2003-04-03 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SIZE FEEDERS PER 310-15
 SHOWN AS #2? MISPRINT?
  
 2)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITSON PANEL SCHEDULE.
 210-12
  
 3)NOTE: PLEASE SEE MISSING RECEPT FOR
 KITCHEN COUNTERSPACE PER 210-52-C-1
  
 4)NOTE: PLEASE MOVE SD FROM HALLWAY
 INTO BEDROOM. NFPA-72 8-1.4.2
  
 5)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS
 ON PLANS.
  
 NO INFORMATION SHOWN FOR PANELS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QESTIONS,
 PLEASE CALL.
  