Plan Review Notes
Plan Review Notes For Permit 03031778
Permit Number 03031778
Review Stop B
Sequence Number 1
Notes
Date Text
2003-04-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03031778
 ADD: 610 CLEMATIS ST
 CONT: WHITING -TURNER CONTRACTING
 TEL: (954)776-0800
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ARCH: B & A BERMELLO.AJAMIL &
 PARTNERS INC
 TEL: (305)859-2050
 FAX: (305)859-9638
  
 ENG:DER DE LOS REYE ENGINEERING INC
 TEL: (305)665-2778
 FAX: (305)665-2793
  
 BUILDING PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PROVIDE DOCUMENTATION OF UNITY OF
 TITLE, SECOND THAT THE CITY ABANDED THE
 ALLEY WAY.
  
 3)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 FOR THRESHOLD BUILDINGS FOR THE PER-
 MIT SET OF PLANS, PROVIDE (3) THREE COP-
 IES OF ALL DOCUMENTS, INCLUDING SHOP
 DRAWINGS, PRODUCT APPROVALS, LETTERS,
 ETC. EXCEPTION: THE STRUCTURAL CALCULA-
 TIONS (7 BOOKS).
  
 4) PLANS INDICATE THAT THIS BUILDING
 IS PLANNED TO BE A CONDOMINIUM. BEFORE
 THE BUILDING WILL RECEIVE A CERTIFICATE
 OF OCCUPANCY THE DOCUMENT " DECLARATION
 OF CONDOMINIMUM" IS TO BE SUBMITTED TO
 THE STATE, APPROVED AND THEN RECORDED
 AT THE COUNTY CLERK OF THE COURT. THE
 CITY WILL NEED TO HAVE A RECORDED COPY
 FOR OUR RECORDS, ADDRESSING AND NOTIFICA
 TION OF THE PROPERTY APPRAISERS OFFICE.
  
 5) AMENDMENTS TO APPENDIX F, FLORIDA
 BUILDING CODE, 2001 ED. LOCAL FIRE
 DISTRICT, SECTIONS 102- 105 SHALL APPLY
 TO THIS STRUCTURE. SEE ATTACHMENTS.
  
 6) CHAPTER 13, FLORIDA ENERGY CODE,
 SECTION 400, ENERGY CALCULATIONS FOR THE
 WHOLE BUILDING.
  
 7) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 PLEASE PROVIDE SOILS REPORT PREFORMED BY
 ARDAMAN & ASSOCIATES, GEOTECNICAL
 REPORT # 01-2233 BASED ON 10-01-02
 INVESTIGATION. (VIBROFLOTATION).
 3 SIGNED/ SEALED COPIES.
  
 8) REQUIREMENTS FOR SPECIAL FOUNDATION
 PERMIT:
 A) THRESHOLD INSPECTOR TO BE SIGNED ON
 WITH DON NEELY THRESHOLD/ RESIDENT
 INSPECTOR PROGRAM COORDINATOR @ EXT.
 6665.
 B) FILED SOILS REPORTS.
 C) PROVIDE THE DESIGN FOR SHEET PILE
 BY SPECILITY ENGINEER, TO BE REVIEWED
 BY & ACCEPTED BY THE ENGINEER OF RECORD
 ( HECTOR DE LOS REYES).
 D) COUNTY IMPACT FEES PAID FOR THE
 COMPLETE BUILDING.
 E) STATE RADON FEES TO BE PAID TO CITY.
  
