Plan Review Notes For Permit 03031778
Permit Number 03031778
Review Stop E
Sequence Number 1
Notes
Date Text
2003-04-15 00:00:00PLEASE SEE COMMENTS STARTED 4/14 AND
 COMPLETED 4/15/03
2003-04-14 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE PROVIDE NOTE ON ELECTRIC-
 -AL RISER DIAGRAM: ELECTRICAL CONTRACTOR
 TO PROVIDE SPARE CONDUITS TO ANY
 PANELS AND/OR EQUIPMENT THAT MAY NEED TO
 BE FED FROM TEMPORARY POWER BEFORE
 MAIN SERVICE IS RELEASED ON BLDG.
 PLEASE ALSO NOTE: TEMPORARY SERVICE MUST
 BE OF ADEQUATE SIZE.
  
 2)NOTE: PLEASE SEE DOUBLE PRINT ON TITLE
 BLOCK FOR ENGINEER OF RECORD. PLEASE
 REPRINT FOR CLARITY. FAC 61G15-23.002
  
 3)NOTE: PLEASE SUBMIT AND SHOW AIC
 RATINGS FOR ALL NEW EQUIPMENT BEING
 INSTALLED. MAINS/PANELS/BREAKERS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT. PER 110-9 IT IS NOTED, ELECTRI-
 -CAL CONTRACTOR TO PROVIDE SIGNED AND
 SEALED SHOP DRAWINGS FOR THIS.
 PLEASE NOTE, THIS MUST BE SUBMITTED WITH
 PLANS FROM THE ENGINEER OF RECORD.
  
 4)NOTE: PLEASE SEE E3.1. GENERATOE SHOWN
 AS 600W? PLEASE CORRELATE W/ RISER
 DIAGRAM.
  
 5)NOTE: PLEASE SHOW(MAP) LOCATION AROUND
 FUEL FILL AREA REMOTE FROM GENERATOR
 PER NEC 500.
  
 6)NOTE: PLEASE SHOW/LIST GROUNDING FOR
 ALL TRANSFORMERS PER 250-30
  
 7)NOTE: PLEASE SEE E3.1, SHOWS 2-4"
 CONDUITS FOR 400A SE RATED SWITCH,
 PLEASE SEE RISER, SHOWS ONLY ONE CONDUIT
 FROM FPL.? PLEASE CORRELATE.
  
 8)NOTE: PLEASESUBMIT/SHOW MORE ON
 SERVICE FOR FUTURE TENANT SPACES.
 SERVICE, MAINS ETC?
 PLEASE CLARFIY IF 400A SE RATED MAIN IS
 FOR FUTURE TENANTS?
  
 9)NOTE: PLEASE SEE CODE REFERENCED FOR
 GROUNDING ELECTRODE IS FROM THE 96 NEC.
 (250-81) PLEASE NOTE:250-66 99NEC
  
 10)NOTE: PLEASE NOTE, AS PER PLANS,
 MAINS IN BLDG ARE NOT GROUPED. PLANS
 ARE SHOWING 13 MAINS IN BLDG WHICH DOES
 NOT INCLUDE FIRE PUMP.230-2/230-70,
 230-72, 225-38 ETC.
 MAINS ARE TO BE LOCATED AT THE NEAREST
 POINT OF ENTRANCE TO A BLDG.E
 PLEASE ALSO NOTE, FIRE AND LIFE SAFTEY
 ISSUES COME INTO PLAY W/ THE MAJOR
 TRAVEL DISTANCES AND NUMEROUS LOCATIONS
 TO TURN POWER OFF IN BLDG.
 PLEASE ALSO NOTE, SERVICES CROSSING
 EACH OTHER, AND/OR HOUSE (277/480V)
 POWER.
  
 11)NOTE: PLEASE CLARIFY HDP, RISER SHOWS
 PLEASE SEE 240-3B FOR SIZING OF SEC`S
 FROM FPL. SHOWS ONLY, 4-500MCM`S IN
 4-SETS.310-16/110-14
  
 12)NOTE: PLEASE INDICATE AND SHOW REQ`D
 GFI PROTECTION FOR HDP. 230-95/215-10 ET
  
 13)NOTE: PLEASE CLARIFY/INDICATE METER
 TYPES FOR HOUSE AND FIRE PUMP? OF THE
 CT TYPE?
  
 14)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROETECTED CIRCUITS ON EACH PANEL SCHED-
 -ULE PER 210-12
  
 15)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 ED PER 210-8A-6THIS WOULD INCLUDE ANY
 ISLAND RECEPTS.
  
 16)NOTE: PLEASE SEE PLANS AND UNITS,
 MISSING RECEPTS PER 210-52. 2',6',12'
 RULE.
  
 17)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRLEATE W/ SUBMITTED PANEL
 SCHEDULES.
  
