE:PLEASE NOTE, LIGHTNING PROTECT- |
| -ION WILL BE REQ` TO BE UNDER SEPARATE |
| PERMIT. |
| |
| 39)NOTE: PLEASE NOTE; COLOR CODING OF |
| FEEDERS TO BE PER LOCAL AMENDMENTS. 215 |
| 277/480V |
| BROWN/ PURPLE /YELLOW |
| 120/208V |
| BLACK/RED/BLUE |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. PLEASE DO NOT HESITATE TO CALL |
| AND EITHER SET UP A MEETING TO GO OVER |
| PLANS/COMMENTS ON PHONE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |
| 561-805-6717 |
| [email protected] |
| |
| PLEASE SEE FIRE REVIEW COMMENTS THAT |
| WILL HAVE AN AFFECT ON ELECTRICAL PLANS |
| DUE TO THE REQUEST OF MORE EXIT/EM LTS. |