 104.4.5. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT
 OR ENLARGE A BUILDING HAS BEEN FILED, &
 PENDING ISSURANCE OF SUCH PERMIT, THE
 BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR
 THE FOUNDATION ONLY, UPON WRITTEN RE-
 QUEST OF THE OWNER AND CONTRACTOR. THE
 HOLDER OF SUCH A SPECIAL PERMIT IS PRO-
 CEEDING AT HIS OR HER OWN RISK AND WITH-
 OUT ASSURANCE THAT A PERMIT FOR THE
 REMAINDER OF THE WORK WILL BE GRANTED
 AND THAT CORRECTIONS WILL NOT BE RE-
 QUIRED IN ORDER TO MEET THE PROVISIONS
 OF THE TECHNICAL CODE.
 *****FAIR HOUSING ACT*****
 9)THE PRIMARY ENTRY DOOR OF COVERED
 DWELLING UNITS IS PART OF PUBLIC AND
 COMMON USE SPACES, THEREFORE, IT MUST BE
 ON AN ACCESSIBLE ROUTE & BE ACCESSIBLE,
 I.E., MEET THE ANSI REQUIREMENTS OF
 4.13 DOORS.
 SHEET A-3-5AB,5BC & 5DA UNITS @ ELE.
 42', ENTRY VS, SECONDARY ENTRY DOORS,
 THE PLANS INDICATE THAT THE ENTRY (PRI-
 MARY) DOORS ARE TO THE EXTERIOR, THE
 PRIMARY DOORS ARE TO BE ON AN ACCESSIBLE
 ROUTE, THE COORIDOR ENTRY DOOR SINCE IT
 IS SERVED BY AN ELEVATOR. LEVER HANDLE
 OR OTHER EASY TO USE DOOR HARDWARWE,
 ANSI 4.13.9.
  
 10) A-3.1AB/ A-3.1BC LOWER BASEMENTS,
 NOT ON A ACCESSIBLE ROUTE, PLANS DO NOT
 INDICATE SIGNAGE "NOT ACCESSIBLE ROUTE".
  
 11) POOL, POOL DECK AND SURROUNDING
 AREAS ARE TO BE ACCESSIBLE. NO INFORMA-
 TION IS PROVIDED FOR THIS AREA.
  
 12)FAIR HOUS REGUIREMENT 7.2 USEABLE
 BATHROOMS(I) NOTE: CABINETS UNDER LAVA-
 TORIES ARE ACCEPTABLE PROVIDED THE BATH-
 ROOM HAS SPACE TO ALLOW A PARALLEL
 APPROACH BY A PERSON IN A WHEELCHAIR;
 IF PARALLEL APPROACH IS NOT POSIBLE WITH
 IN THE SPACE, ANY CABINETS PROVIDED
 WOULD HAVE TO BE REMOVABLE TO AFFORD THE
 NECESSARY KNEE CLEARENCE FOR FORWARD
 APPROACH.
  
 13) POOLS ARE TO HAVE AN EFFICTIVE
 BARRIER ( PUBLIC POOLS DOH RULE 64E-9
 FL ADMINISTRATIVE CODE) INDICATE WHERE
 THIS WILL BE AN ACCESSIBILITY THROUGH
 THE ENCLOSURE?
 IF CONCIDERED A PRIVATE POOL SEE SEC-
 TION 424.2.17.(1) -(8).
  
 14) SHEET A-3-5DA CORRIDOR 154 LEVEL 42
 (NORTH) INDICATES THE USAGE OF RAMPS BUT
 NO ELEVATIONS ARE PROVIDED?
 *****GENERAL BUILDING COMMENTS******
 15) IT IS DIFFICULT TO DO PLAN REVIEWS
 WITHOUT A LEGEND INDICATING WHAT TYPE
 OF INFORMATION IS BEING RELAYED THE
 BOX WITH A NUMBERIN IT???????ALL PAGES!
  
 16) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 17)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 18)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) FIXED WINDOWS INCLUDING STORE FRONT
 B) SINGLE HUNG WINDOWS
 C) MULLIONS VERTICAL & HORIZONTAL
 D) EXTERIOR GLAXED DOORS BOTH SWINGING
 AND SLIDING DOORS.
 E) SOLID EXTERIOR DOORS
 F) EXTERIOR DOORS W/ TRANSOMS (1 UNIT)
 G) OVERHEAD GARAGE DOOR
 H) LOUVERED VENTS
 I) ROOFING ASSEMBLIES:(II) ROOF TILE
 (III) FLAT ROOF W/ INSULATION
  
 COMMENTS TO BE CONTINUED ON THE NEXT
 PENTIMATION BUILDING REVIEW SESSION!!!!