Date Text
2003-05-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS. SECOND FLOOR BATHROOM
 SHALL NOT DRAIN INTO THE VENT FOR THE
 WASH MACHINE. NO DRY HORIZONTAL VENTS.
 D/W SHALL DRAIN INTO DRAIN FOR KIT SINK
 NOT DIRECTLY INTO STACK. NO TRAPS UNDER-
 GROUND FOR W/C'S. UNVENTED FIXTURES ECT.
 ---- PLEASE SEE ATTACHED SANITARY RISER
 DIAGRAM AS AN EXAMPLE OF A SANT. RISER
 THAT REFLECTS THE FLOOR PLAN AND MEETS
 CODE REQUIREMENTS.---------
  
 REVIEW BY KEN STEVENS