Plan Review Notes For Permit 03031730 |
Permit Number |
03031730 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-04-03 00:00:00 | ***************** UNSAT **************** | | | | 1)NOTE: PLEASE SIZE FEEDERS PER 310-15 | | SHOWN AS #2? MISPRINT? | | | | 2)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | PROTECTED CIRCUITSON PANEL SCHEDULE. | | 210-12 | | | | 3)NOTE: PLEASE SEE MISSING RECEPT FOR | | KITCHEN COUNTERSPACE PER 210-52-C-1 | | | | 4)NOTE: PLEASE MOVE SD FROM HALLWAY | | INTO BEDROOM. NFPA-72 8-1.4.2 | | | | 5)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS | | ON PLANS. | | | | NO INFORMATION SHOWN FOR PANELS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|