 18)NOTE: PLEASE SEE V/33, APPEARS TO
 HAVE 2-WATER HEATERS AND 2-A/C UNITS?
 PLEASE CLARIFY.
  
 19)NOTE: PLEASE SEE MISSING COUNTERSPACE
 RECEPTS PER 210-52-1
  
 20)NOTE: PLEASE CLARIFY GFI PROTECTION
 FOR WHIRLPOOL TUBS 680-70
  
 21)NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-52D/210-11C-3
 MUST BE 20A/ #12AWG.
  
 22)NOTE: PLEASE CLARIFY SQ FT SHOWN FOR
 UNIT D36, "L"UNITS? "L" UNITS ARE SHOWN
 MUCH LARGER ON SMAE SCLE THAN D36 , YET
 SQFT ON LOAD CALCS AND PANEL SCHEDULE
 DO NOT SEEM TO REFLECT THIS.
 PLEASE VERIFY OTHE UNITS ALSO.
  
 23)NOTE: PLEASE VERIFY SQ FT ON OTHER
 UNITS ALSO. SOME OTHERS DO NOT SEEM TO
 SCALE OUT.
  
 24)NOTE: PLEASE SEE OTHER UNITS FOR
 MISSING RECEPTS PER 210-52/210-52C-1
  
 25)NOTE: PLEASE SEE MISSING RECEPT W/IN
 3' OF LAV IN "L" UNITS. 210-52D
  
 26)NOTE: PLEASE NOTE: ALL SD`S TO BE A
 MIN OF 3' FROM BATHS AND KITCHENS.
 NFPA-72 8-1.4.2
  
 27)NOTE: PLEASE SEE MISSING RECEPT W/IN
 3' OF LAV`S IN OTHER UNITS ALSO 210-52D
  
 28)NOTE: PLEASE CLARIFY EGRESS LIGHTING
 CONTROL IN MULTI-LEVEL UNIT A/13.
 FOR STAIRWAY ,210-70
 PLEASE ALSO SEE A17
  
 29)NOTE:PLEASE CLARIFY MEANS OF EGRESS
 LIGHTING/CONTROL OR AUTOMATIC MEANS
 FOR GRADE LEVEL UNITS W/ ACCESS TO
 STREET.
  
 30)NOTE: PLEASE SHOW LIGHTING AND RECEPT
 -S SHOWN 2.9/2.10 ETC ON UNITS,, G-14,
 K-16,K18,K-20, L-22 ETC.OR NOTE
 LOCATION FO LIGHTING AND RECEPT.
  
 31)NOTE: PLEASE SEEMISSING RECEPTS
 FOR 12" OF COUNTERSPACE,210-52C1
  
 32)NOTE: PLEASE SEE WHIRLPOOL TUB SHOWN
 IN MIDDLE OF MASTER BEDROOM FLOOR IN
 UNIT C/17, E 4.8
  
 33)NOTE: AS PER 210-52, RAIL AREA IN
 BEDROOMS ON MULTI-LEVEL UNITS ARE
 CONSIDERED WALL SPACE. RECEPT RE`D.
  
 34)NOTE: PLEASE CLARFIY MEANS OF EGREES
 CONTROL COMING INTO S1(N) FROM HALL INTO
 LIVING ROOM.210-70
  
 35)NOTE: PLEASE CLARIFY METER CENTER "A"
 SHOWS 150A MAINS AND ONLY 7 V/33 UNITS?
  
 36)NOTE: PLEASE SHOW SPECS ON PANEL
 SCHEDULES. FEEDERS ARE NOTED AS 125A AND
 150ABUT PANELS DO NOT INDICATE SIZE
 ETC.
  
 37)NOTE: PLEASE NOTE, POOL WILL BE REQ`D
 TO BE UNDER SEPARATE PERMIT FOR STRUC/
 ELEC/PLUMB. PLEASE ALSO NOTE, A SEPARATE
 ELECTRCIAL WIRING DIAGRAM FOR PUMPS/
 HEATERS AND EQUIPMENT WILL BE REQ`D TO
 BE SUBMITTED W/ POOL PERMIT.
  
 38)NOTE:PLEASE NOTE, LIGHTNING PROTECT-
 -ION WILL BE REQ` TO BE UNDER SEPARATE
 PERMIT.
  
 39)NOTE: PLEASE NOTE; COLOR CODING OF
 FEEDERS TO BE PER LOCAL AMENDMENTS. 215
 277/480V
 BROWN/ PURPLE /YELLOW
 120/208V
 BLACK/RED/BLUE
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE DO NOT HESITATE TO CALL
 AND EITHER SET UP A MEETING TO GO OVER
 PLANS/COMMENTS ON PHONE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 561-805-6717
 [email protected]
  
 PLEASE SEE FIRE REVIEW COMMENTS THAT
 WILL HAVE AN AFFECT ON ELECTRICAL PLANS
 DUE TO THE REQUEST OF MORE EXIT/EM LTS.